3BDS009029R5001 B
Calculation of a bus length against of two transmission rates:
A transmission rate of 3 Mbit/s shall be used. The transmission rates in the table
close to this value are 1.5 Mbit/s with l
1,5Mbit/s
and 12 Mbit/s with l
12Mbit/s
. Thus,
you can calculate the line length l
3Mbit/s
:
RS485 network limits
Up to 32 nodes (master and slaves) can be grouped in a single segment. When using
more than 32 nodes, several segments linked to each other through repeaters (power
amplifiers) are needed. Note that the repeater has to be considered as another bus
node, since the integrated bus drivers are an additional load on the bus. It is
recommended to use not more than three series-connected repeaters on a line.
However, the number of repeaters in a single PROFIBUS network is limited to 9.
The maximum admissible distance between two bus stations in each PROFIBUS
network can be calculated as follows:
(Number of re 1) * Segment length
Number of repeater = The maximum number of repeaters connected in series.
Example:
The repeater manufacturer’s specifications allow nine repeaters to be
connected in series.
The maximum distance between two bus stations at a data transfer rate of 1500
kbit/s is then as follows:
=> (9 + 1) * 200 m = 2000 m
l
3Mbit/s
:
l
1.5Mbit/s
+ 3Mbit/s - 1.5Mbit/s
(
)
l
1.5Mbit/s
-
l
12Mbit/s
1.5Mbit/s - 12Mbit/s
-------------------------------------------------
×
l
3Mbit/s
185m
≈
=
Содержание AC 800M
Страница 1: ...Power and productivity for a better worldTM AC 800M PROFIBUS DP Installation System Version 5 0 5 1...
Страница 2: ......
Страница 3: ...AC 800M PROFIBUS DP Installation System Version 5 0 5 1...
Страница 8: ...Table of Contents 8 3BDS009029R5001 B...
Страница 16: ...Released User Manuals and Release Notes About This User Manual 16 3BDS009029R5001 B...
Страница 29: ...Section 2 Transmission Technology RS485 network limits 3BDS009029R5001 B 29 Figure 2 RS485 network limits...
Страница 56: ...Calculation of transmission delay time TTD Section 2 Transmission Technology 56 3BDS009029R5001 B...
Страница 116: ...Updates in Revision Index B 116 3BDS009029R5001 B...
Страница 117: ......