A B B U PS PRODUC TS A N D SOLUTI ON S
The
PowerValue 11 RT G2 6-10 kVA
is designed,
manufactured and commercialized in accordance
with the
EN ISO 9001
standard relating to quality
management systems.
These products conform with the
following directives:
• 2014/35/EU Low voltage directive
• 2014/30/EU Electromagnetic Compatibility
directive (EMC)
• 2011/65/EU Restriction of the use of certain
hazardous substances (RoHS) directive
Inquiries regarding the UPS should be
addressed to the local ABB office or agent
authorized by ABB. Note the type code and
the serial number of the equipment before
contacting ABB or authorized agent. The
serial number is shown on the nameplate
of the product. For further information on
troubleshooting, see Chapter 6.
—
1 .3 Declaration of safety conformity and CE marking
WARNING
DO NOT DISCONNECT THE MAINS CABLE
FROM THE UPS OR THE BUILDING WIRING
SOCKET DURING OPERATION AS THIS
REMOVES THE GROUND FROM THE UPS
AND ALL CONNECTED LOADS.
NOTE
PRESS THE OFF BUTTON TO FULLY
DISCONNECT THE UPS. ENSURE THE UPS IS
ON BYPASS OR ON STANDBY MODE BEFORE
DISCONNECTING IT FROM THE MAINS.
NOTE
TO REDUCE THE RISK OF FIRE, CONNECT
THE UPS TO A CIRCUIT PROVIDED WITH
BRANCH CIRCUIT OVERCURRENT
PROTECTION WITH AN AMPERE RATING IN
ACCORDANCE WITH THE IEC/EN 60934
STANDARD OR YOUR LOCAL ELECTRICAL
CODE.
SEE TECHNICAL SPECIFICATIONS FOR
RECOMMENDATIONS.
WARNING
INDISCRIMINATE OPERATION OF
SWITCHES MAY CAUSE OUTPUT LOSS
OR DAMAGE TO EQUIPMENT.
WARNING
NEVER DISPOSE OF BATTERIES IN A FIRE
AS THEY MAY EXPLODE.
WARNING
DO NOT OPEN OR DAMAGE
THE BATTERIES.
WARNING
RELEASED ELECTROLYTE IS HARMFUL
TO THE SKIN AND EYES.
—
1 .5 Operation
—
1 .4 Inquiries
These products also meet the following
product standards:
—
Table 1: Standards
Product Standards
Safety
IEC/EN 62040-1:2008+A1:2013
EMC
IEC/EN 62040-2:2006
Performance
IEC/EN 62040-3
ESD
IEC 61000-4-2: Level 3
Radiated field
IEC 61000-4-3: Level 3
EFT
IEC 61000-4-4: Level 4
Fast transients
IEC 61000-4-5: Level 4
Electromagnetic field
IEC 61000-4-6: Level 3
Conducted magnetic field
IEC 61000-4-8: Level 4
RoHS
IEC/EN50581:2012