30
A B B U PS PRODUC TS A N D SOLUTI ON S
A USB and an RS-232 port are available to enable
the communication between the UPS and a
remote computer/ station. Only one
communication port can be active at a time
and the priority is given to the USB port.
Once the communication cable is installed,
the power management software can exchange
information with the UPS. The software collects
information from the UPS and indicates the
status of the device, the power quality of the
mains and the battery autonomy of the units.
If there is a power failure and a predicted
shutdown of the UPS due to low battery
autonomies, the monitoring system can save
the load data and initiate shutdown of the
equipment connected to the UPS.
—
5 Communication
The UPS has an RS-232 port for UPS monitoring,
control and firmware updates. To establish
communication between the UPS and a computer,
connect one end of the serial communication
cable to the RS-232 port on the UPS and the other
end to the RS-232 port of a computer.
The cable pins for the RS-232 communication
port are described in “Figure 30” and “Table 11”.
—
5 .1 RS-232 port
—
30 RS-232
Communication Port
(DB-9 Connector)
—
Table 11: Communication port pin assignment
PIN
Signal Name
Function
Direction
from UPS
1
DCD
Battery low signal
Out
2
TxD
Transmit to
external device
Out
3
RxD
Receive from
external device
In
4
DTR
PnP from
external device
In
5
GND
Signal common
--
6
DSR
To external device
Out
7
RTS
No connection
In
8
CTS
On battery signal
Out
9
RI
V
DC
power
Out
—