12.1.8
Technical data
Table 213:
SESRSYN (25) technical data
Function
Range or value
Accuracy
Phase shift,
j
line
-
j
bus
(-180 to 180) degrees
-
Voltage ratio, V
bus
/V
line
0.500 - 2.000
-
Reset ratio, synchronism check
> 95%
-
Frequency difference limit
between bus and line for
synchrocheck
(0.003-1.000) Hz
± 2.0 mHz
Phase angle difference limit
between bus and line for
synchrocheck
(5.0-90.0) degrees
± 2.0 degrees
Voltage difference limit between
bus and line for synchronizing and
synchrocheck
0.03-0.50 p.u
± 0.5% of V
n
Time delay output for synchronism
check
(0.000-60.000) s
± 0.5% ± 25 ms
Frequency difference minimum
limit for synchronizing
(0.003-0.250) Hz
± 2.0 mHz
Frequency difference maximum
limit for synchronizing
(0.050-0.500) Hz
± 2.0 mHz
Maximum allowed frequency rate
of change
(0.000-0.500) Hz/s
± 10.0 mHz/s
Closing time of the breaker
(0.000-60.000) s
± 0.5% ± 25 ms
Breaker closing pulse duration
(0.050-60.000) s
± 0.5% ± 25 ms
tMaxSynch, which resets
synchronizing function if no close
has been made before set time
(0.000-60.000) s
± 0.5% ± 25 ms
Minimum time to accept
synchronizing conditions
(0.000-60.000) s
± 0.5% ± 25 ms
Time delay output for energizing
check
(0.000-60.000) s
± 0.5% ± 25 ms
Operate time for synchronism
check function
40 ms typically
-
Operate time for energizing
function
100 ms typically
-
1MRK 502 048-UUS A
Section 12
Control
361
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...