14
Installation and maintenance guide
1ZSC000563-ACD EN, REV. A, 2019-06-25
4.3 Installation of the test adapter, 1ZSC003881-AAC
Overview
G006815
1
Cover
4
Test adapter, 1ZSC003881-AAC
DANGER!
Risk of death to personnel!
Make sure that the bushing is de-energized and out of service.
Make sure that the high-voltage parts are visibly grounded, before removing the cover on the tap.
CAUTION!
Do not energize the bushing without a test adapter (4) or the cover (1) installed. The bushing is
grounded through the test adapter (4) or cover (1) and this prevents damage to the bushing.
Procedure
1.
Remove the cover (1).
G000773