20
Installation and maintenance guide
1ZSC000563-ACD EN, REV. A, 2019-06-25
2.
With the screws (5), adjust the nut (2) to a
distance of 1,5 mm (±0,5 mm) from the terminal
box (4).
G005030
3.
Apply Mobilgrease 28 to the O-ring (3), and put it
in the groove (7) in the terminal box.
CAUTION!
Do not remove the plug (11) until the
measuring circuits are installed.
Moisture will enter the terminal box.
G001914
4.
Install the test adapter (8).
G001917