2600T Series Pressure transmitters | 

OI/266/LowP-EN Rev.A   15

6 Transmitter wiring

6.3 Supply requirement

For signal connection use, wiring n

o

 18 to 22 AWG / 0.8 to 

0.35mm

2

 ø up to 164 feet (50 meters). Longer loops require 

larger wire. For power connection use, wiring n

o

 18 to 22 AWG 

/ 0.8 to 0.35mm

2

.

The 1 to 5 V dc output signal and the dc power supply to the 
transmitter are separated.

The supply voltage at the transmitter terminals must be 
between the limits of 8 and 30 V dc.

For Ex ia approval power supply must not exceed 30 Vdc. 

For maximum power supply voltage please refer to the top 
identification plate of the transmitter.

6.4 Wiring procedure

Follow these steps to wire the transmitter:

  — Remove the temporary plastic cap from one of the two    
    electrical connection ports located at   both sides in the    
    upper part of the transmitter housing.

  — These connection ports may have a 1/2 inch internal NPT  
    or M20 threads. Various adaptors and bushings can be    
    fitted to these threads to comply with plant wiring  

 

    (conduit) standards.

  — Remove the housing cover of the “field terminals” side.    
    See the indication on the label on top of the housing.  

 

    In an Explosion-Proof/Flame-Proof installation, do not  

 

    remove the transmitter covers when power is applied to    
    the unit.

  — Run the cable through the cable gland and the open port.

  — Connect the POWER supply, the positive lead to the  

 

    PWR+ terminal, and the negative lead to the  

 

 

    PWR– terminal.

  — Connect the signal_out 1-5V, the positive lead to the  

 

    Vout/COMM+ terminal and the negative lead to the  

 

    PWR– terminal.

  — Plug and seal the electrical ports. Make sure that when    
    the installation has been completed, the electrical ports    
    are properly sealed against entry of rain and/or corrosive   
    vapors and gases.

Warning - General risks.

 Cable, cable gland and unused port plug 

must be in accordance with the intended type of protection (e.g. 
intrinsically safe, explosion proof, etc.) and degree of protection 
(e.g. IP6x according to IEC EN 60529 or NEMA 4x). See also the 
addendum for “EX SAFETY” ASPECTS AND “IP” PROTECTION. In 
particular, for explosion proof installation, remove the red temporary 
plastic cap and plug the unused opening with a plug certified for 
explosion containment

 — 

If applicable, install wiring with a drip loop. Arrange the    

    drip loop so the bottom is lower than the conduit  

 

    connections and the transmitter housing. 

 — 

Put back the housing cover, turn it to seat O-ring into the  

    housing and then continue to hand tighten until the cover  
    contacts the housing metal-to-metal. In Ex-d (Explosion   
    Proof) installation, lock the cover rotation by turning the   
    set nut (use the 2mm Allen key supplied with the  

 

   instrument).

Содержание 266HSH

Страница 1: ...2600T Series Pressure Transmitters 266HSH Model Low Power Consumption 1 5 V DC Operating Instruction OI 266 LowP EN Rev A Engineered solutions for all applications Measurement Made Easy...

Страница 2: ...ns As a part of ABB a world leader in process automation technology we offer customers application expertise service and support worldwide We are committed to teamwork high quality manufacturing advan...

Страница 3: ...dard instruments 13 6 Transmitter wiring 14 6 1 Cable connection 14 6 2 Analogue output HART transmitter wiring 14 6 3 Supply requirement 15 6 4 Wiring procedure 15 6 5 Grounding 16 6 6 Surge protecto...

Страница 4: ...g from the receipt of the transmitter and its identification passing to the installation to the electrical connections to the configuration and to the troubleshooting and maintenance operations 1 2 Mo...

Страница 5: ...se of adequate safety systems For safety reasons ABB draws your attention to the fact that only sufficiently insulated tools conforming to DIN EN 60900 may be used Since the transmitter may form part...

Страница 6: ...EE Directive 2002 96 EC or corresponding national laws e g the ElektroG Electrical and Electronic Equipment Act in Germany Dispose of the product solution directly at a specialist recycling facility d...

Страница 7: ...2600T Series Pressure transmitters OI 266 LowP EN Rev A 7 3 Transmitter overview 3 Transmitter overview 3 1 Transmitter components overview Figure 1 Gauge pressure transmitter components...

Страница 8: ...nsor The lowest value of the measured value that the transmitter can be adjusted to measure URV Upper Range Value The highest value of the measured value to which the transmitter is calibrated LRV Low...

Страница 9: ...ctronics housing as standard Option I2 allows to select these plates as metal AISI 316 ss fastened to the electronics housing with rivets or screws The instrument may be used as a pressure accessory c...

Страница 10: ...bodies including water 6 means that the housing is protected against water specifically powerful jets of water under standardized conditions 7 means that the housing is protected against water specif...

Страница 11: ...pressure on the measuring diaphragm resulting in a zero shift In such an event the zero point can be corrected via the set PV to zero command Please refer to the configuration section for further det...

Страница 12: ...71 16 0 63 108 4 25 52 2 05 27 1 06 width across flats Figure 7 Model 266HSH with 1 2 14 NPT male process connection and barrel housing installed on a 2 pipe with optional bracket B6 carbon steel or B...

Страница 13: ...ipes must be as short as possible and free from sharp bends Lay the impulse piping in such a way that no deposits accumulate in them Gradients should not be less than approx 8 ascending or descending...

Страница 14: ...out Voltmeter 1 2 5 4 3 6 HART hand held communicator may be connected or between the terminals Vout COMM and PWR or at the terminal blocks of the voltmeter Figure 10 HART transmitter connection schem...

Страница 15: ...overs when power is applied to the unit Run the cable through the cable gland and the open port Connect the POWER supply the positive lead to the PWR terminal and the negative lead to the PWR terminal...

Страница 16: ...d is direct connection to earth ground with impedance equal or less of 5 ohm Figure 11 Ground connection on transmitter housing 6 6 Surge protector equipped terminal block optional The pressure transm...

Страница 17: ...on the sums of the capacitances and inductances of all circuits including the transmitter see EC type examination certificate must be equal to or less than the permissible capacitances and inductances...

Страница 18: ...ly the pressure for the lower range value and upper range value to the measuring equipment Make sure that the measuring limits are not exceeded Important Reducing station with adjustable pressure and...

Страница 19: ...Select Select submenu parameter Edit Edit parameter Ok Save selected parameter and display stored parameter value 8 6 HMI as feedback of the local push button operations As consequence of the operati...

Страница 20: ...selections are available Linear Custom Linearization Curve Cylindrical Lying Tank and Spherical Tank This submenu allows user to set the display view One or two lines with our without bargraph are the...

Страница 21: ...is High 5 4V on 1 position the output is Low 0 94V Write lock switch 4 If the user wants to protect the configuration from unauthorized writing dip switch 4 has to be moved up in 1 position 8 9 Dampi...

Страница 22: ...herical tank The transmitter calculates the volume from the measured filling level 8 11 Configuration with the PC or HHT The 266 transmitters can be configured by either one of the following device Ha...

Страница 23: ...ed error messages Error message Tx LCD message Possible cause Suggested action Tx response F120 016 Sensor Invalid The sensor signal is not being updated correctly as a result of an electronics failur...

Страница 24: ...and process conditions has to be checked A different transmitter type could be required no effect F102 004 P dP Out Of Limits The measurement range has not been correctly calculated OR an incorrect t...

Страница 25: ...part with an original spare part Please contact your local ABB office for spare parts support information or refer to the spare part list The use of non original spare parts makes the warranty void I...

Страница 26: ...FM Approvals for the following Class Divisions and Gas groups hazardous classified locations temperature class and types of protection Explosionproof US for Class I Division 1 Groups A B C and D hazar...

Страница 27: ...N DANGEROUS FLUIDS In case of toxic or otherwise dangerous fluid please attach the relevant Material Safety Data Sheet Trouble found during Installation Commissioning Maintenance At start up On servic...

Страница 28: ...dismantle without any special precautions Material s which have been in contact with this equipment C If A or B are not applicable full instructions for the safe handling of this equipment for dispos...

Страница 29: ...2600T Series Pressure transmitters OI 266 LowP EN Rev A 29 Intentionally blank...

Страница 30: ...30 OI 266 LowP EN Rev A 2600T Series Pressure transmitters Intentionally blank...

Страница 31: ...level transmitters ABB s portfolio of device management Fieldbus and wireless solutions Scalable asset device management Asset vision software Mobility handhelds Customer support We provide a comprehe...

Страница 32: ...us Note We reserve the right to make technical changes or modify the contents of this document without prior notice With regard to purchase orders the agreed particulars shall prevail ABB does not acc...

Отзывы: