- 27 -
Fig. 4 - ConF METER menu
ConF
METER
ENTER
ConF
AUTO
ESC
ENTER
ESC
. . . *
LOADING
NEXT
PREV
ENTER
NEXT
PREV
ConF
UPDATE?
ConF
VIEW ?
ESC
ESC
ESC
0.000
ZERO
40.000
FULL SC
KPA
ConF
MANUAL
OUTPUT
LINEAR
SQR
ESC
ENTER
NEXT
PREV
NEXT
PREV
4000
ZERO
04000
04000
04000
00000
00000
ZERO
20000
FULL SC
20000
FULL SC
20000
20000
20000
20000
NEXT
PREV
NEXT
PREV
ENTER
ESC
ENTER
ESC
ENTER
ESC
ENTER
ENTER
ESC
ENTER
ESC
ENTER
UNITS
NEXT
PREV
KPA
TORR
ATM
MPA
IN H2O
KG / CM2
ENTER
NEXT PREV
NEXT PREV
ENTER
ENTER
NEXT
PREV
NEXT
PREV
NEXT
PREV
ENTER
ConF
CURRENT
ConF
UPDATE?
ConF
PERCENT
ESC
ENTER
ENTER
ConF
PASSWD
NEXT
PREV
NEXT
PREV
ESC
ENTER
LINEAR
ConF
UPDATE ?
SQR
ESC
ENTER
NEXT
PREV
01234
PASSWD
00000
01000
01200
01230
ENTER
ESC
UPDATE?
ESC
ENTER
ESC
ENTER
ENTER
ENTER
NEXT
PREV
NEXT
PREV
ESC
ConF
OK
ENTER
ESC
NEXT
PREV
NEXT
PREV
UPDATE ZERO,
FULL-SCALE
AND UNIT
SET 4
÷
20 mA
INDICATION
SET 0
÷
100% INDICATION
(WITH OR WITHOUT
SQUARE ROOT)
UPDATE NEW
PASSWORD
ADDENDUM FOR COMETER OR INDICATOR WITH HART PROGRAMMING CAPABILITY
AND PROMETER - PROGRAMMABLE INDICATOR
COMETER ONLY
COMETER and PROMETER
The other options under ConF METER menu are:
ConF AUTO
By selecting this option, the CoMeter is automatically updated
with the LRV, URV and Unit of the HART transmitter connected.
Before accepting the transmitter configuration by pressing
ENTER at the request "ConF UPDATE?", it is possible to view
the LRV (ZERO), the URV (FULL SC) and the UNIT.
If the output transfer function of the transmitter is not linear,
ProMeter and CoMeter show the message: ConF NO_LIN and
the user cannot update the configuration.
It is necessary to change the output transfer function of the
transmitter to linear.
See Fig. 4 - "ConF METER" menu, for ConF AUTO procedure.
ConF MANUAL
The selection of MANUAL configuration allows the user to
define manually CoMeter and ProMeter configuration, i.e.
define the LRV (ZERO), the URV (FULL SC), and the UNIT, as
well as to decide for a LINEAR on SQR output function. LRV
and URV can have a value between -99999 and +99999.
Refer to Fig. 4 - ConF METER menu for detail on the procedure.
For having the CoMeter to display the analog output current or
the output percentage, select respectively:
ConF CURRENT and ConF PERCENT