- 16 -
. . . ELECTRICAL CONNECTIONS
WARNING : DO NOT ATTEMPT TO CONNECT
AN AMPEROMETER BETWEEN A "TEST" TERMINAL
AND A "COMM" TERMINAL. THE RESULT TO THE
POWER SUPPLY IS A SHORT WHICH WILL BLOW
FUSES AND POSSIBLY DAMAGE YOUR EQUIPMENT,
ALSO CAUSING TO INTERRUPT FUNCTION OF
OTHER DEVICES POWERED FROM SAME SUPPLY.
NOTE: If the use of the Hand Held Communicator is
foreseen, a resistance of 250 ohms minimum must be
included in the current loop, between the power supply and
the connection point of the Hand Held Terminal, for
communication purpose.
Here below is given an explanation regarding the possible
connection of the terminal block to the power supply and a
representation of the connection in case of remote indicator
presence (See fig. 8b and 8c).
Fig. 8b - Electrical connections
Fig. 8c - Electrical connections with remote indicator
+
+
-
-
+
+
-
-
Line load
GND
Hand-held
communicator
Power
source
Optional
Receiver
Test points
4-20 mA
250 ohm min
Internal ground
termination point
691HT
A B C
1
D E F
2
G H I
3
J K L
4
M N O
5
P Q R
6
S T U
7
V W X
8
Y Z #
9
@ %
& /
0
+
-
PV
REVIEW
SERIAL
LINK
TRIM
F1
F2
F3
F4
CONF
External ground
termination point
M
TEST COMM
+
+
-
-
+
+
-
-
Line load
GND
Hand-held
communicator
Power
source
Optional
Receiver
Test points
4-20 mA
250 ohm min
Internal ground
termination point
Remote indicator
691HT
A B C
1
D E F
2
G H I
3
J K L
4
M N O
5
P Q R
6
S T U
7
V W X
8
Y Z #
9
@ %
& /
0
+
-
PV
REVIEW
SERIAL
LINK
TRIM
F1
F2
F3
F4
CONF
External ground
termination point
M
Kent-Taylor
0
4
3
5
6
7
8
9
10
20
40
0
60
100
%
2
80
M+
-
TEST COMM
Model 691HT Communicator
may be connected at any wiring
termination point in the loop,
providing the minimum
resistance is 250 ohm.
If this is less than 250 ohm,
additional resistance should be
added to allow communications.