50/54
TLE Scalable Series 40 to 150 UL S1
UPS Installation Guide / REV-B
5.3
“3-ph SNMP/WEB plug-in adapter” board
Fig. 5.3-1 “3-ph SNMP/WEB plug-in adapter” board
3-ph SNMP/WEB plug-in adapter
SNMP - Simple Network Management Protocol
The “3-ph SNMP/WEB plug-in adapter” is an interface to
the Ethernet Network and provides UPS information via
the standard SNMP Protocol (UPS-MIB (RFC-1628); Single
MIB; Parallel MIB).
The UPS can therefore be monitored by a Network
Management System (NMS) or by our applications (for
instance iUPSGuard or Data Protection), which uses this
information to determine the state of the UPS in order to
guarantee safe and orderly shut-down of the server, when
needed.
For additional information about “3-ph SNMP/WEB plug-in adapter” card configuration and functionalities,
please refer to “3-ph SNMP/WEB plug-in adapter” manual included into CD-Rom.
5.4
“IM0305 - UVR control” board for CB3 Battery Breaker Box
Fig. 5.4-1 “IM0305 - UVR Control” board
“IM0305 – UVR Control” board
The “IM0305 - UVR Control” board
allows the remote control of the
external “CB3 Battery Breaker” (option).
Insert the “IM0305 - UVR Control” board
into “CONN4 slot” of the Connectivity
Slots, see Fig. 9.4-1 and Fig. 9-1/2.
The “IM0305 - UVR Control” board must
be blocked with the 2 screws “A”.
Max. rating J2 terminals:
AWG14
/
2.5mm
2
.
OPT
_SN
MP Ca
rd_0
1
IM0305
UVR Control Board
3 (-)
1 (+)
J2
Conn 4
slot
A
TLE
S_U
L_0
40-
150
_S1
_UP
S-IM
0305
_AB
B_01
E
PO
E
PO
-
+
XA
Q1
I ON
0
OF
F
POWER MODULE 1
POWER MODULE 2
POWER MODULE 3
J35µP -
RS232
A