Refer to Figure 2-3 for recommended piping arrangement and Figure 2-5 for proper gasket locations.
If a throttling valve is required, it is strongly recommended that it be placed downstream of the meter.
Upstream valves can create turbulence that result in undesirable air pockets and may affect the
meter’s accuracy or cause its output to be noisy.
FIGURE 2-5. GASKET LOCATIONS
10DS3111A INSTRUCTION MANUAL
2-6