Manual Corrigo Ventilation, revision R
Chapter 17
Configuration
95
Alarm text
Pri Description
30
Fire damper is out of
operation
B
Fire damper exercise test failed
31
Supply Air Fan control error
-
Supply air pressure deviates too much from
the setpoint for too long.
32
Extract Air Fan control error
-
Extract air pressure deviates too much from
the setpoint for too long.
33
Supply Air Fan external
operation
C
SAF run-signal received when unit is
stopped
34
Extract Air Fan external
operation
C
EAF run-signal received when unit is
stopped
35
Ventilation Manual mode
C
The unit is in manual mode
36
Manual supply air control
C
Supply air temp controller in manual control
37
Manual supply Air Fan mode C
Supply air fan in manual control
38
Manual Supply Air
C
The SAF is in manual mode
39
Manual Extract Air Fan mode C
Extract air fan in manual control
40
Manual Extract Air
C
The EAF is in manual mode
41
Manual Heater Control
C
The heater is in manual mode
42
Manual exchanger control
C
Heat exchanger output in manual control
43
Manual cooler control
C
Cooling output in manual control
44
Manual P1-Heater
C
Heating circulation pump in manual control
45
Manual P1-Exchanger
C
Exchanger circulation pump in manual
control
46
Manual P1-Cooler
C
Cooling circulation pump in manual control
47
Fire damp. Manual
C
Fire dampers in manual control
48
Internal battery error
A
Internal battery needs replacing
49
Sensor error Supply Air temp B
Malfunction of connected sensor
50
Sensor error Extract Air temp B
Malfunction of connected sensor
51
Sensor error Room temp 1
B
Malfunction of connected sensor
52
Sensor error Room temp 2
B
Malfunction of connected sensor
53
Sensor error Exhaust air temp B
Malfunction of connected sensor
54
Sensor error Extra sensor
B
Sensor error Extra sensor 1
55
Sensor error SAF pressure
B
Malfunction of connected sensor
56
Sensor error EAF pressure
B
Malfunction of connected sensor
57
Sensor error Deicing temp
B
Malfunction of connected sensor
58
Sensor error Frost Protection
temp
B
Malfunction of connected sensor
59
Sensor error CO
2
B
Malfunction of connected sensor
60
Sensor error Humidity Room B
Malfunction of connected sensor
61
Sensor error Humidity Duct
B
Malfunction of connected sensor
62
Sensor error Extra unit temp
B
Malfunction of connected sensor
63
Sensor error External control
SAF
B
Malfunction of connected sensor
64
Sensor error External control
EAF
B
Malfunction of connected sensor
65
Sensor error SAF Pressure 2
B
Malfunction of connected sensor
66
Sensor error Humidity
outdoor
B
Malfunction of connected sensor