Manual Corrigo Ventilation, revision R
Chapter 3
Installation and wiring
19
Analogue output signal
Description
E tool
©
Display
Inactive output
Not used
Not used
Y1 Actuator Heating
Heating Y1
Y1-Heating
Y2 Actuator Exchanger
Exchanger Y2
Y2-Exchanger
Y3 Actuator Cooling
Cooling Y3
Y3-Cooling
Frequency converter, supply air fan
SAF
SAF
Frequency converter, extract air fan
EAF
EAF
Actuator Humidity control
Dehumidification/
Humidification
Humidity
Split of any one of temp outputs Y1, Y2,
Y3 or Y1 Heating/Y3 Cooling outputs
Split
Sequence
Extra controller
Extra unit control
ExtraUnitCtrlVa
Y1 Heating / Y3 Cooling, Change-over
output
Y1 Heating/Y3 Cooling
Y1-Heat/Y3-Cool
Y4 Extra Sequence
Also used for control of recirculation air
damper 0...10V
Extra Sequence Y4
Y4-extra sequence
Y5 Extra Sequence
Extra Sequence Y5
Y5-extra sequence
Digital output signal
Description
E tool
©
Display
Inactive output
Not used
Not used
Start/stop Supply air fan Normal
SAF Start 1/1 Normal Speed
SAF 1/1-speed
Start/stop Extract air fan Normal
EAF Start 1/1 Normal Speed
EAF 1/1-speed
Start/stop Supply air fan Reduced
SAF Start 1/2 Reduced Speed SAF 1/2-speed
Start/stop Extract air fan Reduced
EAF Start 1/2 Reduced Speed EAF 1/2-speed
Start/stop circulation pump, heating
Heating Pump Start
P1-Heating
Fire damper
Fire Damper
Fire damper
Sum alarm A- and B-alarm
Sum Alarm
Sum alarm
Sum alarm A-alarm
Sum Alarm A
A-sum alarm
Sum alarm B-alarm
Sum Alarm B
B-sum alarm
Start/stop circulation pump, cooling
Cooling Pump Start
P1-Cooling
Start/stop circulation pump, liquid
exchanger
Exchanger Start
P1-Exchanger
Activation-signal SAF frequency
converter
SAF Freq Start
SAF-frequence
Activation-signal EAF frequency
converter
EAF Freq Start
EAF-frequence
Activate heating
Heating Activate
Heat start
Activate cooling
Cooling Activate
Cool start
Activate exchanger
Exchanger Activate
Exch start
Exhaust air close-off damper
Exhaust Air Damper
Exhaust air d
Fresh air close-off damper
Outdoor Air Damper
Fresh air dam