Publication 1738-IN002B-EN-E - November 2004
4
ArmorPoint 24V dc Input Modules, Series A
Mount the I/O Base
To mount the base on a wall or panel, use the screw holes provided
in the base.
A drilling dimensions mounting illustration for the base with an
adapter is shown below.
Install the mounting base as follows:
1.
Lay out the required points as shown in the drilling dimension
drawing.
2.
Drill the necessary holes for #8 (M4) machine or self-tapping
screws.
3.
Mount the base using #8 (M4) screws.
4.
Ground the system using the ground lug connection. (The
ground lug connection is also a mounting hole.)
IMPORTANT
The module must be mounted on a grounded metal
mounting plate or other conductive surface.
43769
4.02 in.
102 mm
1.81 in.
46 mm
Adapter
1.9 in.
47.2 mm
2.0 in.
50 mm
0.87 in.
22 mm
2.0 in.
50 mm
0.87 in.
22 mm
2.0 in.
50 mm
Drilling Dimensions
Ground lug connection
Latching mechanism
Mounting base
43675