5.3 Setting the control parameters and identification mode of doors

 

After entering the programming mode enter the code 

21

, then:

 

• 

value from 

00

 to 

99

 seconds (default 

-

 3 sec.)

 

This is the time by which, when a valid card or code is used the door will be 

 

unlocked.

 

After entering the programming mode enter the code identification mode:

 

• 

221

 

-

 Card only

 

• 

222 

-

 Card + PIN

 

• 

223 

-

 PIN only

 

• 

224

 

-

 Card or PIN

 

6. User Management

 

In standalone mode can be added up to 2000 users. Each user must be assigned 

with ID from 0000 to 1999 in the programming process and then assigned ac-

cess card number read by the reader. This allows the system administrator can 

remove the user from the database without the need a card (which can be erg. 

lost), knowing only the user's ID code. Cards added in standalone mode have full 

access to the passage (24 hours a day, 7 days a week). In contrast to the added 

cards from the program, which can be assigned to a limited level of access. To 

avoid the need for dual record cards and disadvantages related to the two data-

bases cards in practice, it is recommended to use only one controller mode 

-

 

standalone or network. Before adding users, it is recommended that the admin-

istrator has created a list of users with assigned four

-

digit ID code. This makes it 

easier to add new users later, and in particular the removal of lost cards.

 

6.1 Adding a package of cards

 

After entering the programming mode enter the code 

31

, then:

 

• 

Enter the ID of the first user of the package

 

• 

Close the cards one of the other to the reader

 

After read each card reader will generate a single beep.

 

• 

Repeat the operation for the next card

 

• 

After loading press #

 

Read the card will be credited automatically generated ID numbers. The process 

is best preceded by the preparation of a list of IDs, user names and card num-

bers.

 

6.2 Adding a single card

 

After entering the programming mode enter the code 

32

, then:

 

• 

Enter the user ID from the list

 

• 

Close the cards one of the other to the reader

 

After you read the card reader will generate a single beep and automatically ex-

its the programming mode.

 

6.3 Adding a package of cards with PIN codes (6 digits)

 

After entering the programming mode enter the code 

33

, then:

 

• 

Enter the ID of the first user of the package

 

• 

Close the cards one of the other to the reader

 

• 

Enter the PIN 

-

> enter the PIN again

 

• 

Repeat the operation for subsequent reading cards with PIN codes

 

After each added card reader generate a single beep. Read the card will be cred-

ited automatically generated ID numbers.

 

• 

After loading press #

 

Содержание KaDe KDH-KZ2000-IP-U

Страница 1: ...SYSTEMY BEZPIECZE STWA Sp z o o All rights reserved 1 Installation Manual INTEGRATED ACCESS CONTROLLER KDH KZ2000 IP U KDH KZ2000 IP M VERSION 1 0 Installation Manual INTEGRATED ACCESS CONTROLLER KDH...

Страница 2: ...STWA Sp z o o All rights reserved 1 Introduction 3 2 Controller technical data 4 3 Controller wiring diagram 6 4 Controller installation 9 5 Management in standalone mode 10 6 Programming codes table...

Страница 3: ...can use for two way control Recom mended supply power type AWZ 200 plus 7Ah battery It s possibility to set one from four identification mode Card only default mode PIN only Card or PIN Card PIN KZ 1...

Страница 4: ...P For additional module connection RS485 for future used Readers and Cards Integrated reader For UNIQUE card read range 5 10 cm U For MIFARE card red range 2 5 cm M External for two way control 26 U 3...

Страница 5: ...nnectors 12V 110 mA Lock control relay output Alarm relay output Bell control output from keypad key LED located on front panel upper left light in RED as supply power indicator Blue access granted li...

Страница 6: ...der SW Purple Door contact AN Gray Exit button ALM Yellow PIR sensor input 485 Black RS485 port signal 485 Red RS485 port signal 12V Black Controller supply power 12 VDC 12V Black Supply power for ext...

Страница 7: ...2NC Black 2C Red 2NO White 1NC Yellow 1C Orange 1NO Green Electric lock connection NO type Electric lock VDC D0 Green D1 White BUZ Blue SW Purple AN Gray ALM Yellow 485 Black 485 Red J6 connector 8 p...

Страница 8: ...tric lock Sound alarm KDH KZ2000 IP U_M controller RS485 For future use Alarm sensor Exit button Door Status sensor Reader KaDe Premium Plus II supervisor software Buzzer Battery Tamper Administrator...

Страница 9: ...and one in the middle for the cables 2 Attach the back cover of the controller to the wall Place the plugs from the wires in the appropriate sockets and drag them to the other side of the wall 3 Mount...

Страница 10: ...ion was not successful Quad sound at the selected position is already stored card Triple sound card with this number is already added Optical indicator LED Red LED Power on Blue LED confirmation of th...

Страница 11: ...ters of the exit button After entering the programming mode enter the code 141 then 01 code for the NO type button normally open Default setting 00 code for the NC type button normally closed After en...

Страница 12: ...dalone or network Before adding users it is recommended that the admin istrator has created a list of users with assigned four digit ID code This makes it easier to add new users later and in particul...

Страница 13: ...list or Close deleting card to the reader After you read the card controller will generate a single beep and automatically exits the programming mode 7 1 Removal of all users After entering the progr...

Страница 14: ...s Alarm action delay Alarm relay output 161 01 type NO 00 type NC 162 00 99 sec 0 sec default 163 1 RL1 2 RL2 3 RL1 2 4 no out Access mode setup Card only 221 Card PIN 222 PIN only 223 Card or PIN 224...

Страница 15: ...hat the minimum distance from cables and high voltage devices and other devices that generate elec trical noise was 2 m The minimum distance from telephone lines should be 1 m and from 8 m transmittin...

Страница 16: ...Integrated Access Controller Installation manual 16 AAT SYSTEMY BEZPIECZE STWA Sp z o o All rights reserved...

Страница 17: ...l AAT SYSTEMY BEZPIECZE STWA Sp z o o All rights reserved 1 Kontroler zintegrowany Instrukcja instalacji AAT Holding S A Wszelkie prawa zastrze one Instrukcja instalacji KONTROLER ZINTEGROWANY KDH KZ2...

Страница 18: ...rmacje wst pne 3 2 Dane techniczne kontrolera 4 3 Schemat blokowy pod czenia akcesori w do kontrolera 6 4 Monta kontrolera 9 5 Programowanie kontrolera w trybie autonomicznym 10 6 Tabela kod w program...

Страница 19: ...y r wnie czytnik z klawiatur Kontroler wraz z czytnikiem z klawiatur oferuje 4 tryby identyfikacji u ytkownika karta PIN karta lub PIN karta PIN Ka dy u ytkownik mo e mie sw j indywidulany kod PIN r w...

Страница 20: ...rzysz o ci Czytniki i karty zintegrowany w urz dzeniu Na karty UNIQUE zasi g 5 15 cm U Na karty MIFARE zasi g 2 5 cm M dodatkowy Zgodny z 26 U 34 M bit Wiegand format kart ISO UNIQUE 125 kHz MIFARE CL...

Страница 21: ...ie przeka nikowe do sterowania sygnalizatorem alarmowym wyj cie do sterowania dzwonkiem z przycisku na klawiaturze Dioda LED na panelu przednim lewy g rny r g wieci w kolorze Czerwonym w czone zasilan...

Страница 22: ...cisk wyj cia ALM ty Linia dozorowa czujki PIR 485 Czarny RS485 port sygna 485 Czerwony RS485 port sygna 12V Czarny Zasilanie kontrolera 12 VDC 12V Czarny Zasilanie czytnika zew 12 VDC 12V Czerwony Zas...

Страница 23: ...y 1NC ty 1C Pomara 1NO Zielony Pod czenie zamka elektrycznego typu NO rygiel rewersyjny lub zwora Zamek elektryczny VDC D0 Zielony D1 Bia y BUZ Niebieski SW Fioletowy AN Szary ALM ty 485 Czarny 485 C...

Страница 24: ...oler KDH KZ2000 IP U_M RS485 Do przysz ych zastosowa Czujka PIR Przycisk wyj cia Czujnik stanu drzwi Czytnik Program nadzorczy KaDe Premium Plus II Sygnalizator akustyczny Bateria Czujnik sabota owy R...

Страница 25: ...jeden na rodku pod kable 2 Zamocuj tyln ciank kontrolera do cia ny Umie wtyczki od przewod w w odpowied nich gniazdach i przeci gnij je na drug stron ciany 3 Zamontuj modu kontrolera na tylnej cian ce...

Страница 26: ...orowej przycisku wyj cia Po wej ciu w tryb programowania wprowadzi kod 141 nast pnie kod 01 dla przycisku typu NO normalnie otwarty ustawienie domy l kod 00 dla przycisku typu NC normalnie zamkni ty P...

Страница 27: ...k na wybranej pozycji jest ju zapisana karta sygnalizator optyczny diody LED czerwony zasilanie w czone niebieski potwierdzenie wa no ci operacji zielony tryb programowania 5 1 Procedura wej cia w try...

Страница 28: ...unikn prowadzenia podw jnej ewidencji kart i utrud nie zwi zanych z dwoma bazami danych kart zaleca si w praktyce u ywanie tylko jednego trybu pracy kontrolera autonomicznego lub sieciowego Przed przy...

Страница 29: ...do czytnika Po odczytanej karcie kontroler wygeneruje pojedynczy sygna akustyczny i auto matycznie wyjdzie z trybu programowania 7 1 Usuni cie wszystkich u ytkownik w Po wej ciu w tryb programowania...

Страница 30: ...typ NO 00 typ NC 162 00 99 sekund 0s domy l 163 1 PK1 2 PK2 3 PK1 i 2 4 brak Tryby identyfikacji u ytkownika Tylko karta 221 Karta PIN 222 Tylko kod PIN 223 Karta lub kod PIN 224 Zarz dzanie u ytkowni...

Страница 31: ...odle g o od kabli i urz dze wysokiego napi cia oraz innych urz dze generu j cych zak cenia elektryczne wynosi a 2 m Minimalna odleg o od linii te lefonicznych powinna wynosi 1 m a od urz dze nadawczy...

Страница 32: ...rc w prowadzonego przez S d Rejonowy dla m st Warszawy w Warszawie XIII Wydzia Gospodarczy Krajowego Rejestru S dowego pod numerem KRS 0000838329 kapita zak adowy wp acony w ca o ci w wysoko ci 5 000...

Отзывы: