Integrated Access Controller –
Installation manual
AAT SYSTEMY BEZPIECZEŃSTWA Sp. z o.o.
All rights reserved.
11
5.2 Configuring basic parameters include:
•
controller initialization
•
enable / disable the alarm
•
tamper sensor alarm
•
parameters of exit button
•
door status sensor parameters
•
alarm parameters
5.2.1 Controller initialization
•
After entering the programming mode enter the code
11
•
The process takes about 30 seconds, during which the controller gener-
ates beep every 0.5 seconds
•
After this time, the controller generates a long beep and exits the pro-
gramming mode
Initialization operation erases the controller configuration settings (including a
database of cards) and restore the factory settings. Administrator password has
been set to default (000000).
5.2.2 Enable / disable alarm
After entering the programming mode enter the code:
•
121
alarm on
•
122
alarm off
5.2.3 Tamper Alarm
After entering the programming mode enter the code
13
, then:
•
Code 00 when you want to disable the monitoring of the sensor
•
code 01 to activate monitoring
When a tamper alarm is activated an attempt to remove the unit from the wall
will turn on internal buzzer in the controller and an alarm sound. This option
should be activate only after installing the controller on the wall.
5.2.4 Setting the parameters of the exit button
After entering the programming mode enter the code
141
, then:
•
01
code for the NO type button (normally open
-
Default setting)
•
00
code for the NC type button (normally closed)
After entering the programming mode enter the code
142
, then:
•
01
code button enable (default)
•
00
code button disabled
5.2.5 Setting the parameters of the door sensor detection line
After entering the programming mode enter the code
151
, then:
•
01
code for the NO type sensor (normally open
-
Default setting)
•
00
code for the NC type sensor (normally closed)
After entering the programming mode enter the code
152
, then:
•
value from
00
to
99
seconds (default
-
3 sec.)
This is the time to close the door after time to unlock leaf.
5.2.6 Setting the parameters of the alarm line
After entering the programming mode enter the code
161
, then:
•
Code
01
for NO type detector (normally open
-
default setting.)
•
Code
00
for NC type detector (normally closed)
After entering the programming mode enter the code
162
, then:
•
value from
00
to
99
seconds (default
-
0 sec. default settings)
This is the time of relay alarm action.
Value 0 second time means
“
Alarm action Synchronous with input state
”.
Value from range 1 to 99 means
“
Alarm action delay time
”.
After entering the programming mode enter the code
163
, then:
•
value
1
if the alarm siren will be activated relay 1
•
value
2
when the alarm siren will be activated relay 2
•
value
3
when the alarm siren will be activated relay 1 and 2
•
value
4
when none of these relays will not switch