Standard controller –
Installation manual
AAT SYSTEMY BEZPIECZEŃSTWA Sp. z o.o.
All rights reserved.
5
3. General guidelines for controller installation
•
Before controller installation please read this manual.
•
Controller installation can be performed only by qualified personnel with the
appropriate certificate, authorizing to install and service such equipment
•
Controller should be installed
inside protected area
with temperature
above +2°C and normal humidity.
•
Controllers should be located so that the minimum distance from the cables
and high voltage devices and other devices, that generate electrical noise,
was 2 m. The minimum distance from the telephone line should be 1 m, and
from transmitting devices 8 m.
•
Controller should be powered from dedicated power supply, type APSAAT4,
described in further part of manual
•
Wire connections and works with internal controller parts with power on is
strictly prohibited, as it may damage the device
•
Before connecting controller to power supply, all necessary connections
should be made, in accordance with this manual.
Connection
Wire type
Distance
Ethernet switch (or router)
> IP controller
UTP
-
5 twisted
-
pair wire
with RJ45 connectors
Up to 50 m
(recommended)
(max. 100m)
KDH
-
MOD2000 module > Controller
(located out of enclosure)
2 pairs of
UTP
-
5 twisted
-
pair wire
Up to 800m
(recommended)
(max. 1200m)
Reader > Controller
6
-
core LIYCY 6x0,75 or
UTP
-
5 twisted
-
pair wire
Up to 60m max.
Emergency exit button > Lock >
Controller
2 or 4
-
core cable
(4×1.0)
150m
Door contact > Controller
2
-
core cable
(2×0.5)
150m
Exit button > Controller
2
-
core cable
(2×0.5)
150m
Detector > Controller input
2
-
core cable
(2×0.5)
150m
Mains power supply 230VAC
3
-
core cable
(3×1.5)
-
Connection wires table