![AAON SS1113 Скачать руководство пользователя страница 61](http://html.mh-extra.com/html/aaon/ss1113/ss1113_technical-manual_449211061.webp)
Main Chiller Controller Technical Guide
APPENDIX B - BACnet
®
61
BACnet
®
Parameters
ANALOG VALUES
BACnet
®
Point Name
Object
BACnet
®
Description
Limit Range
Vestibule
Heating
Setpoint
AV:9
If the Vestibule Temperature drops below this setpoint
the heating mode will activate on the Fan Coil.
50-90
Vestibule Heat/
Cool Setpoint
Deadband
AV:10
The Vestibule temperature has to be above or below the
setpoint by this amount to initiate heat or cool modes.
0.1-10
Vestibule
Temp Sensor
Calibration
Off set
AV:11
If the Vestibule Temperature Sensor is reading incorrectly
you can use this option to enter an off set temperature
to adjust the Sensor’s Temperature.
-100-100
Leaving
Water Sensor
Calibration
Off set
AV:12
If the Leaving Water Sensor is reading incorrectly
you can use this option to enter an off set temperature
to adjust the Sensor’s Temperature.
-100-100
Entering
Water Sensor
Calibration
Off set
AV:13
If the Entering Water Sensor is reading incorrectly
you can use this option to enter an off set temperature
to adjust the Sensor’s Temperature.
-100-100
Outdoor
Air Sensor
Calibration
Off set
AV:14
If the Outdoor Air Sensor is reading incorrectly
you can use this option to enter an off set temperature
to adjust the Sensor’s Temperature.
-100-100
Comp Ratio
Setpoint for
Condenser
Speed
AV:15
The Condenser Fan Speed is controlled by the highest
Pressure Ratio from the active compressors.
0.5-3
Comp Ratio
Startup for
Compressors
AV:16
During Compressor Startup, the Pressure Ratio must be
below this setpoint.
0.5-3
Override Start/
Stop On
AV:17
Mechanical Cooling will be locked out if the
Outdoor Air Temperature is below this setpoint.
0-1
Override
Outdoor Air
Temperature
AV:18
Mechanical Heating will be locked out if the
Outdoor Air Temperature is above this setpoint.
-100-150
-100 = No
Override