Main Chiller Controller Technical Guide
SECTION 3:
WIRING
29
Main Chiller Controller Output Wiring
Figure 25: Main Chiller Controller Output Wiring
Main Chiller Controller Outputs
The Main Chiller Controller has (2) E-BUS Expansion Ports which
allow for the connection of the Chiller Expansion Module, (3)
Compressor Circuit Modules, and (3) Economizer Subcool Modules
via EBC E-BUS Cables.
The Main Chiller Controller must be connected to 18-30 VAC as
shown in
Figure 25
, below. Please see
Table 8, page 40
for correct
VA requirements to use when sizing the transformer(s) used for
powering the Controller.
Also please note that when wiring the Main Chiller Controller, its
contacts must be wired as wet contacts (connected to 24 VAC).