28
RSM-DEV1 Technical Guide
LCD SCREENS
Screen Descriptions
Setpoint Status Screens
Refer to the following map when navigating through the Setpoint
Status Screens. From the SETPOINT STATUS Screen, press
<ENTER>
to scroll through the screens.
SETPOINT STATUS SCREENS
Screen Text
Description
SETPOINT
STATUS
Setpoint Status screens
HEADPRSP
XXX PSIG
Head Pressure Setpoint. Valid range is 260-475
psig. Default is 340 psig. Measured in PSIG.
SUPRHT SP
XX.X°F
Superheat Setpoint. Valid range is 1-30ºF. Default
is 15ºF. Measured in degrees Fahrenheit.
LOW SUCT
XX PSIG
Low Suction Pressure Setpoint. Default is 95 psig.
Measured in PSIG.
COILT SP
XX.XºF
Coil Temperature Setpoint. Valid range is 35-60ºF.
Default is 40ºF.Measured in degrees Fahrenheit.
Table 11: Setpoint Status Screens