20
Table 6 - Input Current Foldback
Condition
Action taken by the Drive
1
Input Current >= Foldback Current
Will reduce the speed to minimum speed at rate of 20 rpm/s
2
Recovering Current <= Input Current <Foldback
Current
Will remain in the current speed
3
Input Current < Recovering Current
Speed will be recovered to commanded speed
4
Drive in foldback state for >=30 sec
Compressor will be tripped
Table 7 - Output Current Foldback
Condition
Action taken by the Drive
1
Output Current >= Foldback Limit of operating
speed range
Will reduce to minimum speed of the speed range at rate of 20
rpm/s
2
Recovering Current <= Output Current <
Foldback Limit of operating speed range
Will remain in the current speed
3
Output Current < Recovering Current
Speed will be recovered to commanded speed
4
Drive in foldback state for >=30 sec
Compressor will be tripped
Table 8 - Inverter Temperature Feedback
Condition
Action taken by the Drive
1
Inverter Temperature >= Foldback Temperature
Will reduce the speed to minimum speed at rate of 20 rpm/s
2
Recovering Temperature <= Inverter Temperature
<Foldback Temperature
Will remain in the current speed
3
Inverter Temperature < Recovering Temperature
Speed will be recovered to commanded speed
4
Drive in foldback state for >=30 sec
Compressor will be tripped