Input Voltage and Input Current 

The drives are designed for rated AC power 
supply: 50/60Hz, 380-480V on EV20XXM 
KX-XXX models and 208-240V on 
EV20XXM-JX-XXX drive models.  
 

Drive 

AC Input Overcurrent 

Protection 

EV2080J 

24A RMS 

EV2080K 

15A RMS 

EV2055J 

18A RMS 

EV2055K 

12A RMS 

 

Power Factor Correction 

Drive has passive power factor correction, 
which is capable of improving efficiencies. 

Speed Control  

The frequency range of the drive is from 
15Hz to 120Hz. If the frequency set by unit 
controller is less than 15Hz but not zero, 
then the compressor will work at 15Hz. 
Similarly, if the frequency set by unit 
controller is greater than 120Hz, then the 
compressor will work at 120Hz. 
 
There are three cases for unit shut down. 
  
Case I (Controlled shut down):  Unit shut 
down the compressor.  
 
Case II (Faulted condition): When drive 
faults occur, the drive will shut down the 
compressor. Major and minor faults have 
different shutdown sequences. For major 
faults, the drive trips the compressor 
immediately (from running frequency to 
zero frequency). For minor faults, it has the 
same sequence as Case I. As mentioned 
above clear faults using the 'Fault Clearing' 
method shown below. 
 
Case III: Loss of power shut down, this 
control procedure is the same as major fault 
shut down. 

Fault Clearing 

Faults are cleared through unit controls 
interface.  

Status Indication 

There are two control chips on the drive 
board and all of them have their own LED 
for status display. COMMS MCU has three 
LED indicators, DSP has one LED indicator. 

LED for COMMS MCU 
 

Operation Indicating LED  
(Green LED805) 

When the drive is in normal state (no 
protection and fault), the drive is in standby 
state and the compressor does not work, the 
LED will blink every 2 seconds. If the 
compressor is running, the LED will always 
be on. 
 

Protection Indicating LED  
(Yellow LED804) 

When the drive is under protection, the 
yellow LED will blink. Refer to 

Troubleshooting Table

 more information. 

 

Hardware Fault Indicating LED  
(Red LED803) 

When the drive is under hardware fault, the 
red LED will blink. Refer to 

Troubleshooting Table

 for more 

information. 
 

LED for Drive Control DSP Chip  
(Green LED802)  

When the drive is in normal state, whether 
the compressor is running or standby, the 
LED will blink every 1 second. When the 
drive is under protection or hardware fault, 
the LED will blink every 1/8 of a second.

 

Содержание RQ SERIES

Страница 1: ...RQ SERIES Variable Speed Scroll Compressor Supplement...

Страница 2: ...escription 11 Theory of Drive Operation 11 Nomenclature 11 Temperature Humidity 11 Power On Off 11 Communication Setting 11 Input Voltage and Input Current 12 Power Factor Correction 12 Speed Control...

Страница 3: ...tMaster VCC X Controller and Refrigeration System Control Module 21 Figure 7 Modular Silicon Expansion Valve 22 Figure 8 USHX 22 Figure 9 USHZ Wiring Harness 22 Figure 10 MSEV and USHC installation sc...

Страница 4: ...4...

Страница 5: ...5 RQ Series Variable Speed Compressor Components Variable Speed Compressor Inverter Electronic Expansion Valve WattMaster VCC X Controls EC Motor Automation Control Unit...

Страница 6: ...6 Variable Speed Compressor Inverter WattMaster VCC X Controls Condenser Fan EC Motor Automation Control Unit Electronic Expansion Valve Controller...

Страница 7: ...7 Example Wiring Diagram showing WattMaster Refrigeration System Module for Variable Speed Compressors Copeland Inverter Electronic Expansion Valve and Variable Speed Condenser Fan Control...

Страница 8: ...e intervals between phases Oil Pump The variable speed scroll is equipped with an oil pump to ensure an adequate supply of oil to the bearing system throughout the operating speed range of 900 to 5000...

Страница 9: ...l performance A filter drier is required on all R 410A and POE lubricant systems to prevent solid particulate contamination oil dielectric strength degradation ice formation oil hydrolysis and metal c...

Страница 10: ...sor will provide no useful information to the service technician other than to show that each winding of the compressor is drawing current The more appropriate measurement is the current input to the...

Страница 11: ...power rating and nominal voltage input to the drive Figure 3 provides a complete explanation of all of the alpha and numeric characters in the drive model number Temperature Humidity Drive operating...

Страница 12: ...quence as Case I As mentioned above clear faults using the Fault Clearing method shown below Case III Loss of power shut down this control procedure is the same as major fault shut down Fault Clearing...

Страница 13: ...ing The drive may indicate fault or protection for various reasons If fault or protection occurs users should power down the drive check the drive and check the drive running condition carefully For t...

Страница 14: ...er than 170V Check the AC power supply and if the right voltage is supplied according to the drive model The drive running condition is not stable Check the compressor load and makes sure it is OK Res...

Страница 15: ...g screws on the drive make sure they are tight If the problem still persists replace the drive 18 19 Power module temp foldback timeout Power module temperature exceeds normal design limits 1 Verify p...

Страница 16: ...ow Check the input voltage and compressor is operating within limits 12 Note Two Different values are for EV2080M and EV2055M Models Model Numbers Capacity EV2080M K9 XXX 080 8 0kW EV2080M J9 XXX 080...

Страница 17: ...17 Figure 4 U S Drive Model Wiring Diagram Figure 5 U S Wiring Diagram...

Страница 18: ...ion Pin Number Description Figure 1 RS485 2 Not Used 3 Not Used 4 RS485 5 Common 6 EMI Drain Wire Table 3 Sensor Connector Pin Definition Pin Number Description Figure 1 Sensor Pin 2 3 3VDC 3 Not Used...

Страница 19: ...ompressor reaches minimum start frequency 25 1 5 III Compressor remains at platform frequency 25 10 IV Compressor reaches commanded frequency Commanded 1 Table 5 Ramp Down Sequence Stage Description T...

Страница 20: ...imum speed of the speed range at rate of 20 rpm s 2 Recovering Current Output Current Foldback Limit of operating speed range Will remain in the current speed 3 Output Current Recovering Current Speed...

Страница 21: ...ndenser Fan to maintain the Head Pressure Setpoint Provides alarms and safeties for the compressor and condenser operation Contains a 2 x 8 LCD character display and 4 buttons that allow for status di...

Страница 22: ...that applies varying fractions of fluid line pressure onto the second stage spool valve according to the command signal provided by the Universal SuperHeat Controller USHC The MSEV is installed at the...

Страница 23: ...t Black 18 AWG 9 Pin 3 DATA RS485 Communication Black 24 AWG Shielded 9 Pin 4 DATA RS485 Communication Red 24 AWG Shielded 9 Pin 2 SENS Digital Signal Ground and Thermistor Signal Ground Black 24 AWG...

Страница 24: ...ves and controls the MSEV is installed at the outlet of the evaporator in place of the TXV bulb or EEV controller sensing device The MSEV and USHC are connected together by a wiring harness A thermist...

Страница 25: ...ugh the valve Also ensure that the MSEV is installed in an upwards orientation or at any angle less than 90 in either direction represented by the curved green arrows a The MSEV cannot be installed in...

Страница 26: ...a vertical copper line as shown in Figure 13 the USHX cannot be installed at a downward angle represented by the red arrow 4 Drill a hole into the copper line that extended tubes may fit in to The loc...

Страница 27: ...pin connector of the wiring harness Figure 15 Installed USHX with attached 10 pin wiring harness 10 Install the thermistor at the outlet of the evaporator and close to the access fitting using a zip...

Страница 28: ...Mode and other settings 20 Power on the HVAC R system and the MSEV and USHX will automatically begin functioning 21 Observe the superheat temperature values in the GUI Status tab to ensure that the sy...

Страница 29: ...Figure 18 a For the user s own safety only Class 2 power sources should be used to power the MSEV and USHX devices 3 Double check the power source output voltage AC transformer secondary or DC power s...

Страница 30: ...tep in the procedure All connectors used between the USHX power source and MSEV should be UL approved b The wiring schemes of the Single USHC MSEV Setup and Single USHS Setup are the same except that...

Страница 31: ...ted be terminated with wire nuts and wrapped with electrical tape so that they do not form short circuits with each other or any other wires or metal surfaces 10 Tape any dangling wires to existing st...

Страница 32: ...orator at a 10 o clock or 2 o clock position Check that the temperature sensor is wrapped with insulated tape Over Voltage to MSEV Check the resistance across the valve terminals Remove both power con...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications and or design of it...

Отзывы: