COMMUNICATIONS WIRING
Secondary Board - Four Modulating Valves, One Ignitor, One Stage (2V1IGN1S)
Figure 14: Communications Wiring - Secondary Board 2V1IGN1S
Heat Valve 3 and 4
(Stage 1)
ASSEMBLED IN USA
U15
D13
R
R
R
R
L1
R61
C28
SERIAL #
POWER
COMM
ALARM
STATUS
TB3
GND
AUX AIN
J3
GND
1
2
SAT
OPTIONS
RESET IN
D8
HEAT EN
D7
AUX BIN
GND
J1 U1
TB2
R1
YS102408 REV 3
TB1
RLY1
RLY2
RLY3
RLY4
RLY5
RLY6
COMMON
PO-IGN1
P3
D9
R33
R1
P1
PO-IGN2
P4
D10
R36
R2
Q2
R5
P2
C35
.01UF
R8
R22
R18
R16
R12
R13
R42
R44
D14
SOFTWARE
C22
C27
GAS VALVE 2
GAS VALVE 1
ALARM
UP
DOWN
ENTER
MENU
AAON P/N: ASM06909
MODGAS-XWR2-B
LABEL P/N:
G112180
DUAL
E-BUS
+24 V
AC
GND
CONTACT
RATING IS
1 AMP MAX
@ 24 VAC
COMMON
RELAY
OUTPUTS
GAS VALVE
TERMINALS
GAS
VAL
VE 1
GAS
VAL
VE 2
INPUT TERMINALS (TYPE)
HEAT ENABLE (BI)
AUX. (BI)
GND
RESET IN (AI)
SAT IN (AI)
GND (AI)
GND
AUX. (AI)
www.aaon.com
LOW SPEED
HEAT 1
HEAT 2
HEAT 3
HEAT 4
PROOF OF IGNITION 1
PROOF OF IGNITION 2
FAN
NOTES:
1. 24 VAC must be connected so that all ground wires
remain common.
2. All wiring to be in accordance with local and national
electrical codes and specifications.
E-BUS cable connects to the
primary MODGAS-XWR2
series module.
GV3
H1
Line
40 VA
transformer
minimum
GND
18-30
VAC
GV4
Fixed Heat Stage 5
Fixed Heat Stage 6
Fixed Heat Stage 7
Modulating
Gas Valve 3
Modulating
Gas Valve 4
Proof of Ignition
Signal 1 (24 VAC)
CR2
Combustion
Fan Enable
Combustion Fan
Low Speed
Check your Fan Relay Wiring
(Both RLY1 and RLY2)
Schematic for proper wiring.
CR1
In this configuration, the wiring on
Figure 13, page 20
is the primary
portion and
Figure 14, this page
is the secondary portion, thus
creating four modulating valves as one stage.
NOTE:
Up to three additional fixed heat stages can be
configured by using Heat 2 (RLY4), Heat 3 (RLY6),
and Heat 4 (RLY6). If additional fixed stages are
required, these should be configured and wired to the
AAON unit controller’s relays.