19
MODGAS-XWR2-B Technical Guide
COMMUNICATIONS WIRING
Secondary Board - Four Modulating Valves, Two Ignitors, Two Stages (2V2IGN2S)
Figure 12: Communications Wiring - Secondary Board 2V2IGN2S
Modulating
Gas Valve 3
(Slave to Mod
Gas Valve 1)
Proof of Ignition
Signal 1 (24 VAC)
Heat Valve 3 (Stage 1)
Heat Valve 4 (Stage 2)
Fixed Heat Stage 5
Fixed Heat Stage 6
ALARM
UP
DOWN
ENTER
MENU
AAON P/N: ASM06909
MODGAS-XWR2-B
LABEL P/N:
G112180
DUAL
E-BUS
+24 V
AC
GND
CONTACT
RATING IS
1 AMP MAX
@ 24 VAC
COMMON
RELAY
OUTPUTS
GAS VALVE
TERMINALS
GAS
VAL
VE 1
GAS
VAL
VE 2
INPUT TERMINALS (TYPE)
HEAT ENABLE (BI)
AUX. (BI)
GND
RESET IN (AI)
SAT IN (AI)
GND (AI)
GND
AUX. (AI)
www.aaon.com
LOW SPEED
HEAT 1
HEAT 2
HEAT 3
HEAT 4
PROOF OF IGNITION 1
PROOF OF IGNITION 2
FAN
NOTES:
1. 24 VAC must be connected so that all ground wires
remain common.
2. All wiring to be in accordance with local and national
electrical codes and specifications.
E-BUS cable connects to the
primary MODGAS-XWR2
series module.
GV3
H1
Line
40 VA
transformer
minimum
GND
18-30
VAC
H2
Proof of Ignition
Signal 2 (24 VAC)
GV4
Modulating
Gas Valve 4
(Slave to Mod
Gas Valve 2)
CR2
Combustion
Fan Enable
Combustion Fan
Low Speed
Check your Fan Relay Wiring
(Both RLY1 and RLY2)
Schematic for proper wiring.
CR1
In this configuration, the wiring on
Figure 11, page 18
is the primary
portion and
Figure 12, this page
is the secondary portion, thus
creating four modulating valves as two stages.
NOTE:
Up to two additional fixed heat stages can be
configured by using Heat 3 (RLY5) and Heat 4
(RLY6). If additional fixed stages are required, these
should be configured and wired to the AAON unit
controller’s relays.