10
1.
Startup and service must be performed by
a Factory Trained Service Technician.
2.
The unit is for outdoor use only. See
General Information section for more
information.
3.
Every unit has a unique equipment
nameplate with electrical, operational,
and
unit
clearance
specifications.
Always refer to the unit nameplate for
specific ratings unique to the model
purchased.
4.
READ THE ENTIRE INSTALLATION,
OPERATION AND MAINTENANCE
MANUAL.
OTHER
IMPORTANT
SAFETY
PRECAUTIONS
ARE
PROVIDED THROUGHOUT THIS
MANUAL.
5.
Keep this manual and all literature
safeguarded near or on the unit.
COMPRESSOR CYCLING
3 MINUTE MINIMUM OFF TIME
To
prevent
motor
overheating
compressors must cycle off for a
minimum of 3 minutes.
5 MINUTE MINIMUM ON TIME
To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.
The cycle rate must not exceed 7
starts per hour.
WARNING