26
Minimum Value
(-000)
Maximum Value
(000)
Op Range Outside
Allowable Value.
Reset to Max F.S.
(Press Enter)
Op Range value within
New Min/Max values
Op Range value exceeds
New Min/Max values
Entering a new Min &
Max Temperature
value and pressing the
Enter button will
calculate new Min &
Max Op Range values.
Warning Message
Operating Range
(ACFM)
(6,000 - 12,000)
(12,000)
Pressing the Enter button
will reset the current Op
Range value to the new
calculated Max. F.S value
which will represent 100%
of the process output value.
The Op Range value can be
changed and will represent
100% of the process output
signal (5vdc, 10vdc, or 20mA).
-Temperature Range Example-
Minimum Value
(-000)
Accepted
(100)
6.2.3.3. Temperature Input
The Temperature Input Menu allows the user to select between three temperature input options (Fixed,
Variable, and Network) for the flow calculations. Since the AAON Temperature Transmitter has been
supplied, Variable has been selected. If Fixed is selected, the default temperature value entered in the
Fixed Value Menu (see Section 6.1.2.4) is used. If Net is selected, the temperature input signal is
obtained through network communications. The Net option is only available if one of the
communication options is ordered. The temperature value is only displayed on the LCD screen, if the
Temperature Input is set to Variable or Network.
Field Setup
Menu
Flow Correction
Temperature Units
Temp. Input
AutoZero
Temperature Values
(Fix/Var/Net)
Temp Comp.
Temperature Input
Display Filter
Fixed Value
(Variable)