15
5.1.4. Baud Rate (Modbus and BACnet Communication Options)
The Baud Rate Menu allows the user to set a unique network baud rate. Modbus communications
supports 9.6, 19.2, 38.4, 57.6 and 115.2 Kbps baud rate. The current BACnet protocol supports 9.6,
19.2, 38.4 and 76.8 Kbps baud rate. The default is 38.4 Kbps. For communication with WattMaster
Controls, the Baud Rate has been set by the factory to 9.6 Kbps. For additional information refer to the
AAON Outdoor Airflow Measurement System O&M.
Tech. Config.
Password: 1000
Baud Rate
Baud Rate
(9.6, 19.2, 38.4, 76.8)
(38.4) Kbps
5.2.
FIELD SETUP MENU
The High/Low Alarm Option, if ordered, and Flow Correction (K-Factor) will be configured under the
Field Setup Menu. To set the parameters refer to the following procedure, below subsections, and
Section 4.3 for Key functions.
Step 1.
Enter the Field Setup Menu by depressing and holding the Enter Key for 5
seconds.
Step 2.
Once in the Field Setup Menu use the Up/Down Keys to highlight the required
parameter for configuration as shown in Sections 5.2.1 through 5.2.3. Press the
Enter Key once to access the highlighted parameter Menu.
Step 3.
Once in the parameter menu, the parameter can be changed using
Up/Down/Left/Right Keys. After the parameter has been changed, press the Enter
Key once. Then Press the ESC Key once to return to the Field Setup Menu.
Step 4.
After all of the required parameters have been configured, exit the Field Setup
Menu by pressing the ESC Key. The Process Display (see Section 4.2) will then
be displayed.
5.2.1. High/Low Alarm Option
The following menus for configuration of High/Low Alarms are only available if the High/Low Alarm
option is purchased.