13
5. FIELD STARTUP
The AAON Airflow Signal Processor has been configured by the factory for the specific application.
Therefore, the only parameters that need to be configured in the field are the network communication
settings, with the exception of Modbus® Slave communication with WattMaster Controls which has
been configured at the factory, and the High/Low Alarm Option if ordered. Communication settings
will be configured under the Tech Configuration Menu (see Section 5.1). The High/Low Alarm Option
will be configured under the Field Setup Menu (see Section 5.2).
During field startup, if the displayed value on the AAON Airflow Signal Processor does not match the
reading from the Balancer, a Flow Correction (K-Factor) can also be entered under the Field Setup
Menu (see Section 5.2).
If required, the AAON Factory Settings can be checked or reconfigured following procedures outlined
in Section 6. If parameters are reconfigured incorrectly, all device settings can be restored to the
original AAON Factory Settings (see Section 5.2.3). This guide is intended for field startup only of the
AAON Airflow Signal Processor. The full AAON Outdoor Airflow Measurement System O&M can be
downloaded from AAON’s website at www.AAON.com.
5.1.
TECH CONFIGURATION MENU
If a network communication option is ordered the associated settings will need to be configured, with
the exception of Modbus® Slave communication with WattMaster Controls which has been configured
at the factory. To set the parameters refer to the following procedure, below subsections, and Section
4.3 for Key functions.
Step 1.
Enter the Tech Configuration Menu by pressing and holding the Up/Down Keys
simultaneously for 5 seconds.
Step 2.
Using the Up/Down/Left/Right Keys, enter password number 1000 and press the
Enter Key.
Step 3.
Once in the Tech Configuration Menu, use the Up/Down Keys to highlight the
required parameter for configuration as shown in Sections 5.1.1 through 5.1.4.
Press the Enter Key once to access the highlighted parameter Menu.
Step 4.
Once in the parameter menu, the parameter can be changed using the
Up/Down/Left/Right Keys. After the parameter has been changed, press the Enter
Key once. Then Press the ESC Key once to return to the Tech Configuration
Menu.
Step 5.
After all of the required parameters have been configured, exit the Tech
Configuration Menu by pressing the ESC Key. The Process Display (see Section
4.2) will then be displayed.