Attach moisture indicator to side of motor, place several bags of silica gel
inside, then seal plastic bag. If motor cannot be placed in plastic bag and
relative humidity exceeds 50%, use space heaters to keep motor at least
10F above ambient air temperature.
Rotate motor shaft at least 10 revolutions every month; re-lubricate
bearings after each year of storage.
Check desiccant bags and rust prohibitive monthly; replace desiccant
and recoat with rust preventative as required. Also check operation of space
heaters.
If the unit has been in use and prolonged storage is anticipated, the unit
shall be cleaned on the inside and outside of dust and water to prevent damage to
the interior and exterior of the collector.
8
SITE PREPARATION
8.1
Locating equipment
The dust collector site location must take into account the wind and seismic
loadings. See collector specifications to ensure proper site location.
Ensure local laws, codes and regulations are followed for the materials being
collected. Noise levels should be considered when selecting the proper location of
the RotoClone LVN.
Locate the RotoClone LVN in a location so that maintenance to the collector
can be handled easily. See collector drawing for cartridge clearance.
In the case of hazardous dust, consult your local authorities, laws, codes, or
regulations for the location of the unit.
8.2
Foundations
Foundations must be true, level, and rigid enough to prevent vibration and
support the weight of the RotoClone LVN with its maximum dust and water load.
See section 3.6 for net weights of the RotoClone LVN.