Code and
description
Cause
Measure
XA5-XXXX
(lock out error)
Temperature error
High temp limit exceeded
The temperature in the tank is above
95ºC.
Refer to indication X54-XXXX (see 12.1.3).
-
Make sure that the wiring between
1 and 4 of J9 is connected and not
damaged.
-
If necessary, replace or reconnect the
wiring.
-
When the wiring is reconnected, reset
the controller.
X48-XXXX
(blocking error)
Sensor error
Open circuit of
temperature sensor
Sensor is not (correctly) connected.
-
Make sure that the connector is
connected to J10.
-
Make sure that the wire is connected
to the sensor.
Damaged wiring and/or defective sensor. Replace the wiring and/or the sensor.
X46-XXXX
(blocking error)
Sensor error
Short circuit of
temperature sensor
Short circuit in the sensor circuit.
Replace the wiring and/or the sensor.
X57-XXXX
(lock out error)
Short circuit flame sensor
Electrical connection between flame
sensor and tank or burner.
-
Make sure that the flame sensor does
not touch the tank.
-
If necessary, replace the flame sensor.
-
Make sure that the combustion
chamber is dry.
-
Make sure that the cables of the flame
sensor are correctly connected.
-
If necessary, replace the connector of
the flame sensor to the correct
connection.
XAC-XXXX
(blocking error)
Air proving switch
error
Switch is not closed when
fan is running during pe-
purge
Hoses are damaged.
-
Make sure that the hoses, between
the air proving switch and fan and the
air proving switch and gas control
valve are not damaged and reset the
controller.
-
If necessary replace the hose(s).
-
When the hose(s) are replaced and
reconnected, reset the controller.
Wiring is damaged.
-
Make sure that the wiring, between
the air proving switch and the
controller, is connected and not
damaged.
-
If necessary, replace the wiring or
reconnect the wires.
-
When wires are replaced or
reconnected, reset the controller.
Leakage of air between venturi and air
connector.
-
Make sure that the air connector is not
damaged. If necessary, replace the air
connector.
-
Make sure that the hose is properly
connected to the venturi. If necessary,
tighten the clamp.
76
Installation, Maintenance and Service part
Содержание TWI 35-200
Страница 6: ...6...
Страница 13: ...User part 0313279_TWISTER II_UKUK_V1 1 18 02 2019 13...
Страница 14: ...14...
Страница 16: ...16 User part...
Страница 18: ...18 User part...
Страница 25: ...Installation Maintenance and Service part 0313279_TWISTER II_UKUK_V1 1 18 02 2019 25...
Страница 26: ...26 User part...
Страница 34: ...34 Installation Maintenance and Service part...
Страница 42: ...Fig Venting systems IMD 1353 R0 C43 C13 C53 B23 C33 42 Installation Maintenance and Service part...
Страница 54: ...54 Installation Maintenance and Service part...
Страница 56: ...56 Installation Maintenance and Service part...
Страница 66: ...66 Installation Maintenance and Service part...
Страница 72: ...72 Installation Maintenance and Service part...
Страница 80: ...80 Installation Maintenance and Service part...
Страница 83: ...Fig Dimensions A D E 3 5 1 3 7 4 1 G 5 2 IMD 1349b R0 0313279_TWISTER II_UKUK_V1 1 18 02 2019 83...
Страница 87: ...13 6 Declaration of conformity 0313279_TWISTER II_UKUK_V1 1 18 02 2019 87...
Страница 90: ...90 Installation Maintenance and Service part...