Fig. Twister water heater
2
3
1
1. Water inlet
2. Heat exchanger
3. Water outlet
When the temperature is too low, the water heater starts a operating cycle:
1.
The controller detects a "heat demand".
2.
The fan starts pre-purging.
3.
The air proving switch closes when the air pressure differential is sufficient.
4.
The spark plug is activated.
5.
The gas control valve opens and the gas/air mixture is ignited.
6.
The water heater heats the water in the tank.
7.
When the water temperature reaches the setpoint, the heat demand ends and the
controller stops the operating cycle.
8.
The fan starts post-purging.
The operating cycle starts again when a new heat demand is detected.
28
Installation, Maintenance and Service part
Содержание TWI 35-200
Страница 6: ...6...
Страница 13: ...User part 0313279_TWISTER II_UKUK_V1 1 18 02 2019 13...
Страница 14: ...14...
Страница 16: ...16 User part...
Страница 18: ...18 User part...
Страница 25: ...Installation Maintenance and Service part 0313279_TWISTER II_UKUK_V1 1 18 02 2019 25...
Страница 26: ...26 User part...
Страница 34: ...34 Installation Maintenance and Service part...
Страница 42: ...Fig Venting systems IMD 1353 R0 C43 C13 C53 B23 C33 42 Installation Maintenance and Service part...
Страница 54: ...54 Installation Maintenance and Service part...
Страница 56: ...56 Installation Maintenance and Service part...
Страница 66: ...66 Installation Maintenance and Service part...
Страница 72: ...72 Installation Maintenance and Service part...
Страница 80: ...80 Installation Maintenance and Service part...
Страница 83: ...Fig Dimensions A D E 3 5 1 3 7 4 1 G 5 2 IMD 1349b R0 0313279_TWISTER II_UKUK_V1 1 18 02 2019 83...
Страница 87: ...13 6 Declaration of conformity 0313279_TWISTER II_UKUK_V1 1 18 02 2019 87...
Страница 90: ...90 Installation Maintenance and Service part...