13.4 Displayed warnings
Displayed warnings
Symptom
Cause
Solution
Remark
Q/T sensor not
correctly connected
Lead(s) loosened or
incorrectly connected
Appliance runs, but displays a warning
1. Properly connect Q/T sensor and the warning will disappear
2. If correctly wired but the warning remains, replace sensor
Note: To have the sensor connected or replaced, contact your
installation engineer
Collector temperature
excessive
Temperature S1 is
higher than T
collector
max
The pump in the solar circuit switches off, until S1 < 70°C
1. You can let the message disappear automatically by allowing
the heating fluid to cool down
2. You can also manually eliminate the message by pressing the
RESET and ENTER button simultaneously
Maximum burning
hours: Service required
The actual burning
hours have exceeded
the preset burning
hours
Appliance runs, but displays a warning
For maintenance to your appliance, contact your installation
engineer
Содержание SGS - 100
Страница 1: ...80 100 Installation User and Service Manual Installation User and Service Manual...
Страница 2: ...www aosmithinternational com your installer...
Страница 4: ...4 Instruction manual SGS gis...
Страница 8: ...Table of contents 8 Instruction manual SGS...
Страница 12: ...Introduction 12 Instruction manual SGS 1 gis...
Страница 30: ...Installation 30 Instruction manual SGS 3 is Types of appliances IMD 0468 R0 C43 C13 C53 B23 C33...
Страница 44: ...Installation 44 Instruction manual SGS 3 is...
Страница 62: ...Shutting down 62 Instruction manual SGS 10 gis...
Страница 92: ...Maintenance frequency 92 Instruction manual SGS 14 is...
Страница 101: ...Instruction manual SGS 101 is...
Страница 106: ...Appendices 106 Instruction manual SGS 17 is...
Страница 108: ...Appendices 108 Instruction manual SGS 17 is...