Filling
50
Instruction manual SGS
5
gis
7. Stop the glycol pump as soon as the pressure gauge on the pump station
begins to rise.
8. Completely bleed the system of air at the air bleed point (26, see installation
diagram).
9. Close the air bleed when no further air comes out.
10. Repeat steps 6 through 9 until glycol runs out of the air bleed (26).
Note
The system does not need be filled to a certain pressure. The pressure in
the system will increase when the fluid heats up and expands.
11. Switch off the glycol pump.
12. Close the valve of the inlet combination and disconnect the glycol pump
(including the hoses).
Note
Dispose of the residual glycol in the filler hose in an environment-friendly
manner, and according to local regulations.
Caution
The very first time the appliance is started, the correct fluid must be
set
(12.8.2 "Setting the heating fluid type in the solar heating system")
using the
Service Menu.
Note
If the system is equipped with a drain-back tank, then the system must be
filled to a certain pressure. For the installation and filling of a drain-back tank,
please refer to the installation and users manual of the solar collector.
Содержание SGS - 100
Страница 1: ...80 100 Installation User and Service Manual Installation User and Service Manual...
Страница 2: ...www aosmithinternational com your installer...
Страница 4: ...4 Instruction manual SGS gis...
Страница 8: ...Table of contents 8 Instruction manual SGS...
Страница 12: ...Introduction 12 Instruction manual SGS 1 gis...
Страница 30: ...Installation 30 Instruction manual SGS 3 is Types of appliances IMD 0468 R0 C43 C13 C53 B23 C33...
Страница 44: ...Installation 44 Instruction manual SGS 3 is...
Страница 62: ...Shutting down 62 Instruction manual SGS 10 gis...
Страница 92: ...Maintenance frequency 92 Instruction manual SGS 14 is...
Страница 101: ...Instruction manual SGS 101 is...
Страница 106: ...Appendices 106 Instruction manual SGS 17 is...
Страница 108: ...Appendices 108 Instruction manual SGS 17 is...