Pump Motors

45

Level 2

A.O.Smith

2-SPEED MOTORS — HIGH SPEED START SCHEMATIC
DIAGRAMS AND RECONNECTION INSTRUCTIONS FOR

REMOTE OPERATION

2-Speed with Hi - Low Switch

Mounted on Motor Canopy

RECONNECTION FOR REMOTE  SWITCH OPERATION

BLACK

BLACK

PURPLE

CANOPY SWITCH

LINE VOLTS

YELLOW MUST BE CONNECTED
TO BOTTOM TERMINAL WITH
SWITCH IN POSITION SHOWN

START  - X & Y CLOSED   Z OPEN
RUN 

- X & Y OPEN   

Z CLOSED

RED

RED

HI

WHITE

CAPACITOR

START

YELLOW

LOW

YELLOW

HI-LOW SWITCH

PURPLE

REMOVE BOTH YELLOW LEADS
FROM ‘A’ TERMINALAND CONNECT
TO TERMINALL1.

REMOVE BLACK LEAD FROM HI-LOW
SWITCH AND CONNECT IT TO
TERMINALA.

LEAVE SWITCH IN CANOPYAND
LEAVE PURPLE LEAD CONNECTED
TO SWITCH.

CONNECT POWER SUPPLY LINES TO
TERMINALBOARD

L2-L1

HIGH SPEED

L2-A

LOW SPEED

BEFORE REPLACING MOTOR
CANOPY, BE SURE ALLLEADS ARE
PROPERLY PLACED TO PREVENT
DAMAGE FROM GOVERNOR AND/OR
CANOPY.

NOTE:

Several different connections have been used in production. If the wiring on the
motor you are reconnecting does not match these diagrams contact A.O. Smith and
we will FAX or mail a connection for that model.

Содержание PT1072

Страница 1: ...T PUMPS INSTALLATION TIPS REPAIR TROUBLESHOOTING OTHER MODULES INCLUDE HEATING VENTILATION AIR CONDITIONING REFRIGERATION MOTORS GENERAL PURPOSE MOTORS SPECIAL PURPOSE MOTORS PUMP MOTORS A O SMITH A O...

Страница 2: ...ly 32 Single Speed Motor Typical Schematic Diagrams 33 Motor Assembly 36 How To Replace Bearings 37 Bearing Information Table 39 Recommended Tools 39 Motor Reassembly 40 2 Speed Motors 40 Start Switch...

Страница 3: ...no capaci tors 2 Capacitor Start This is the most common single phase motor found on in ground pool and jet pump appli cations The starting torque is higher 150 175 of full load and starting current l...

Страница 4: ...rs and Standard 778 applies to jet pump motors The motors are two pole 3450 RPM designs or two pole four pole 1725 RPM designs The two pole design is used because it runs cooler and moves more water T...

Страница 5: ...load has failed you should look for other prob lems Its failure is often a symptom of another problem The pumps are designated centrifugal since the motor spins an impeller which moves the water by c...

Страница 6: ...ic or velocity energy into the water As the water is propelled to the outer edge of the impeller there is a reduction in pressure at the eye of the impeller creating a vacuum figure 6 The combination...

Страница 7: ...eed motor 3450 1725 for energy sav ings during low traffic periods on pool or spa motors The load on the motor is reduced drasti cally but you also do not get the turn over rate of the high speed In t...

Страница 8: ...the total horse power output Find it on the motor s name plate Use this equation The total horsepower times x the service factor of the replacement motor must be equal to or greater than that of the...

Страница 9: ...ted tub motors also operate on the principle of centrifugal force Pool and spa motors are two pole 3450 RPM designs The two speed versions are 3450 1725 Four pole windings are used on the low speed Th...

Страница 10: ...eplate indicating a non standard mount Even though the mount is not standard per NEMA it has become standard among the pump manufactur ers Spas and jetted tubs may sometimes be sim ilar in looks and c...

Страница 11: ...bearing It is not recommended that a jet pump motor be used as a replacement for a pool pump motor even though horsepower and mountings may be equivalent The pool motor will have a ground bonding lug...

Страница 12: ...olt connection and 207 volts to 253 volts on the 230 volt connection At 207 volts the amps will be higher and the RPM will be approx imately 25 lower If the system is rated at 208 volts or 200 volts a...

Страница 13: ...ion so that the amps may be easily checked or the connections are made so that a loop in the wire is available for checking amps If total horsepower or horsepower times ser vice factor is difficult fo...

Страница 14: ...2 1 90 95 3 4 1 27 95 3 4 1 65 1 25 1 1 25 1 25 1 1 65 1 65 1 1 2 1 10 1 65 1 1 2 1 47 2 20 2 1 10 2 20 2 1 30 2 60 2 1 2 1 04 2 60 Uprated Uprated Uprated Uprated Uprated CAPACITORS It is recommende...

Страница 15: ...g Most jet pumps use open drip proof motors ODP When used in a vertical application out doors a different or additional rain canopy is required A separate dog house or motor cover such as the Blue Dev...

Страница 16: ...maged by the dry oper ating condition it will leak and probably allow moisture into the motor bearing Jet pumps operate on the principle of centrifu gal force The motor spins the impeller which does t...

Страница 17: ...jet pumps may be configured for either shallow or deep well applications Shallow well systems use one pipe into the water source and deep well systems use two pipes One pipe provides water to operate...

Страница 18: ...he amount of air pressure in the system As water is pumped air in the tank is com pressed until system pressure reaches the cut out level The most popular tanks have a bladder or diaphragm which separ...

Страница 19: ...ted at twenty starts of three second duration per hour Rapid cycling causes heat to build up which may cause failure Premature wear also occurs on the start switch When a pump s flow decreases the pre...

Страница 20: ...ngle voltage 115 or 230 for example or dual voltage 115 230 On original equipment 115 volt 1 3 and 1 2 HP units are common since there is enough volume to warrant a separate model with a slightly lowe...

Страница 21: ...n provides many clues to help determine the cause Did the motor fail due to a defect or old age or was its failure hastened by the application or environment The application is the only place an attem...

Страница 22: ...for pump motors The calculations were based on motors with the highest starting currents Larger wire sizes reduce the voltage drop at the motor in both the start and run modes A lower voltage drop mea...

Страница 23: ...h operation See if there is evidence of the rotor striking the stator Check for internal corrosion cracked end frames clogged fan or other obstruction within the motor Check pump for obstructions bind...

Страница 24: ...leaves lint and bugs and small lizards may plug air passages If the motor has an internal cooling fan is it intact and functioning properly Application overload In cases of flooded suc tion or positiv...

Страница 25: ...ion ELECTRICAL SHOCK Check motor windings all motor wiring and capacitor for ground PROTECT AGAINST MOISTURE The open drip proof type motors discussed here may be used outside but their life expectanc...

Страница 26: ...start making noise failure is imminent If the seal leaks and is not replaced the bear ings may also be ruined A new seal should be installed any time a motor is replaced A slinger or flinger should a...

Страница 27: ...ge use the next higher range DIGITAL OHMMETER MULTIMETER Direct reading digital ohmmeters are readily available in the field To use this type Make sure all motor leads are disconnected from the power...

Страница 28: ...r adequate wire size Look for loose terminals and connections or pitted contacts check pres sure switch and pump disconnect switch Check voltage at service entrance If not with in 10 contact power com...

Страница 29: ...ed which would remove the plat ing and cause early failure They may be cleaned by wiping with a piece of cardboard or paper bag Reconnect power Start motor Visually check the action of the switch and...

Страница 30: ...slightly On models with two screws turn the switch adjustment screw until the correct clearance is obtained When finished tighten the adja cent switch screw to secure the switch to the bracket Under n...

Страница 31: ...d moisture could show resistance to ground below 10K and still run satisfactorily A cleaning may be in order Readings may vary from day to day depending upon the humidi ty levels Approximately 25K at...

Страница 32: ...minal WINDING CONTINUITY For typical single phase dual voltage only capaci tor start single speed motor connected for 230V Set meter to R x 1 For single voltage motors check between L1 and L2 Slip a h...

Страница 33: ...Attach one probe to each terminal ohmmeter needle should move rapidly to right then slowly drift to the left Low ohm reading to high ohm value If a digital meter is used readings should start low and...

Страница 34: ...oblem not just a defective over load 1 2 PUMP DISASSEMBLY Wrench flats on shaft have been provided to facilitate impeller removal Insert a 7 16 open end wrench under governor assembly and hold while u...

Страница 35: ...p Motors 33 Level 2 A O Smith SINGLE SPEED MOTOR TYPICAL SCHEMATIC DIAGRAMS Capacitor Start Induction Run Single Speed EXT WIRE ROUTING Dual Voltage Single Speed Capacitor Start With Voltage Change Pl...

Страница 36: ...34 Pump Motors Level 2 A O Smith Capacitor Start Capacitor Run Single Speed SWITCH RUN CAP...

Страница 37: ...Pump Motors 35 Level 2 A O Smith SINGLE SPEED MOTOR TYPICAL SCHEMATIC DIAGRAMS Capacitor Start or Split Phase Single Voltage on Winding Protector Capacitor not shown in schematic SWITCH...

Страница 38: ...s in baffles type of protector type of flange and bearing construction When disassembling make sure you note the exact location of all com ponents so they can be reassembled in the proper order This i...

Страница 39: ...ps as necessary Refer to the table for the size tube needed to install new bearing s It is important to press only on the bearing inner race The bearing will be damaged if the outer race surface is us...

Страница 40: ...ng the proper size tube and a mallet or use a press Attach any other parts as used to the short shaft end Compare the rotor and shaft parts assembly shown on the previous pages with the order of assem...

Страница 41: ...ions show how the bear ing installation tube is used to install new bearings RECOMMENDED TOOLS Bearing Installation Tube Dimensions In Inches 2 Bearing Dimensions A O Smith Bearing Part No 1 Outer Dia...

Страница 42: ...to elaborate and exotic automatic systems Thus troubleshooting two speed systems requires an extensive knowledge of both motors and controls Two speed motors are built with and without high low switc...

Страница 43: ...ufficient tension against the screw Tighten only when adjusting If the screw is loosened it should be removed and the U bracket should again be opened slightly Under no circumstances should switch con...

Страница 44: ...HIGH SPEED START WHITE COMMON FROM START WINDING RED TRACER BLACK TO 3 YELLOW TO 1 4 POLE MAIN 2 POLE MAIN START CAPACITOR LOW HI YELLOW TO 5 YELLOW TO 1 TO 5 TERMINAL 1 TERMINAL 5 TERMINAL 4 TERMINAL...

Страница 45: ...le windings When the control calls for high speed run the start switch automatically switches the motor to high WHITE COMMON LOW HI YELLOW TO 4 BLACK TO 5 BLACK 1 TO 5 TERMINAL 1 TERMINAL 5 TERMINAL 2...

Страница 46: ...h 2 SPEED MOTORS HIGH SPEED START SCHEMATIC DIAGRAM 2 Speed for Remote Switch Operation LINE VOLTS HIGH SPEED LINE VOLTS LOW SPEED BLACK YELLOW START X Y CLOSED Z OPEN RUN X Y OPEN Z CLOSED BLACK RED...

Страница 47: ...W LOW YELLOW HI LOW SWITCH PURPLE REMOVE BOTH YELLOW LEADS FROM A TERMINALAND CONNECT TO TERMINALL1 REMOVE BLACK LEAD FROM HI LOW SWITCH AND CONNECT IT TO TERMINALA LEAVE SWITCH IN CANOPYAND LEAVE PUR...

Страница 48: ...L2 L1 HIGH SPEED L2 A LOW SPEED 2 SPEED MOTORS HIGH SPEED START SCHEMATIC DIAGRAMS AND RECONNECTION INSTRUCTIONS FOR REMOTE OPERATION 2 Speed with Hi Low Switch Mounted in External Box START BLACK CAP...

Страница 49: ...FR 2 Electrical Determine operating voltage phase max amps and hertz or cycles 3 Horsepower Multiply nameplate horsepower times the service factor to find total horsepower The total horsepower of the...

Страница 50: ...lace ment C Always install a new seal when reassembling a pump or installing a replacement motor D Be sure the motor is connected for the system voltage Most A O Smith dual voltage pump motors are fac...

Страница 51: ...If an external motor cover is used be certain it does not trap moisture or allow cooling air to recirculate D Don t store or use chemicals close to the motor E A running motor that is too hot to touch...

Страница 52: ...531 NORTH FOURTH STREET TIPP CITY OH 45371 937 667 6800 FAX 937 667 5873 www aosmithmotors com 2001 A O Smith Corporation Bulletin 3300 3 01...

Отзывы: