If necessary, create a heat demand:
Use a hot water draw-off point to tap water, or
Raise the setpoint of the water temperature, refer to Set the water
temperature (see section 4.2.2).
Wait until the measured value on the CO
2
meter remains stable for some time. This
can take several minutes.
Compare the full load measured value to the value from the appendix Gas details
(see section 13.3).
The CO
2
value at full load must be within ±1.0 vol% of the CO
2
value stated in the
table.
Caution
When the CO
2
value is not correct, refer to General errors (see section
12.1.1), CO
2
value (at full load) is not correct.
Do not use the water heater when the CO
2
value is not correct and this is not
caused by the restrictor, venturi, venting system or gas category:
Switch off the appliance.
Turn off the gas supply.
Put the cover back on the water heater.
Contact your supplier.
c
•
•
•
•
Set parameter
201
to
Lo
, refer to section Settings (see section 10).
Wait until the measured value on the CO
2
meter remains stable for some time. This
can take several minutes.
Compare the measured value to the value measured under full load.
The CO
2
value at partial load must be within ±0.3 vol% of the CO
2
value measured
under full load.
If necessary, use a hex driver to adjust the adjuster screw until the CO
2
value is
correct.
Turn the screw clockwise for a higher CO
2
value.
Turn the screw anticlockwise for a lower CO
2
value.
If applicable, set the temperature value back to the original value (parameter
002
).
Set parameter
201
to
dIS
, refer to Settings (see section 10).
Press [RESET]. The water heater goes into OFF mode.
Set the control switch on the side of the water heater to 0 to turn off the water
heater.
Remove the measurement probe of the CO
2
meter from the test nipple and place the
cap (1) back on the nipple (2).
Shut off the gas supply.
Fig. CO
2
value
1
2
1. Cap
2. Test nipple
6.
-
-
7.
8.
9.
10.
11.
12.
a.
b.
13.
14.
15.
16.
17.
18.
0312266_INNOVO_UKUK_V3.0, 2017-02-10
55
Содержание Innovo 12-160
Страница 6: ...6...
Страница 13: ...User part 0312266_INNOVO_UKUK_V3 0 2017 02 10 13...
Страница 14: ...14...
Страница 16: ...16 User part...
Страница 18: ...18 User part...
Страница 24: ...24 User part...
Страница 27: ...Installation Maintenance and Service part 0312266_INNOVO_UKUK_V3 0 2017 02 10 27...
Страница 28: ...28 User part...
Страница 36: ...36 Installation Maintenance and Service part...
Страница 43: ...Fig Venting systems 0312266_INNOVO_UKUK_V3 0 2017 02 10 43...
Страница 58: ...58 Installation Maintenance and Service part...
Страница 70: ...70 Installation Maintenance and Service part...
Страница 83: ...0312266_INNOVO_UKUK_V3 0 2017 02 10 83...
Страница 87: ...13 5 Declaration of conformity 0312266_INNOVO_UKUK_V3 0 2017 02 10 87...
Страница 90: ...90 Installation Maintenance and Service part...
Страница 92: ...92 Installation Maintenance and Service part...