Instruction manual GWV
59
gis
10
Shutting down
10.1 Introduction
This chapter describes:
•
Shutting the installation down for a brief period
("OFF mode")
;
•
Isolating the appliance from the mains
;
•
Shutting the appliance and storage tank down for
a long period
.
10.2 Shutting the installation down for a
brief period ("OFF mode")
To shut the installation down for a brief period, you
must activate the frost protection.
You can use the frost protection to prevent water
freezing in the appliance.
Activate the frost protection as follows:
1. Press the
button to select the main menu.
2. Use and to position the cursor in front of
OFF
.
Confirm with
.
The frost protection cuts in if the water temperature
drops below 5°C. The text
FROST
will then appear on
line one of the display. The appliance heats the water
to 20°C (T
set
) and drops back to the
OFF
mode.
Note
These values of 5°C and 20°C cannot be adjusted.
10.3 Isolating the appliance from the mains
The appliance should only be isolated from mains
power in the correct way. The correct procedure is as
follows:
1. Activate the
MENU
with
.
2. Position the cursor in front of
OFF
.
3. Confirm
OFF
with
.
Caution
Failure to wait until the fan stops purging can
cause damage to the appliance.
4. Wait until the fan has stopped. The icon then
goes out.
5. Switch the appliance
OFF (position 0)
using the
ON/OFF switch on the control panel.
6. Isolate the appliance from the power supply by
setting the isolator between the appliance and the
mains power supply to position 0.
10.4 Shutting the appliance and storage
tank down for a long period
Drain the appliance and storage tank if you are
shutting the installation down for a longer period of
time. Proceed as follows:
1. Isolate the appliance from the power
supply
(10.3 "Isolating the appliance from the
mains")
.
2. Shut off the gas supply.
3. Close the stop valve in the hot water pipe.
4. Close the supply valve of the protected cold supply
setup.
5. Open the drain valve
6. Open the air valves to the appliance and storage
tank so that the water can run out of them
completely.
OFF
13:45 Thursday
6ÉC
FROST PROTECTION
ACTIVATED
MENU
»OFF
^ ON
È WEEK PROGRAM
GENESIS
IMD-0511 R1
Содержание GWV - 120
Страница 2: ...www aosmithinternational com your installer ...
Страница 4: ...4 Instruction manual GWV gis ...
Страница 8: ...Table of contents 8 Instruction manual GWV ...
Страница 12: ...Introduction 12 Instruction manual GWV 1 gis ...
Страница 40: ...Installation 40 Instruction manual GWV 3 is ...
Страница 42: ...Conversion to a different gas category 42 Instruction manual GWV 4 is ...
Страница 46: ...Filling 46 Instruction manual GWV 5 gis ...
Страница 58: ...Starting and running 58 Instruction manual GWV 9 gis ...
Страница 60: ...Shutting down 60 Instruction manual GWV 10 gis ...
Страница 72: ...Service program 72 Instruction manual GWV 12 is ...
Страница 86: ...Troubleshooting 86 Instruction manual GWV 13 gis ...
Страница 88: ...Maintenance frequency 88 Instruction manual GWV 14 is ...
Страница 98: ...Appendices 98 Instruction manual GWV 17 is ...
Страница 100: ...Instruction manual GWV 100 ...
Страница 102: ...0307 971 4 0 UK Index Instruction manual GWV ...