 Important Notes and Warnings

• 

This heater is certified to be installed using PVC, 
CPVC,  or polypropylene plastic vent material. Check 
with your local authorities to determine which materials 
are allowed in your area. All venting material and 
components must be joined with the approved primer/
cleaner and solvent cement or mechanical seals (see 
“Polypropylene Vent Systems”). 

• 

Do not common vent this heater with any other 
appliance.

• 

Do not allow insulation to cover the vent piping.

• 

During operation the plastic piping will expand as it 
heats up and contract as it cools down. This is normal 
for this type of venting. Rigidly fastening the vent piping 
can cause undue stress that may result in the cracking 
or fracturing the vent piping material. A fracture of the 
venting pipe may pose a serious safety hazard. To 
prevent stressing of the vent system, all hangers and 
supports must allow the vent piping freedom to move.

• 

Use long sweep elbows wherever possible. Closely-
coupled elbows and short radius elbows can reduce 
the venting capacity.

• 

All power vented water heaters generate a certain 
amount of operational noise. In order to minimize noise 
transmission to the support structure, use isolation pads 
between the pipe hangers and the vent pipe.

• 

Most power vent installations develop some 
condensation in the vent piping. When using long runs 
of venting or when the venting passes through cold or 
unheated areas, considerable amounts of condensate 
from the flue gases can develop. Provision must be 
made for the condensate to drain freely from the 
system or to be collected in a condensate trap(s) that 
can be drained. Damage or fracture of the vent piping 
may occur if the condensate is allowed to collect and 
freeze. Pooling of condensate can restrict airflow and 
can cause nuisance failures of the system.

• 

In regions that experience freezing conditions, slope the 
venting back towards the heater so that the condensate 
will drain back to the blower and be collected in the 
condensate trap. Draining condensate out through the 
termination can result in vent freeze up resulting in a 
nuisance shut down situation. Ice formed from frozen 
condensate can cause a safety hazard. See also notes 
in the “Venting” section.

   Venting terminations and sizing

• 

Heaters are supplied with a 3”x3” rubber coupling to 
attach the venting to the blower and a 3”, 45° vent 
termination elbow.

• 

Supplied with this heater are several vent termination 
screens (see Figure 26).

Installed in the vent termination elbow, the vent screen 
is required to keep foreign objects, rodents and small 
birds from entering the venting system. These screens 
have been sized to ensure maximum energy efficiency of 
the vent system based on the “equivalent length” of the 
vent piping. CHOOSE ONLY the ONE SCREEN THAT 
MATCHES YOUR VENTING CONFIGURATION (see 

Figure 26). How to determine the “equivalent length” is 
shown in Figure 27 and in Table 2.

  Vent screen installation

Note: The correct vent screen is required for proper 
operation of this water heater. Failure to install and secure 
the correct screen can result in improper vent operation 
which can result in the water heater overheating or 
nuisance shut downs.

• 

Install the appropriate vent screen into the vent 
termination elbow.

• 

Gently push the screen into the termination elbow until 
it sits against the inside shoulder.

• 

The metal wire screens are self-securing.

• 

Plastic screens must be secured with (2) screws:
1.  Install plastic screen into elbow (see Figure 26).
2.  Orient screen as shown in see Figure 26 with an 

opening at the bottom of the assembly and the 
smooth side facing in.

3.  Ensure screen is fully seated against shoulder in 

elbow.

4.  Secure screen in place with screws (field supplied) 

(see Figure 26).

with 3 in. venting (short)

with 3 in. venting (long)

VENT LENGTH LESS THAN OR 

EQUAL TO 6 EQUIVALENT METRES 

(20 EQUIVALENT FT.) USE THIS 

SCREEN (SUPPLIED).

VENT LENGTH GREATER THAN 

6 EQUIVALENT METRES 

(20 EQUIVALENT FT.) 

USE THIS SCREEN (SUPPLIED).

with 4 in. venting

VENT LENGTH GREATER THAN 

15.2 EQUIVALENT METRES 

(50 EQUIVALENT FT.) USE THIS 

SCREEN (SUPPLIED).

ELBOW

#6 SHEET METAL 

SCREW (FIELD 

SUPPLIED)

PLASTIC 
SCREEN

SHOULDER

OPEN 

POCKET

CLOSED 
POCKET

POCKETS 
FACING OUT

Figure 26 

Содержание GPVX 75L Series

Страница 1: ...210 211 Do not store or use gasoline or other flam mable vapours and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch...

Страница 2: ...ping 20 Sediment Traps 21 Filling The Water Heater 22 Venting 22 Termination Clearances Sidewall Power Vent 23 Blower Assembly Installation 24 Planning The Vent System 24 Polypropylene Vent Systems 25...

Страница 3: ...ed to comply with a maximum weighted average of 0 25 lead content as required in some areas IMPORTANT DEFINITIONS Qualified Installer A qualified installer must have ability equivalent to a licensed t...

Страница 4: ...g BURN HOT HOT DANGER Read instruction manual before installing using or servicing water heater Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this water heater...

Страница 5: ...er air intake Do not place chemical vapour emitting products near water heater Gas and carbon monoxide detectors are available No vent damper installation is compatible with this power vented water he...

Страница 6: ...entire manual carefully If you don t follow safety rules the water heater will not operate properly It could cause DEATH SERIOUS BODILY INJURYAND OR PROPERTY DAMAGE This manual contains instructions f...

Страница 7: ...Gas Shut off Valve 25 Gas Supply 26 Baffle Assembly 27 Rating Plate 28 Blower with Power Cord see Figure 6 29 Rubber Coupling see Figure 6 30 Inlet Water Shut off Valve 31 Union water connection 32 H...

Страница 8: ...ion harness has 120 VAC In operation See Planning The Vent System Condensate and Blower Assembly Installation for more information REPLACEMENT PARTS AND DELIMING PRODUCTS Replacement parts and recomme...

Страница 9: ...NG CONNECTIONS FOR SPACE HEATING NOTE THE T P VALVE DISCHARGE PIPE SHALL BE PIPED DIRECTLY TO THE DRAIN OR EXTERNAL TO THE BUILDING Figure 8 This appliance has been design certified as complying with...

Страница 10: ...talled at water heater see Figure 8 Figure 9 or at hot water taps to further reduce system water temperature Mixing valves are available at plumbing supply stores Consult a Qualified Installer or Serv...

Страница 11: ...wiring diagram for the correct electrical connections After making all electrical connections completely fill the tank with water and check all connections for leaks Open the nearest hot water faucet...

Страница 12: ...water heater there is a risk of flammable vapours entering the combustion chamber being ignited by the burner flame and causing a flashback In order to detect such flammable vapours before they enter...

Страница 13: ...water heater s outer jacket and must be piped to an adequate drain The pan must have a maximum depth of 45mm 1 75 in Water heater life depends upon water quality water pressure and the environment in...

Страница 14: ...75mm 3 in in every direction or if the appliance is installed in an alcove or closet the entire floor must be covered by the panel Failure to heed this warning may result in a fire hazard Clearance fo...

Страница 15: ...sk of asphyxiation Never obstruct the flow of dilution ventilation air If you have any doubts or questions at all call your gas supplier Failure to provide the proper amounts of air can result in a fi...

Страница 16: ...Control System section in this manual This water heater should not be connected to any heating systems or components previously used with a non potable water heating appliance All piping components co...

Страница 17: ...e heat loss 7 If the local jurisdiction requires a back flow preventer in the cold water line an expansion tank of adequate size must be installed 8 Combo Heating Systems require higher water temperat...

Страница 18: ...ef valve operation water discharged from the valve due to excessive pressure build up The temperature pressure relief valve is not intended for the constant relief of thermal expansion This condition...

Страница 19: ...the discharge capacity of the valve No valve or other obstruction is to be placed between the T P valve and the tank Do not connect discharge piping directly to the drain unless a maximum of 300mm 12...

Страница 20: ...es to the water heater 4 Locate the slit running the length of a section of pipe insulation 5 Spread the slit open and slip the insulation over the cold water inlet pipe Apply gentle pressure along th...

Страница 21: ...Use joint compound or tape compatible with propane Leak test before operating heater Disconnect gas piping and shut off valve before pressure testing system Fire and Explosion Hazard WARNING Use pipe...

Страница 22: ...Check all water piping and connections for leaks Repair as needed VENTING All venting must comply with the current edition of the Natural Gas and Propane Installation Code B149 1 This heater is certi...

Страница 23: ...any other appliance 300mm 12 in D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 ft from the center line of the terminal 300mm 12 in K to a mecha...

Страница 24: ...nductor must be run with the circuit conductors and connected to the equipment grounding terminal or lead on the water heater see Figure 12 the wiring diagram g Close the panel on the junction box Mak...

Страница 25: ...ons in unconditioned space or having long horizontal or vertical vent runs can accumulate condensate Long lengths of venting that pass through cool cold areas will experience condensation The vent pip...

Страница 26: ...ndensate trap Draining condensate out through the termination can result in vent freeze up resulting in a nuisance shut down situation Ice formed from frozen condensate can cause a safety hazard See a...

Страница 27: ...quivalent metres 20 equivalent ft see Figure 26 Note The vent pipe must be supported every 1 2m 4 ft To prevent vibration and sagging it is recommended to use isolation pads when attaching straps to f...

Страница 28: ...E WALL 9 Insert the vent piping through this hole and secure into position Connect the vent pipe to the end termination elbow as shown in Figure 28 thru Figure 30 10 Dry fit all vent pipes elbows conn...

Страница 29: ...he rubber coupling Check that there is no stress on the connection or the vent piping that may be caused by twisting or bending 5 Tighten the upper clamp so that the vent piping is firmly secured in t...

Страница 30: ...blower outlet remove the four nuts with 11 32 nut driver see Figure 34 securing the flue collector to the blower housing Pull the blower assembly forward to free it from the mounting studs Rotate the...

Страница 31: ...n of Natural Gas and Propane Installation Code B149 1 Horizontal piping slopes at an upward pitch of 3mm 1 8 in rise per 1 2m 4 ft away from the water heater Not obstructed in any way Venting properly...

Страница 32: ...to the OFF position 5 Do not attempt to light manually 6 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above on this label If you don t smell...

Страница 33: ...e groups or if there is a local code or state law requiring certain temperature water at the hot water tap then you must take special precautions In addition to using the lowest possible temperature s...

Страница 34: ...n to a temperature that prevents the water in the water heater from freezing while still conserving energy GAS CONTROL VALVE THERMOSTAT 181 WHITE ON OFF SWITCH TEMPERATURE SETTING DIAL 83 C 181 F 21 C...

Страница 35: ...ndensate section in this manual OPERATIONAL CONDITIONS Smelly water Each water heater contains at least one anode rod for corrosion protection of the tank Certain water conditions will cause a reactio...

Страница 36: ...ting or deterioration something is wrong Call the local gas utility to correct the problem and clean or replace the flue and venting before resuming operation of the water heater BLOWER MAINTENANCE In...

Страница 37: ...LUTION AIR INTAKES COUPLING BLOWER FLUE COLLECTOR HOOD 11 32 NUTS MOUNTING PLATE GEAR CLAMP VENT PIPE MOTOR DRAIN PORT Figure 37 BURNER OPERATION AND INSPECTION Flood damage to a water heater may not...

Страница 38: ...g the anode rod if it is depleted Once the anode rod is depleted the tank will start to corrode eventually developing a leak Obtain a new anode rod from your local plumbing supplier or have a qualifie...

Страница 39: ...Pressure Relief Valve on the water heater weeps or discharges periodically it may be due to thermal expansion Note Excessive water pressure is the most common cause of temperature pressure relief val...

Страница 40: ...ater in the storage tank has drained and remove the hose 10 Follow instructions in the Filling The Water Heater section 11 Follow the lighting instructions on the label or see Lighting Instructions to...

Страница 41: ...aking D Small amounts of water from temperature pressure relief valve may be due to thermal expansion or high water pressure in your area E The temperature pressure relief valve may be leaking at the...

Страница 42: ...r Coupling see Figure 6 see also Figure 49 32 Hot Water Outlet Nipple 33 Anode under cap 34 Air Inlet Snorkel 35 Flue Collector 37 Aluminum Burner see Figure 3 see also Figure 46 38 Gas Orifice see Fi...

Страница 43: ...9 41 38 45 43 Figure 46 Propane LP main burner with igniter assembly item 17 in Figure 44 Flare Nut 42 44 40 46 39 41 38 45 43 21 Figure 47 20 Figure 48 28 49 6 29 48 47 51 50 Figure 49 Note For Natur...

Страница 44: ...O HOT 1 Thermostat is too high 2 Incorrect or missing vent screen in vent termination 3 Defective gas control valve thermostat 1 Turn temperature knob to lower setting 2 Check venting for correct scre...

Страница 45: ...tilation to water heater Check flue way flue baffle and burner 3 Check with gas utility company 4 Replace with correct orifice see rating plate 5 Clean locate source and correct 6 Replace gas control...

Страница 46: ...d for combustion and dilution of flue temp 3 Increase ventilation to lower room temperature 4 Install correct orifice 5 Install and secure proper vent termination screen RESETTING THE HEATER CONTROL S...

Страница 47: ...idelines to diagnose the problem before attempting corrective action See also Flammable Vapour Sensor LED Flash Sequence Control Status Short flash once every four seconds IDLE no call for heat no fau...

Страница 48: ...is connected ii Turn power to the heater OFF check the capacitor rating 3uF 5 iii Turn power to the heater OFF replace the blower assembly 2 Ensure the air pressure sensing tubes are properly connect...

Страница 49: ...7 If there are excessive restrictions in the air intake pipe the air pressure switch N C will open 8 Check air pressure switch performance Check blower vacuum with a manometer Compare with air pressur...

Страница 50: ...50 100271597 NOTES...

Страница 51: ...100271597 51 NOTES...

Страница 52: ...599 Hill St West Fergus ON N1M 2X1 Phone 888 479 8324 Fax 519 787 5500 www hotwater com...

Отзывы: