 COMBO  HEATING

This section serves as a guide for the installation and use 
of “Combo” heating systems utilizing a domestic water 
heater that has been specifically approved for such use. 
It is written for those knowledgeable in the required trades 
and professionals involved in the design and installation 
of Combo Heating Systems.
It is the responsibility of the installer/designer to follow all 
applicable codes to ensure the effectiveness and safety 
of the installation.

 System  Requirements

The following requirements must be met for the installation 
of Combo Heating Systems:
1.  All components used for the distribution of water in 

the heating loop must be suitable for potable water. 
These include all piping, fittings, solder and fluxes, 
pumps for circulation of water, valves, etc.

2.  The water heater must not be connected to a hydronic 

heating system that has been used previously. This 
heater is not designed to be used in a space heating 
only application.

3.  No boiler treatment chemicals of any kind shall be 

introduced into the system.

4.  The Combo System components must be selected 

and sized to meet and maintain the total calculated 
demands for both domestic service hot water 
and space heating requirement. The sizing and 
installation must be performed in accordance with 
good engineering practice such as

 “ASHRAE 

Handbooks”, HRAI’s Unified Combo Guidelines, 
“Hydronics Institute Manuals”, ANSI Z223.1, CSA 
F280, National/Provincial Building Codes

, ANSI 

and/or codes having jurisdiction.

5.  The air handler (fan coil) and/or the circulating pump 

in a baseboard hydronic loop will require a dedicated 
120V circuit. This must be provided and identified for 
this purpose.

6.  All piping between the water heater and the air handler 

or hydronic baseboard loop must be adequately 
insulated to reduce heat loss.

7.  If the local jurisdiction requires a back-flow preventer 

in the cold water line, an expansion tank of adequate 
size must be installed.

8.  “Combo” Heating Systems require higher water 

temperatures than other applications. When the 
system is used to supply water for Combo Heating 
applications, a means, such as mixing valve, must be 
installed to temper the water in order to reduce scald 
hazard potential (see Figure 17 & Figure 18).

 Installation

The heating mode may be one of the following options:
A.  A fan coil/air handler (Figure 17).
B.  A hydronic baseboard (finned tube) loop/In floor 

heating (Figure 18).

The following is a list of requirements for the installation 
of option A or B.

1.  Install shut-off valves and unions so that the water 

heater can be isolated from the heating module should 
servicing of the water heater become necessary.

2.  Install a drain valve at the lowest point of the heating 

loop so that water can be drained from the heating 
module without affecting the water heater.

3.  If the air handler does not have a venting means at 

the highest point of the piping arrangement, install 
an air bleed at the highest point of the plumbing 
arrangement.

4.  Install a solenoid valve before the side tap return to 

prevent cold water from continuously entering the 
water heater. Failure to install a solenoid valve could 
cause “stacking” and cause the T&P valve to open.

WATER 

HEATER

HOT 

OUTLET

EXPANSION TANK 
(OPTIONAL)

MIXING 

VALVE

COLD 
INLET

CHECK VALVE (IF USED 
REQUIRES EXPANSION TANK)

COLD SUPPLY

HOSE BIB 

(OPTIONAL)

FLOW 
CONTROL

SUPPLY

RETURN

CHECK 
VALVE

EXTERNAL 
CIRCULATOR

AIR 

HANDLER

HOT WATER 

TO HOUSE 

FIXTURE

C
H

M

INTERNAL 

CIRCULATOR

DRAIN/
PURGE 
VALVE

SOLENOID
VALVE

 

Figure 17 

WATER 

HEATER

HOT 

OUTLET

EXPANSION TANK 
(OPTIONAL)

MIXING 

VALVE

COLD 
INLET

CHECK VALVE (IF USED 
REQUIRES EXPANSION TANK)

COLD SUPPLY

HOSE BIB 

(OPTIONAL)

FLOW 
CONTROL

SUPPLY

RETURN

CHECK 
VALVE

EXTERNAL 
CIRCULATOR

HOT WATER 

TO HOUSE 

FIXTURE

C
H

M

HYDRONIC 

BASEBOARDS 

(SERIES 

CONNECTED 

SHOWN)

SOLENOID 
VALVE

 

Figure 18 

Содержание GPVX 75L Series

Страница 1: ...210 211 Do not store or use gasoline or other flam mable vapours and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch...

Страница 2: ...ping 20 Sediment Traps 21 Filling The Water Heater 22 Venting 22 Termination Clearances Sidewall Power Vent 23 Blower Assembly Installation 24 Planning The Vent System 24 Polypropylene Vent Systems 25...

Страница 3: ...ed to comply with a maximum weighted average of 0 25 lead content as required in some areas IMPORTANT DEFINITIONS Qualified Installer A qualified installer must have ability equivalent to a licensed t...

Страница 4: ...g BURN HOT HOT DANGER Read instruction manual before installing using or servicing water heater Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this water heater...

Страница 5: ...er air intake Do not place chemical vapour emitting products near water heater Gas and carbon monoxide detectors are available No vent damper installation is compatible with this power vented water he...

Страница 6: ...entire manual carefully If you don t follow safety rules the water heater will not operate properly It could cause DEATH SERIOUS BODILY INJURYAND OR PROPERTY DAMAGE This manual contains instructions f...

Страница 7: ...Gas Shut off Valve 25 Gas Supply 26 Baffle Assembly 27 Rating Plate 28 Blower with Power Cord see Figure 6 29 Rubber Coupling see Figure 6 30 Inlet Water Shut off Valve 31 Union water connection 32 H...

Страница 8: ...ion harness has 120 VAC In operation See Planning The Vent System Condensate and Blower Assembly Installation for more information REPLACEMENT PARTS AND DELIMING PRODUCTS Replacement parts and recomme...

Страница 9: ...NG CONNECTIONS FOR SPACE HEATING NOTE THE T P VALVE DISCHARGE PIPE SHALL BE PIPED DIRECTLY TO THE DRAIN OR EXTERNAL TO THE BUILDING Figure 8 This appliance has been design certified as complying with...

Страница 10: ...talled at water heater see Figure 8 Figure 9 or at hot water taps to further reduce system water temperature Mixing valves are available at plumbing supply stores Consult a Qualified Installer or Serv...

Страница 11: ...wiring diagram for the correct electrical connections After making all electrical connections completely fill the tank with water and check all connections for leaks Open the nearest hot water faucet...

Страница 12: ...water heater there is a risk of flammable vapours entering the combustion chamber being ignited by the burner flame and causing a flashback In order to detect such flammable vapours before they enter...

Страница 13: ...water heater s outer jacket and must be piped to an adequate drain The pan must have a maximum depth of 45mm 1 75 in Water heater life depends upon water quality water pressure and the environment in...

Страница 14: ...75mm 3 in in every direction or if the appliance is installed in an alcove or closet the entire floor must be covered by the panel Failure to heed this warning may result in a fire hazard Clearance fo...

Страница 15: ...sk of asphyxiation Never obstruct the flow of dilution ventilation air If you have any doubts or questions at all call your gas supplier Failure to provide the proper amounts of air can result in a fi...

Страница 16: ...Control System section in this manual This water heater should not be connected to any heating systems or components previously used with a non potable water heating appliance All piping components co...

Страница 17: ...e heat loss 7 If the local jurisdiction requires a back flow preventer in the cold water line an expansion tank of adequate size must be installed 8 Combo Heating Systems require higher water temperat...

Страница 18: ...ef valve operation water discharged from the valve due to excessive pressure build up The temperature pressure relief valve is not intended for the constant relief of thermal expansion This condition...

Страница 19: ...the discharge capacity of the valve No valve or other obstruction is to be placed between the T P valve and the tank Do not connect discharge piping directly to the drain unless a maximum of 300mm 12...

Страница 20: ...es to the water heater 4 Locate the slit running the length of a section of pipe insulation 5 Spread the slit open and slip the insulation over the cold water inlet pipe Apply gentle pressure along th...

Страница 21: ...Use joint compound or tape compatible with propane Leak test before operating heater Disconnect gas piping and shut off valve before pressure testing system Fire and Explosion Hazard WARNING Use pipe...

Страница 22: ...Check all water piping and connections for leaks Repair as needed VENTING All venting must comply with the current edition of the Natural Gas and Propane Installation Code B149 1 This heater is certi...

Страница 23: ...any other appliance 300mm 12 in D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 ft from the center line of the terminal 300mm 12 in K to a mecha...

Страница 24: ...nductor must be run with the circuit conductors and connected to the equipment grounding terminal or lead on the water heater see Figure 12 the wiring diagram g Close the panel on the junction box Mak...

Страница 25: ...ons in unconditioned space or having long horizontal or vertical vent runs can accumulate condensate Long lengths of venting that pass through cool cold areas will experience condensation The vent pip...

Страница 26: ...ndensate trap Draining condensate out through the termination can result in vent freeze up resulting in a nuisance shut down situation Ice formed from frozen condensate can cause a safety hazard See a...

Страница 27: ...quivalent metres 20 equivalent ft see Figure 26 Note The vent pipe must be supported every 1 2m 4 ft To prevent vibration and sagging it is recommended to use isolation pads when attaching straps to f...

Страница 28: ...E WALL 9 Insert the vent piping through this hole and secure into position Connect the vent pipe to the end termination elbow as shown in Figure 28 thru Figure 30 10 Dry fit all vent pipes elbows conn...

Страница 29: ...he rubber coupling Check that there is no stress on the connection or the vent piping that may be caused by twisting or bending 5 Tighten the upper clamp so that the vent piping is firmly secured in t...

Страница 30: ...blower outlet remove the four nuts with 11 32 nut driver see Figure 34 securing the flue collector to the blower housing Pull the blower assembly forward to free it from the mounting studs Rotate the...

Страница 31: ...n of Natural Gas and Propane Installation Code B149 1 Horizontal piping slopes at an upward pitch of 3mm 1 8 in rise per 1 2m 4 ft away from the water heater Not obstructed in any way Venting properly...

Страница 32: ...to the OFF position 5 Do not attempt to light manually 6 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above on this label If you don t smell...

Страница 33: ...e groups or if there is a local code or state law requiring certain temperature water at the hot water tap then you must take special precautions In addition to using the lowest possible temperature s...

Страница 34: ...n to a temperature that prevents the water in the water heater from freezing while still conserving energy GAS CONTROL VALVE THERMOSTAT 181 WHITE ON OFF SWITCH TEMPERATURE SETTING DIAL 83 C 181 F 21 C...

Страница 35: ...ndensate section in this manual OPERATIONAL CONDITIONS Smelly water Each water heater contains at least one anode rod for corrosion protection of the tank Certain water conditions will cause a reactio...

Страница 36: ...ting or deterioration something is wrong Call the local gas utility to correct the problem and clean or replace the flue and venting before resuming operation of the water heater BLOWER MAINTENANCE In...

Страница 37: ...LUTION AIR INTAKES COUPLING BLOWER FLUE COLLECTOR HOOD 11 32 NUTS MOUNTING PLATE GEAR CLAMP VENT PIPE MOTOR DRAIN PORT Figure 37 BURNER OPERATION AND INSPECTION Flood damage to a water heater may not...

Страница 38: ...g the anode rod if it is depleted Once the anode rod is depleted the tank will start to corrode eventually developing a leak Obtain a new anode rod from your local plumbing supplier or have a qualifie...

Страница 39: ...Pressure Relief Valve on the water heater weeps or discharges periodically it may be due to thermal expansion Note Excessive water pressure is the most common cause of temperature pressure relief val...

Страница 40: ...ater in the storage tank has drained and remove the hose 10 Follow instructions in the Filling The Water Heater section 11 Follow the lighting instructions on the label or see Lighting Instructions to...

Страница 41: ...aking D Small amounts of water from temperature pressure relief valve may be due to thermal expansion or high water pressure in your area E The temperature pressure relief valve may be leaking at the...

Страница 42: ...r Coupling see Figure 6 see also Figure 49 32 Hot Water Outlet Nipple 33 Anode under cap 34 Air Inlet Snorkel 35 Flue Collector 37 Aluminum Burner see Figure 3 see also Figure 46 38 Gas Orifice see Fi...

Страница 43: ...9 41 38 45 43 Figure 46 Propane LP main burner with igniter assembly item 17 in Figure 44 Flare Nut 42 44 40 46 39 41 38 45 43 21 Figure 47 20 Figure 48 28 49 6 29 48 47 51 50 Figure 49 Note For Natur...

Страница 44: ...O HOT 1 Thermostat is too high 2 Incorrect or missing vent screen in vent termination 3 Defective gas control valve thermostat 1 Turn temperature knob to lower setting 2 Check venting for correct scre...

Страница 45: ...tilation to water heater Check flue way flue baffle and burner 3 Check with gas utility company 4 Replace with correct orifice see rating plate 5 Clean locate source and correct 6 Replace gas control...

Страница 46: ...d for combustion and dilution of flue temp 3 Increase ventilation to lower room temperature 4 Install correct orifice 5 Install and secure proper vent termination screen RESETTING THE HEATER CONTROL S...

Страница 47: ...idelines to diagnose the problem before attempting corrective action See also Flammable Vapour Sensor LED Flash Sequence Control Status Short flash once every four seconds IDLE no call for heat no fau...

Страница 48: ...is connected ii Turn power to the heater OFF check the capacitor rating 3uF 5 iii Turn power to the heater OFF replace the blower assembly 2 Ensure the air pressure sensing tubes are properly connect...

Страница 49: ...7 If there are excessive restrictions in the air intake pipe the air pressure switch N C will open 8 Check air pressure switch performance Check blower vacuum with a manometer Compare with air pressur...

Страница 50: ...50 100271597 NOTES...

Страница 51: ...100271597 51 NOTES...

Страница 52: ...599 Hill St West Fergus ON N1M 2X1 Phone 888 479 8324 Fax 519 787 5500 www hotwater com...

Отзывы: