background image

8

NOTE:  1. For water heaters in locations with high ambient
temperatures (above 100°F) and/or insufficient dilution air, it is
recommended that CPVC or ABS pipe and fittings be used.  2.
The SUPPLIED VENT TERMINAL must be used in all cases.

4. The temperature of the flue gases leaving the blower is about

160°F after mixing the dilution air in the inlet adapter of the
blower.  Even with high concentrate of room air taken into the
vent system for dilution air,  there will be some installations
where condensate will be formed in the horizontal runs of
the vent system.  This condensate MUST NOT be allowed to
drain back into the fan unit.

One method to catch the condensate before it can run back
to the fan is to install a "TEE" mounted upside down and
capped, just past the first elbow, (Fig.9) of the vent pipe
system.  This set-up will require the installation of a small (1/
4-3/8 inch) plastic tube, with the proper trap, to drain the
condensate to a floor drain.

A second method to prevent the condensate from draining
back to the fan unit would be to install the vent system with a
slight, 1/8 inch per five foot of pipe maximum, downward slope
(max. of 5/8 inch).

Number of

3" Maximum

4" Maximum

90° Elbows

Pipe (Feet)

Pipe Feet

ONE (1)

25

55

TWO (2)

20

50

THREE(3)

15

45

FOUR (4)

10

40

FIVE (5)

- - -

35

TABLE 1

INSTALLATION OF SIDEWALL VENT SYSTEM

Before beginning installation of piping system thoroughly read
the section of this manual VENT PIPE PREPARATION.

If you are installing your system so that it vents through roof,
please refer to following section titled INSTALLATION OF
VERTICAL VENT SYSTEM.

VENT TERMINAL INSTALLATION, SIDEWALL

1. Install the vent terminal by using the cover plate as a template

to mark the hole for the vent pipe to pass through the wall.
BEWARE OF CONCEALED WIRING AND PIPING INSIDE THE
WALL.

2. If the Vent Terminal is being installed on the outside of a

finished wall, it may be easier to mark both the inside and
outside wall.  Align the holes by drilling a hole through the
center of the template from the inside through to the outside.
The template can now be positioned on the outside wall using
the drilled hole as a centering point for the template.

3. A)  MASONRY SIDE WALLS

Chisel an opening approximately one half inch larger than
the marked circle.

B)  WOODEN SIDE WALLS

Drill a pilot  hole approximately one quarter inch outside of
the marked circle.  This pilot hole is used as a starting point
for a saws-all or sabre saw blade.  Cut around the marked
circle staying approximately one quarter inch outside of the
line.  (This will allow the vent to easily slide through the
opening.  The resulting gap will be covered up by the Vent
Terminal cover plate.)  Repeat this step on inside wall if
necessary.

SEQUENCE OF INSTALLATIONS, FIGURE 4

Cut a length of 3" PVC pipe about 3.5 inches longer than the
wall thickness at the opening.  Glue the vent terminal  "TEE"
with screens to this section of pipe.  Slide the wall plate over the
pipe to stop against "TEE".  Place a bead of caulking (not
supplied) around the gap between the pipe and cover plate.
Apply enough to fill some of the gap between the pipe and wall.
Place some of the caulking on the back of the plate to hold it
against the wall after installation.  If the vent pipe is installed up
to the wall, with a coupling on the end against the wall opening,
the pipe with the vent terminal can be prepared for gluing before
inserting through the wall.  Slide the pipe through the wall and
insert into the coupling on the other side of the wall, making
sure that the vent terminal ends up pointed in the correct position.
(See fig. 5).

 

FIGURE 5

PREPARATION OF BLOWER ASSEMBLY

1. Check to make sure that the wire harness is attached to the

gas valve and blower control box..

2. Make sure no material is still attached to the outside or inside

of blower assembly.

       

FIGURE 6

Содержание FPSE-75

Страница 1: ...XT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE RESIDENTIAL GAS WATER HEATERS OWNER SMANUAL A DIVISION OF A O SMITH CORPORATION McBee South Carolina U S A www hotwater com GET TO KNOW YOUR WATER HEATER 2 GENERAL SAFETY INFORMATION 3 4 INSTALLATION 4 12 OPERATION 12 14 MAINTENANCE AND TROUBLESHOOTING 14 17 ...

Страница 2: ...he Yellow Pages for your A O Smith plumber or contact the A O Smith Water Products Company 5621 W 115th Street Alsip IL 60803 1 800 433 2545 When ordering parts provide complete model and serial numbers see rating plate quantity and name of part desired as listed in fig 1 Standard hardware items may be purchased locally FPSE 75 with Hot Surface Ignition SmartValve VACUUM RELIEF VALVE INSTALL PER L...

Страница 3: ...ind the cause yourself Go to a neighbor s house leaving your doors open to ventilate the house then call your gas supplier or service agent Keep area clear until a service call has been made At times you may not be able to smell an LP gas leak One cause is odor fade which is a loss of the chemical odorant that gives LP gas its distinctive smell Another cause can be your physical condition such as ...

Страница 4: ...g minimum clearances from combustible material of 2 clearance from sides and rear 6 from the front and 24 from the top Standard clearance If clearances stated on the heater differ from standard clearances install water heater according to clearances stated on heater A minimum clearance of 4 must be allowed for access to replaceable parts such as the thermostats drain valve and relief valve A top c...

Страница 5: ... higher than required for domestic water purposes a tempering valve must be installed Please refer to Fig 2 for suggested piping arrangement FIGURE2 CLOSED WATER SYSTEM A closed system will exist if a back flow preventer check valve pressure reducing valve or other similar device is installed in the cold water line between the water heater and the street main or well Excessive pressure may develop...

Страница 6: ...erating main burner Bubbles indicate gas leak To stop leak tighten pipe connections After piping connections are checked turn on main burner With main burner in operation paint pipe joints including flanges pilot gas tubing connections and control inlet and outlet with rich soap and water solution Bubbles indicate gas leak To stop leak tighten flange screws joints and pipe connections Replace part...

Страница 7: ...h information in this manual under LOCATION OF HEATER and VENT TERMINAL INSTALLATIONS and with the National Fuel Gas Code and local codes PLANNING THE VENT SYSTEM Plan the route of the vent system from the discharge of the blower to the planned location of the vent terminal 1 Layout the total vent system to use a minimum of vent pipe and elbows Take into consideration that an elbow will be necessa...

Страница 8: ... the Vent Terminal is being installed on the outside of a finished wall it may be easier to mark both the inside and outside wall Align the holes by drilling a hole through the center of the template from the inside through to the outside The template can now be positioned on the outside wall using the drilled hole as a centering point for the template 3 A MASONRY SIDE WALLS Chisel an opening appr...

Страница 9: ...e of control box as close to inside wall as possible C If flexible cord and strain relief are removed then opening in box must be covered D Remove plastic cap in top of control box and install suitable conduit fitting in enclosure E Splice field wiring into existing wiring using code authorized method wire nuts etc F Be certain that neutral and line connections are not reversed when making these c...

Страница 10: ...roof with only the vent terminal that is included with the unit see Figure 9 A proper flashing or BOOT should be used to seal the pipe where it exits the roof The total vent system should not exceed the thirty 30 equivalent feet of 3 inch pipe or sixty 60 equivalent feet of 4 inch pipe as listed in Table 1 NOTE The equivalent feet of pipe listed above are exclusive of the TEE termination with inst...

Страница 11: ...ELY FLAMMABLE AND MUST NOT BE STORED OR USED NEAR HEAT OR OPEN FLAME ALSO USE ONLY IN A WELL VENTILATED AREA 3 MAKINGTHEJOINT A Cutting Pipe must be squarely cut to allow for the proper interfacing of the pipe end and the fitting socket bottom This can be accomplished with a miter box saw or wheel type cutter Wheel type cutters are not generally recommended for larger diameters since they tend to ...

Страница 12: ... a tendency to slide back while the cement is still wet so hold the joint together for about 15 seconds STEPG G Cleanup and joint movement Remove all excess cement from around the pipe and fitting with a dry cotton rag This must be done while the cement is still soft The joint should not be disturbed immediately after the cementing procedure and sufficient time should be allowed for proper curing ...

Страница 13: ...ice which automatically lights the burner DO NOT TRY TO LIGHT THE BURNER BY HAND 5 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above on this label If you don t smell gas go to the next step 6 Set thermostat to desired setting 7 Turn on all electrical power to the appliance 8 If the appliance will not operate follow the instructions TO TURN...

Страница 14: ...er temperature settings to reduce scald hazards Valves for reducing the point of use temperature by mixing cold and hot water are available See figure 2 Also available are inexpensive devices that attach to faucets to limit hot water temperatures Contact a licensed plumber or the local plumbing authority SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUTOFF TURN OFF THE MAIN MANUAL GAS SHUTOF...

Страница 15: ...y will operate at their full input Repeat step C above POWER VENTER MAINTENANCE The FPSE 75 must be inspected quarterly Points of inspection are 1 MOTOR Motor must rotate freely Oil every three months of operation with 4 drops of SAE 20 oil see fig 12 2 WHEEL Wheel must be clean of soot ash or any other coating which inhibits either rotation or air flow Remove all foreign material from vent system...

Страница 16: ...LESHOOTING sections If service becomes necessary contact your dealer installer or an authorized service agent Do not attempt to repair the water heater yourself Any work performed by authorized personnel may void the warranty If you are having a problem with your A O Smith water heater and are not pleased with the service you received First please contact your dealer or the A O Smith authorized se...

Страница 17: ...switch Replace control harness Replace blower and motor Replace switch Check for low voltage less than 102 vac have service checked and repaired If voltage is above 102 vac make sure there is not more than 30 Equivalent feet of 3 inch pipe or 60 equivalent feet of 4 inch pipe installed or vent terminal blockage If at least 102 vac less than 30 equivalent feet of 3 inch pipe or 60 equivalent feet o...

Страница 18: ... connectors 3 System wiring harness in good condition and securely connected at both ends Not Applicable 1 Replace control 1 Airflow proving switch stuck closed 2 Airflow proving switch miswired or jumpered WARNING Line Voltage Hazard Can cause property damage severe injury or death Turn off appliance before coming in contact with pressure switch and or electrical connections 1 Airflow proving swi...

Страница 19: ...BLOWER WITHIGNITERCABLECONNECTED MEASURE VOLTAGE AT HSI ELEMENT OUTPUT SEE INSET B 120V NOMINAL CHECK DAMAGED OR BROKEN HSI ELEMENT WARNING Line Voltage Hazard Can cause property damage severe injury or death Only a trained experienced service technician should perform this trouble shooting Be certain to avoid contact with pressure switch and or electrical connections REPLACEHSI CHECK ISTHEAPPLIAN...

Страница 20: ...rrantor will furnish the ORIGINAL OWNER a replacement A O Smith water heater of equivalent size and current model or a replacement part for any component part which fails in normal use in accordance with the warranty terms and conditions specified below THE A O SMITH REPLACEMENT MODEL OR PART WILL BE WARRANTED FOR ONLY THE UNEXPIRED PORTION OF THE ORIGINAL WARRANTY The warranty period will be dete...

Отзывы: