The water within the water heater tank expands as it is heated and
increases the pressure of the water system.  If the relieving point of
the water heater’s temperature-pressure relief valve is reached, the
valve will relieve the excess pressure.  

The temperature-pressure

relief valve is not intended for the constant relief of thermal
expansion.

  This is an unacceptable condition and must be corrected.

It is recommended that any devices installed which could create a
closed system have a by-pass and/or the system have an expansion
tank or device to relieve the pressure built by thermal expansion in the
water system.  Expansion tanks are available for ordering through a
local plumbing contractor. 

 

Contact the local water supplier and/or a

service agency for assistance in controlling these situations.

NOTE:

 

To protect against untimely corrosion of hot and cold

water fittings, it is strongly recommended that di-electric
unions or couplings be installed on this water heater when
connected to copper pipe.

Figure 4 shows the typical attachment of the water piping to the water
heater. The water heater is equipped with 3/4 inch NPT water
connections.

NOTE:

 

 If using copper tubing, solder tubing to an adapter

before attaching the adapter to the cold water inlet connection.
Do not solder the cold water supply line directly to the cold
water inlet,  it will harm the dip tube and damage the tank.

FIGURE 4.

TEMPERATURE-PRESSURE RELIEF VALVE

This heater is provided with a properly certified combination
temperature - pressure relief valve by the manufacturer.

The valve is certified by a nationally recognized testing laboratory that
maintains periodic inspection of production of listed equipment of
materials as meeting the requirements for Relief Valves and Automatic
Gas Shut-off Devices for Hot Water Supply Systems, ANSI Z21.22 •
CSA 4.4, and the code requirements of ASME.

If replaced, the valve must meet the requirements of local codes, but
not less than a combination temperature and pressure relief valve
certified as indicated in the above paragraph.

The valve must be marked with a maximum set pressure not to exceed
the marked hydrostatic working pressure of the water heater
 (150 psi = 1,035 kPa) and a discharge capacity not less than the water
heater input rate as shown on the model rating plate.

For safe operation of the water heater, the relief valve must not be
removed from its designated opening nor plugged.

The temperature-pressure relief valve must be installed directly into
the fitting of the water heater designed for the relief valve.  Position the
valve downward and provide tubing so that any discharge will exit
only within 6 inches (153 mm) above, or at any distance below the
structural floor.  Be certain that no contact is made with any live electrical
part.  The discharge opening must not be blocked or reduced in size
under any circumstances.  Excessive length, over 30 feet (9.14 m), or
use of more than four elbows can cause restriction and reduce the
discharge capacity of the valve.

No valve or other obstruction is to be placed between the relief valve
and the tank.  Do not connect tubing directly to discharge drain unless
a 6 inch air gap is provided.  To prevent bodily injury, hazard to life, or
property damage, the relief valve must be allowed to discharge water
in quantities should circumstances demand.  If the discharge pipe is not
connected to a drain or other suitable means, the water flow may
cause property damage.

Содержание Commercial gas water heaters

Страница 1: ...TIONS SHOULDBEDIRECTEDTOTHELOCALDEALERFROMWHOMTHEWATERHEATERWAS PURCHASED IFYOUAREUNSUCCESSFUL PLEASEWRITETOTHECOMPANYLISTEDONTHERATINGPLATEONTHEWATERHEATER RESIDENTIAL ELECTRIC WATER HEATERS FOR POTA...

Страница 2: ...l Code and applicable local electrical and plumbing codes and tools necessary to confirm proper installation and operation of the water heater as they relate to the installation of electric water heat...

Страница 3: ...ef Valve 9 10 Filling the Water Heater 10 T P Valve and Pipe Insulation Selected Models 10 TEMPERATUREREGULATION 11 Temperature Adjustment 11 FORYOURINFORMATION 12 Thermal Expansion 12 Strange Sounds...

Страница 4: ...ation must conform with these instructions and the local code authority having jurisdiction and the requirements of the power company In the absence of code requirements follow NFPA 70 latest edition...

Страница 5: ...ELIEF IN COLD WATER INLET LINE AS REQUIRED BY LOCAL CODES INSTALL SUITABLE DRAIN PANS UNDER HEATERS TO PREVENT DAMAGE DUE TO LEAKAGE REFER TO WATER HEATER LOCATION ON PAGE 8 INSTALL THERMAL EXPANSION...

Страница 6: ...2 A 9 240 VOLT OFF PEAK NON SIMULTANEOUS OPERATIONBOTTOMELEMENTONSEPARATE TIMECLOCKOR OFFPEAK METER C 2 TWO WIRE CIRCUIT FOR SINGLE ELEMENTHEATERSEQUIPPED WITH HIGH LIMIT CONTROL A 6 TWO WIRE CIRCUIT...

Страница 7: ...ped If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap then you must take special...

Страница 8: ...Failure to follow these instructions can result in fire serious personal injury or death Do not cover the temperature and pressure relief T P valve with an insulation blanket Do not cover the instruc...

Страница 9: ...tory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Relief Valves andAutomatic Gas Shut off Devices for Hot Water Supply Systems ANSI...

Страница 10: ...ATER HEATER Never use this water heater unless it is completely full of water To prevent damage to the tank the tank must be filled with water Water must flow from the hot water faucet before turning...

Страница 11: ...isfy space heating clothes washing dish washing and other sanitizing needs can scald and permanently injure you upon contact Some people are more likely to be permanently injured by hot water than oth...

Страница 12: ...r heater models by replacing the anode s with one of less active material and then chlorinating the water heater tank and all hot water lines Contact the local water heater supplier or service agency...

Страница 13: ...eaking water heater Many suspected Leakers are not leaking tanks Often the source of the water can be found and corrected If you are not thoroughly familiar with your water heater and safety practices...

Страница 14: ...e condensation due to the panel or insulation not being in place F Water from a drain valve may be due to the valve being slightly opened G The drain valve may be leaking at the tank fitting H Water i...

Страница 15: ...Applicable 17 Drain Pan w Side Drain Instruction Manual Not Illustrated Now that you have purchased this water heater should a need ever exist for repair parts or service simply contact the company it...

Страница 16: ...nces near water heater Install thermal expansion tank DO NOT plug T P valve Check relief valve for proper operation DO NOT plug T P valve Drain and flush heater thoroughly then refill Chlorinate water...

Страница 17: ...tat used at water pressure not exceeding the working pressure shown on the heater filled with potable water free to circulate at all times and with the tank free of damaging water sediment or scale de...

Страница 18: ...5621 W 115th Street Alsip Illinois 60803 Phone 1 800 433 2545 or visit our website at www hotwater com parts The warrantor will only honor replacement with identical or similar water heater or parts...

Страница 19: ...___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________...

Страница 20: ...20 www aosmithwaterheaters com...

Отзывы: