THERMAL EXPANSION

Water supply systems may, because of such events as high line
pressure, frequent cut-offs, the effects of water hammer among
others, have installed devices such as pressure reducing valves, check
valves, back flow preventers, etc. to control these types of problems.
When these devices are not equipped with an internal by-pass, and no
other measures are taken, the devices cause the water system to be
closed.  As water is heated, it expands (thermal expansion) and closed
systems do not allow for the expansion of heated water.

The water within the water heater tank expands as it is heated and
increases the pressure of the water system.  If the relieving point of
the water heater’s temperature-pressure relief valve is reached, the
valve will relieve the excess pressure.  

The temperature-pressure

relief valve is not intended for the constant relief of thermal
expansion.

  This is an unacceptable condition and must be corrected.

It is recommended that any devices installed which could create a
closed system have a by-pass and/or the system have an expansion
tank or device to relieve the pressure built by thermal expansion in the
water 

system.  Expansion tanks are available for ordering through a

local plumbing contractor.  Contact the local water heater supplier or
service agency for assistance in controlling these situations.

STRANGE SOUNDS

Possible noises due to expansion and contraction of some metal parts
during periods of heat-up and cool-down do not necessarily represent
harmful or dangerous conditions.

OPERATIONAL CONDITIONS

SMELLY WATER

In each water heater there is installed at least one anode rod (see
parts sections) for corrosion protection of the tank.  Certain water
conditions will cause a reaction between this rod and the water.  The
most common complaint associated with the anode rod is one of a
“rotten egg smell” in the hot water.  This odor is derived from hydrogen
sulfide gas dissolved in the water.  The smell is the result of four
factors which must all be present for the odor to develop:

a. A concentration of sulfate in the supply water.
b. Little or no dissolved oxygen in the water.

c. A sulfate reducing bacteria which has accumulated within the water

heater (this harmless bacteria is nontoxic to humans).

d. An excess of active hydrogen in the tank.  This is caused by the

corrosion protective action of the anode.

Smelly water may be eliminated or reduced in some water heater
models by replacing the anode(s) with one of less active material, and
then chlorinating the water heater tank and all hot water lines.  Contact
the local water heater supplier or service agency for further information
concerning an Anode Replacement Kit and this chlorination treatment.
If the smelly water persists after the anode replacement and chlorination
treatment, we can only suggest that chlorination or aeration of the
water supply be considered to eliminate the water problem.

Do not remove the anode leaving the tank unprotected.  By
doing so, all warranty on the water heater tank is voided.

“AIR” IN HOT WATER FAUCETS

HYDROGEN GAS: Hydrogen gas can be produced in a hot water
system that has not been used for a long period of time (generally two
weeks or more).  Hydrogen gas is extremely flammable and explosive.
To prevent the possibility of injury under these conditions, we
recommend the hot water faucet, located farthest away, be opened
for several minutes before any electrical appliances which are
connected to the hot water system are used (such as a dishwasher or
washing machine).  If hydrogen gas is present, there will probably be
an unusual sound similar to air escaping through the pipe as the hot
water faucet is opened.  There must be no smoking or open flame near
the faucet at the time it is open.

HIGH WATER TEMPERATURE SHUT OFF SYSTEM

A non-adjustable high temperature limit control operates before steam
temperatures are reached.  The high limit is in the same area as the
upper thermostat and must be reset manually when it operates.
BECAUSE THE HIGH LIMIT OPERATES ONLY WHEN
ABNORMALLY HIGH WATER TEMPERATURES ARE PRESENT, IT
IS IMPORTANT THAT A QUALIFIED SERVICE AGENT BE CONTACTED
TO DETERMINE THE REASON FOR OPERATION BEFORE RESETTING.

ANODE ROD INSPECTION

The anode rod is used to protect the tank from corrosion.  Most hot
water tanks are equipped with an anode rod.  The submerged rod
sacrifices itself to protect the tank.  Instead of corroding the tank,
water ions attack and eat away the anode rod.  This does not affect
the water’s taste or color.  The rod must be maintained to keep the tank
in operating condition.

Anode deterioration depends on water conductivity, not necessarily
water condition. A corroded or pitted anode rod indicates high water
conductivity and should be checked and/or replaced more often then
an anode rod that appears to be intact. Replacement of a depleted

FOR Y

FOR Y

FOR Y

FOR Y

FOR YOUR INFORMA

OUR INFORMA

OUR INFORMA

OUR INFORMA

OUR INFORMATION

TION

TION

TION

TION

PERIODIC MAINTENANCE

PERIODIC MAINTENANCE

PERIODIC MAINTENANCE

PERIODIC MAINTENANCE

PERIODIC MAINTENANCE

Содержание Commercial gas water heaters

Страница 1: ...TIONS SHOULDBEDIRECTEDTOTHELOCALDEALERFROMWHOMTHEWATERHEATERWAS PURCHASED IFYOUAREUNSUCCESSFUL PLEASEWRITETOTHECOMPANYLISTEDONTHERATINGPLATEONTHEWATERHEATER RESIDENTIAL ELECTRIC WATER HEATERS FOR POTA...

Страница 2: ...l Code and applicable local electrical and plumbing codes and tools necessary to confirm proper installation and operation of the water heater as they relate to the installation of electric water heat...

Страница 3: ...ef Valve 9 10 Filling the Water Heater 10 T P Valve and Pipe Insulation Selected Models 10 TEMPERATUREREGULATION 11 Temperature Adjustment 11 FORYOURINFORMATION 12 Thermal Expansion 12 Strange Sounds...

Страница 4: ...ation must conform with these instructions and the local code authority having jurisdiction and the requirements of the power company In the absence of code requirements follow NFPA 70 latest edition...

Страница 5: ...ELIEF IN COLD WATER INLET LINE AS REQUIRED BY LOCAL CODES INSTALL SUITABLE DRAIN PANS UNDER HEATERS TO PREVENT DAMAGE DUE TO LEAKAGE REFER TO WATER HEATER LOCATION ON PAGE 8 INSTALL THERMAL EXPANSION...

Страница 6: ...2 A 9 240 VOLT OFF PEAK NON SIMULTANEOUS OPERATIONBOTTOMELEMENTONSEPARATE TIMECLOCKOR OFFPEAK METER C 2 TWO WIRE CIRCUIT FOR SINGLE ELEMENTHEATERSEQUIPPED WITH HIGH LIMIT CONTROL A 6 TWO WIRE CIRCUIT...

Страница 7: ...ped If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap then you must take special...

Страница 8: ...Failure to follow these instructions can result in fire serious personal injury or death Do not cover the temperature and pressure relief T P valve with an insulation blanket Do not cover the instruc...

Страница 9: ...tory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Relief Valves andAutomatic Gas Shut off Devices for Hot Water Supply Systems ANSI...

Страница 10: ...ATER HEATER Never use this water heater unless it is completely full of water To prevent damage to the tank the tank must be filled with water Water must flow from the hot water faucet before turning...

Страница 11: ...isfy space heating clothes washing dish washing and other sanitizing needs can scald and permanently injure you upon contact Some people are more likely to be permanently injured by hot water than oth...

Страница 12: ...r heater models by replacing the anode s with one of less active material and then chlorinating the water heater tank and all hot water lines Contact the local water heater supplier or service agency...

Страница 13: ...eaking water heater Many suspected Leakers are not leaking tanks Often the source of the water can be found and corrected If you are not thoroughly familiar with your water heater and safety practices...

Страница 14: ...e condensation due to the panel or insulation not being in place F Water from a drain valve may be due to the valve being slightly opened G The drain valve may be leaking at the tank fitting H Water i...

Страница 15: ...Applicable 17 Drain Pan w Side Drain Instruction Manual Not Illustrated Now that you have purchased this water heater should a need ever exist for repair parts or service simply contact the company it...

Страница 16: ...nces near water heater Install thermal expansion tank DO NOT plug T P valve Check relief valve for proper operation DO NOT plug T P valve Drain and flush heater thoroughly then refill Chlorinate water...

Страница 17: ...tat used at water pressure not exceeding the working pressure shown on the heater filled with potable water free to circulate at all times and with the tank free of damaging water sediment or scale de...

Страница 18: ...5621 W 115th Street Alsip Illinois 60803 Phone 1 800 433 2545 or visit our website at www hotwater com parts The warrantor will only honor replacement with identical or similar water heater or parts...

Страница 19: ...___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________...

Страница 20: ...20 www aosmithwaterheaters com...

Отзывы: