background image

35

6 Maintenance Instructions 

6.1 General 

1. The maintenance of the water heater includes cleaning the tank and cleaning up the scales 

on the heating elements, especially in the area with harder water. It is recommended that the 

tank to be cleaned every month. Check the scales on the inner surface of the tank and the 

surface of the elements to determine whether cleaning is necessary, and the cleaning of 

heating elements should be performed by local supplier. It is normal if there is a hissing 

during the cleaning. 

2. The temperature and pressure relief valve should be inspected every month to ensure it is 

in effective operation. Pull the handle of the relief valve several times to ensure the valve can 

switch freely. Please pull the handle of the relief valve once every month, and discharge 4~8L 

water, which can prevent scaling inside of the relief valve. 

3. The water heater is equipped with an anode to protect the enamel water tank from 

corrosion through electrolysis. When the material of the anode is consumed completely, the 

water tank would lose this protection. The anode should be checked once every year to 

determine the consumption of the material or change the new one. When the anode diameter 

is less than 1 cm, change it for a new one. Higher water temperature and softer water can 

accelerate the consumption of the anode, so the anode should be checked more frequently. 

Anode is a consumptive part and is charged for replacement as it is not covered by 

guarantee. 

4. The water heater is recommended to operate in the surrounding that is free from too much 

dust. 

6.2 Cleaning the Water Heater 

The drain valve of the water heater should be opened regularly to prevent precipitation 

on the bottom of the tank. 

1. Disconnect the power supply to the water heater. 

2. Connect a soft tube at the drain valve outlet and put the other end to a floor drain. Turn the 

handle of the drain valve to the left (anti-clockwise) to open the drain valve. Drain the water 

completely. If there is no water flowing out after opening the drain valve, perform according to 

the instruction of cleaning the precipitation. 

CAUTION: 

This water heater should be maintained by a qualified person. Failure to follow 

these instructions can result in severe injury or property loss. 

WARNING:

 Disconnect the power supply to the water heater before maintaining the water 

heater. 

CAUTION: 

When inspecting the T&P relief valve, the water outlet temperature of the valve 

might be high and it could cause severe scalds, so be careful. 

Содержание CAHP-120 Series

Страница 1: ...R...

Страница 2: ...fety Information 2 2 Physical and Technical Specifications 4 3 Installation Instructions 10 4 Electrical Connection Instructions 14 5 Operation Instructions 22 6 Maintenance Instructions 35 7 Trouble...

Страница 3: ...ter before bathing or showering z If the water heater is subjected to dry fire it will produce steam or hot water with high temperature which is in risk of causing severe scalds The water heater shoul...

Страница 4: ...turer or seller of the water heater will not be liable for any damage caused by unauthorized installation These damages include but not limited to leakage of coils dropping of the unit the abnormal op...

Страница 5: ...m Relief Valve Angle Maximum Width H mm 1670 610 901 503 1457 1427 135 22 686 Table 2 2 Technical Specifications Model Number CAHP 80 6 CAHP 80 8 CAHP 80 10 CAHP 80 12 Model Type Outdoor Integrated He...

Страница 6: ...50Hz L h 75 75 75 75 230V 1N 50Hz L h 75 75 75 75 Hot Water Delivering Rate High Demand 380V 3N 60Hz L h 218 153 5 261 175 304 196 5 347 218 220V 1N 60Hz L h 218 153 5 261 175 304 196 5 347 218 400V 3...

Страница 7: ...ical Dimensions Total Height A mm Tank Diameter B mm Maximum Depth C mm Service Panel Width D mm Relief Valve and Water Outlet Height E mm Drain Valve and Water Inlet Height G mm Relief Valve Angle Ma...

Страница 8: ...g 1000 60Hz g 1100 Electrical Heating Capacity kW 6 3 8 4 10 5 12 6 Tank Capacity L 455 Hot Water Delivering Rate Efficiency 380V 3N 60Hz L h 89 89 89 89 220V 1N 60Hz L h 89 89 89 89 400V 3N 50Hz L h...

Страница 9: ...eration mode 3 Sound Pressure Level 1m 2 3 CAHP 120C Physical and Technical Specifications Figure 2 5 Figure 2 6 Table 2 5 Physical Dimensions Total Height A mm Tank Diameter B mm Maximum Depth C mm S...

Страница 10: ...Noise 3 dB A 59 Air Outlet Noise 3 dB A 62 Dimensions L W H mm 1002 770 1770 Net Weight kg 264 Operation Weight kg 694 Anode Aluminum Rod Control Mode LCD Wire Display Standard 10m Optional Maximum 3...

Страница 11: ...ound would have no influence on you and your neighbors CAUTION Put the water heater aside for at least 30 minutes after the unit is located and then connect it to the power supply CAUTION The water he...

Страница 12: ...ON In order to reduce the operation cost the hot water outlet pipes should be properly insulated If the water heater is subjected to freezing temperature that is less than 0 the cold water inlet pipes...

Страница 13: ...mum water pressure listed on the nameplate Install a mixing valve to mix the hot water delivered by the water heater to avoid possible hurt caused by high water temperature It s recommended to insulat...

Страница 14: ...high water temperature water pump Grundfos Pumper UP15 14BT which has nominal water flow rate 0 3 cubic meters and lift 1m If other pump is used adjust the pump according to actual condition for prop...

Страница 15: ...nsure the touch would not result in electric shock touchable double insulation cable could be used or add insulation to normal power cord 4 2Power Cord Connection 1 Select power cord for CAHP80 120 un...

Страница 16: ...Cable Size mm 2 Plastic Insulation and Conduit Air Breaker Capacity A Current Leakage Protection Two Elements Working Mode One Element Working Mode Two Elements One Element Phase Wire Neutral Wire Gro...

Страница 17: ...2 3 Run the main power cord through the cable connector with reference to figure 4 3 Figure 4 1 Figure 4 2 Figure 4 5 Cable Connector of Circulating Pump Cable Connector of Display Box Power Cord Con...

Страница 18: ...ng Wire WARNING An air breaker and an appropriate current leakage protector must be installed outside the water heater as the requirement of power supply specification table for your security The wate...

Страница 19: ...Protect the display box during installation process and keep it away from dust Do not touch electrical parts Otherwise the display box would be damaged z The display box is connected in low voltage c...

Страница 20: ...13 Install the communication cable on the terminal block on the right of display board keep the label of wire corresponding to letters in terminal block as illustrated in figure 4 14 Keep the display...

Страница 21: ...cover on the wall 4 Communication Cable Installation of Water Heater Keep the main control board accessible as illustrated in figure 4 18 before connecting the communication cable to the water heater...

Страница 22: ...21 one connector in the main control board There are two connectors applicable for display board and select one for connection...

Страница 23: ...clockwise to shut off the drain valve of the water heater 3 Open the nearest hot water faucet and purge the air from the system 4 Open cold water inlet valve fully and fill the water tank and pipes w...

Страница 24: ...tton of OFF on the homepage to turn off the water heater The buttons will be locked automatically if there is no operation within three minutes When the water heater is connected to the power supply t...

Страница 25: ...conservation In high demand mode the water will be heated as quickly as possible The factory default mode is efficiency Press the button of or to select the operation mode Press the button of OK to c...

Страница 26: ...tting is the same as on time setting Figure 5 6 Press the button of or to select the sub menu of status below TIMER 1 on the sub menu interface of timer setting and press the button of MODIFY to chang...

Страница 27: ...gure 5 10 Press the button of SET to enter the timer setting interface illustrated in figure 5 11 There are two options in sub menu interface of timer start and stop Press the button of or to select t...

Страница 28: ...he button of SET to change pipe outside diameter value Press the button of or to select proper pipe outside diameter value and the button of OK to confirm the selection Other four sub menus could be o...

Страница 29: ...n must be performed by a qualified person authorized by the manufacturer or the supplier For CAHP80 120 units perform as the following instructions Press the button of or to select the sub menu of SER...

Страница 30: ...spect the software versions and check codes of main control board and display board illustrated in figure 5 24 Comparing with the released check codes can confirm if the software is disturbed or if it...

Страница 31: ...lustrated in figure 5 29 if necessary Press the button of EXIT to return to the last menu interface Figure 5 28 Figure 5 29 Press the button of or to select the sub menu of FIN TEST 1 on the maintenan...

Страница 32: ...e following instructions Press the button of or to select the sub menu of SERVICE on the main menu interface and then press the button of SET to enter the maintenance menu Press the button of or to se...

Страница 33: ...120C unit can record ten faults as illustrated in figure 5 38 and figure 5 39 Figure 5 37 Figure 5 38 Figure 5 39 Press the button of or to select the sub menu of SW VER on the maintenance menu as ill...

Страница 34: ...f or to select each number and the button of OK to confirm the number Figure 5 42 Figure 5 43 If the password is wrong it will show WRONG as illustrated in figure 5 44 Press the button of OK to input...

Страница 35: ...IN TEST 2 and SET FREQ are the same with CAHP80 120 units Press the button of or to select the sub menu of CLR FAULTS on the maintenance menu as illustrated in figure 5 47 Press the button of OK to cl...

Страница 36: ...the material or change the new one When the anode diameter is less than 1 cm change it for a new one Higher water temperature and softer water can accelerate the consumption of the anode so the anode...

Страница 37: ...emoved to inspect regularly If there is scale remove all the heating elements for cleaning If there is precipitation on the bottom of the tank clean it The method of cleaning the lime scale is immersi...

Страница 38: ...elements and determine the normal operation of the heating elements Install the covers of the heating elements and the service panels ADVICE When the hot water is too much it is recommended adjusting...

Страница 39: ...he water heater 1 When there is precipitation or lime scale on the surface of the heating elements a hissing sound would occur during the operation of the water heater The noise is normal but the scal...

Страница 40: ...service phone LOW PRESSURE Compressor is protected for low pressure If it cannot recover within one hour call the service phone HIGH DIS TEMP Compressor is protected for high discharge temperature If...

Страница 41: ...ERR Lower tank temperature AD channel is error Call the service phone COIL SHORT Coil temperature sensor is short Call the service phone COIL OPEN Coil temperature sensor is open Call the service phon...

Страница 42: ...41 8 APPENDIX 8 1 CAHP 80I 120I Wiring Diagram...

Страница 43: ...42 8 2 CAHP 80T 120T Wiring Diagram...

Страница 44: ...43 8 3 CAHP120C 3KW Wiring Diagram...

Страница 45: ...44 8 4 CAHP120C 4KW 5KW 6KW Wiring Diagram...

Страница 46: ...R...

Отзывы: