A.O. Smith BTR 120 Скачать руководство пользователя страница 2

2

BTR MODELS 120 THROUGH 400A - TABLE 1A

  MODEL

INPUT

APPROX.

GAS

H

VENT

       CONNECTIONS

            Approximate

RATE

TANK

INLET

DIA

INLET

OUTLET

             ship. Weight

BTU/Hr.

CAP.

A

B

C

D

E

F

G

I

J

TOP

FRONT

BACK

TOP

FRONT BACK

STD.

ASME

BTR120

120,000 BTU/Hr.

71 Gal

69.75"

4.25"

59.50"

50.87"

19.69"

19"

1/2"

51.88"

5"

27.75"

1.50"

1.50"

1.50"

1.50"

1.50"

1.50" 400 Lbs

NA

35 Kw/Hr

268 L

177 cm

11 cm

151 cm

129 cm

50 cm

48 cm

1/2"

132 cm

13 cm

71 cm

1.50"

1.50"

1.50"

1.50"

1.50"

1.50"

182 Kg

NA

BTR154

154,000 BTU/Hr

81 Gal

73.00"

4.25"

66.50"

57.87"

19.69"

19"

1/2"

59.00"

6"

27.75"

1.50"

1.50"

1.50"

1.50"

1.50"

1.50" 470 Lbs

NA

45 Kw/Hr

307 L

185 cm

11 cm

169 cm

147 cm

50 cm

48 cm

1/2"

150 cm

15 cm

71 cm

1.50"

1.50"

1.50"

1.50"

1.50"

1.50"

213 Kg

NA

BTR180

180,000 BTU/Hr

81Gal

67.50"

4.50"

62.00"

53.62"

20.50"

21"

1/2"

54.62"

6"

27.75"

1.50"

1.50"

1.50"

1.50"

1.50"

1.50" 470 Lbs

NA

53 Kw/Hr

307 L

171 cm

12 cm

157 cm

136 cm

52 cm

53 cm

1/2"

139 cm

15 cm

71 cm

1.50"

1.50"

1.50"

1.50"

1.50"

1.50"

213 Kg

NA

BTR197

199,000 BTR/Hr

100 Gal

75.00"

4.50"

70.00"

61.62"

20.50"

21"

1/2"

62.62"

6"

27.75"

1.50"

1.50"

1.50"

1.50"

1.50"

1.50" 603 Lbs

NA

58 kW/Hr

379 L

192 cm

12 cm

178 cm

157 cm

52 cm

53 cm

1/2"

159 cm

15 cm

71 cm

1.50"

1.50"

1.50"

1.50"

1.50"

1.50"

273 Kg

NA

BTR198

199,000 BTU/Hr.

100 Gal

75.00"

4.50"

70.00"

61.62"

20.50"

21"

1/2"

61.50"

6"

27.75"

1.50"

1.50"

2.00"

1.50"

1.50"

2.00" 603 Lbs

NA

58 Kw/Hr

379 L

192 cm

12 cm

178 cm

157 cm

52 cm

53 cm

1/2"

150 cm

15 cm

71 cm

1.50"

1.50"

2.00"

1.50"

1.50"

2.00"

273 Kg

NA

BTR199

199,000 BTU/Hr

81 Gal

67.50"

4.50"

62.00"

53.62"

20.50"

21"

1/2"

54.62"

6"

27.75"

1.50"

1.50"

1.50"

1.50"

1.50"

1.50" 470 Lbs

NA

58 kW/Hr

307 L

171 cm

12 cm

157 cm

136 cm

52 cm

53 cm

1/2"

139 cm

15 cm

71 cm

1.50"

1.50"

1.50"

1.50"

1.50"

1.50"

213 Kg

NA

BTR 200

199,000 BTR/Hr

100 Gal

72.00"

4.50"

65.13"

55.87"

19.75"

23"

1/2"

56.38"

6"

30.25"

1.50"

2.00"

2.00"

1.50"

2.00"

2.00" 630 Lbs

725 Lbs

58 kW/Hr

379 L

183 cm

12 cm

165 cm

142 cm

50 cm

58 cm

1/2"

143 cm

15 cm

77 cm

1.50"

2.00"

2.00"

1.50"

2.00"

2.00"

286 Kg

329 Kg

BTR 250

250,000 BTR/Hr

100 Gal

72.00"

4.50"

65.13"

55.87"

19.75"

23"

1/2"

56.38"

8"

30.25"

1.50"

2.00"

2.00"

1.50"

2.00"

2.00" 630 Lbs

725 Lbs

72 kW/Hr

379 L

183 cm

12 cm

165 cm

142 cm

50 cm

58 cm

1/2"

143 cm

20 cm

77 cm

1.50"

2.00"

2.00"

1.50"

2.00"

2.00"

286 Kg

329 Kg

BTR 251

251,000 BTR/Hr

65 Gal

75.00"

4.50"

65.75"

57.25"

20.00"

NA

1/2"

58.75

8"

27.75"

NA

1.50"

1.50"

NA

1.50"

1.50" 750Lbs

862 Lbs

73 kW/Hr

246 L

191 cm

12 cm

167 cm

145 cm

51 cm

NA

1/2"

149 cm

20 cm

70 cm

NA

1.50"

1.50"

NA

1.50"

1.50"

341 Kg

391 Kg

BTR 275

275,000 BTR/Hr

100 Gal

72.00"

4.50"

65.13"

55.87"

19.75"

23"

1/2"

56.38"

8"

30.25"

1.50"

2.00"

2.00"

1.50"

2.00"

2.00" 630 Lbs

725 Lbs

80 kW/Hr

379 L

183 cm

12 cm

165 cm

142 cm

50 cm

58 cm

1/2"

143 cm

20 cm

77 cm

1.50"

2.00"

2.00"

1.50"

2.00"

2.00"

286 Kg

329 Kg

BTR 305

305,000 BTR/Hr

65 Gal

75.00"

4.50"

65.75"

57.25"

20.00"

NA

1/2"

58.75

8"

27.75"

NA

1.50"

1.50"

NA

1.50"

1.50" 750 Lbs

862 Lbs

89 kW/Hr

246 L

191 cm

12 cm

167 cm

145 cm

51 cm

NA

1/2"

149 cm

20 cm

70 cm

NA

1.50"

1.50"

NA

1.50"

1.50"

341 Kg

391 Kg

BTR 365

365,000 BTR/Hr

85 Gal

79.50"

4.50"

70.25"

62.50"

22.50"

23”

3/4"

63.00

8"

27.75"

1.50"

1.50"

1.50"

1.50"

1.50"

1.50" 725 Lbs

833 Lbs

107 kW/Hr

322 L

202 cm

12 cm

178 cm

159 cm

57 cm

58 cm

3/4"

160 cm

20 cm

70 cm

1.50"

1.50"

1.50"

1.50"

1.50"

1.50"

329 Kg

379 Kg

BTR 400

390,000 BTU/Hr

100 Gal

75.50"

4.50"

67.50"

58.25"

26.75"

23"

3/4"

59.00"

8"

30.25"

1.50"

2.00"

2.00"

1.50"

2.00"

2.00" 760 Lbs

874 Lbs

114 kW/Hr

379 L

192 cm

12 cm

171 cm

148 cm

68 cm

58 cm

3/4"

150 cm

20 cm

77 cm

1.50"

2.00"

2.00"

1.50"

2.00"

2.00"

345 Kg

396 Kg

BTRC MODELS 120 THROUGH 400/A - TABLE 1B

  MODEL

INPUT

APPROX.

GAS

H

VENT

       CONNECTIONS

            Approximate

RATE

TANK

INLET

DIA

INLET

OUTLET

             ship. Weight

BTU/Hr.

CAP.

A

B

C

D

E

F

G

I

J

TOP

FRONT

BACK

TOP

FRONT BACK

STD.

ASME

BTRC120 120,000 BTU/Hr.

71 Gal

69.75"

4.25"

59.50"

50.87"

19.69"

19"

1/2"

51.88"

5"

27.75"

1.50"

1.50"

1.50"

1.50"

1.50"

1.50" 400 LBS

NA

35 Kw/Hr

268 L

177 cm

11 cm

151 cm

129 cm

50 cm

48 cm

1/2"

132 cm

13 cm

71 cm

1.50"

1.50"

1.50"

1.50"

1.50"

1.50"

182 Kg

NA

BTRC154

154,000 BTU/Hr

81 Gal

73.00"

4.25"

66.50"

57.87"

19.69"

19"

1/2"

59.00"

6"

27.75"

1.50"

1.50"

1.50"

1.50"

1.50"

1.50" 470 LBS

NA

45 Kw/Hr

307 L

185 cm

11 cm

169 cm

147 cm

50 cm

48 cm

1/2"

150 cm

15 cm

71 cm

1.50"

1.50"

1.50"

1.50"

1.50"

1.50"

213 Kg

NA

BTRC180

180,000 BTU/Hr

76 Gal

70.50"

4.25"

63.75"

55.13"

17.75"

19"

1/2"

56.50"

6"

27.75"

1.50"

1.50"

1.50"

1.50"

1.50"

1.50" 470 LBS

NA

53 Kw/Hr

288 L

179 cm

11 cm

162 cm

140 cm

45 cm

48 cm

1/2"

144 cm

15 cm

71 cm

1.50"

1.50"

1.50"

1.50"

1.50"

1.50"

213 Kg

NA

BTRC197

199,000 BTR/Hr

95 Gal

81.50"

4.25"

74.75"

66.13"

17.75"

19"

1/2"

67.50"

6"

27.75"

1.50"

1.50"

1.50"

1.50"

1.50"

1.50" 603 LBS

NA

58 kW/Hr

360 L

207 cm

11 cm

190 cm

168 cm

45 cm

48 cm

1/2"

171 cm

15 cm

71 cm

1.50"

1.50"

1.50"

1.50"

1.50"

1.50"

273 Kg

NA

BTRC199

199,000 BTU/Hr

76 Gal

70.50"

4.25"

63.75"

55.13"

17.75"

19"

1/2"

56.50"

6"

27.75"

1.50"

1.50"

1.50"

1.50"

1.50"

1.50" 470 LBS

NA

58 kW/Hr

288 L

179 cm

11 cm

162 cm

140 cm

45 cm

48 cm

1/2"

144 cm

15 cm

71 cm

1.50"

1.50"

1.50"

1.50"

1.50"

1.50"

213 Kg

NA

BTRC200

199,000 BTR/Hr

100 Gal

72.00"

4.50"

65.13"

55.87"

19.75"

23"

1/2"

56.38"

6"

30.25"

1.50"

2.00"

2.00"

1.50"

2.00"

2.00" 630 lbs

725 lbs

58 kW/Hr

379 L

183 cm

12 cm

165 cm

142 cm

50 cm

58 cm

1/2"

143 cm

15 cm

77 cm

1.50"

2.00"

2.00"

1.50"

2.00"

2.00"

286 Kg

329 Kg

BTRC250

250000 BTR/Hr

100 Gal

72.00"

4.50"

65.13"

55.87"

19.75"

23"

1/2"

56.38"

8"

30.25"

1.50"

2.00"

2.00"

1.50"

2.00"

2.00" 630 lbs

725 lbs

72 kW/Hr

379 L

183 cm

12 cm

165 cm

142 cm

50 cm

58 cm

1/2"

143 cm

20 cm

77 cm

1.50"

2.00"

2.00"

1.50"

2.00"

2.00"

286 Kg

329 Kg

BTRC251

251000 BTR/Hr

65 Gal

75.00"

4.50"

65.75"

57.25"

20.00"

NA

1/2"

58.8

8"

27.75"

NA

1.50"

1.50"

NA

1.50"

1.50" 750 lbs

862 lbs

73 kW/Hr

246 L

191 cm

12 cm

167 cm

145 cm

51 cm

NA

1/2"

149 cm

20 cm

70 cm

NA

1.50"

1.50"

NA

1.50"

1.50"

341 Kg

391 Kg

BTRC275

275,000 BTR/Hr

100 Gal

72.00"

4.50"

65.13"

55.87"

19.75"

23"

1/2"

56.38"

8"

30.25"

1.50"

2.00"

2.00"

1.50"

2.00"

2.00" 630 lbs

725 lbs

80 kW/Hr

379 L

183 cm

12 cm

165 cm

142 cm

50 cm

58 cm

1/2"

143 cm

20 cm

77 cm

1.50"

2.00"

2.00"

1.50"

2.00"

2.00"

286 Kg

329 Kg

BTRC305

305,000 BTR/Hr

65 Gal

75.00"

4.50"

65.75"

57.25"

20.00"

NA

1/2"

58.8

8"

27.75"

NA

1.50"

1.50"

NA

1.50"

1.50" 750 lbs

862 lbs

89 kW/Hr

246 L

191 cm

12 cm

167 cm

145 cm

51 cm

NA

1/2"

149 cm

20 cm

70 cm

NA

1.50"

1.50"

NA

1.50"

1.50"

341 Kg

391 Kg

BTRC365

365,000 BTR/Hr

65 Gal

75.00"

4.50"

65.75"

57.25"

20.00"

NA

3/4"

58.8

8"

27.75"

NA

1.50"

1.50"

NA

1.50"

1.50" 750 lbs

862 lbs

107 kW/Hr

246 L

191 cm

12 cm

167 cm

145 cm

51 cm

NA

3/4"

149 cm

20 cm

70 cm

NA

1.50"

1.50"

NA

1.50"

1.50"

341 Kg

391 Kg

BTRC400

390,000 BTU/Hr

100 Gal

75.50"

4.50"

67.50"

58.25"

26.75"

23"

3/4"

59.00"

8"

30.25"

1.50"

2.00"

2.00"

1.50"

2.00"

2.00" 760 lbs

874 lbs

114 kW/Hr

379 L

192 cm

12 cm

171 cm

148 cm

68 cm

58 cm

3/4"

150 cm

20 cm

77 cm

1.50"

2.00"

2.00"

1.50"

2.00"

2.00"

345 Kg

396 Kg

ROUGH-IN-DIMENSIONS

See Models Below

FIGURE 1

MODELS BTR(C) 120 THROUGH 500

Содержание BTR 120

Страница 1: ...nnessee Waltz Parkway Ashland City TN 37015 Phone 800 527 1953 Fax 800 433 2515 www hotwater com CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROU...

Страница 2: ...3 4 59 00 8 30 25 1 50 2 00 2 00 1 50 2 00 2 00 760 Lbs 874 Lbs 114 kW Hr 379 L 192 cm 12 cm 171 cm 148 cm 68 cm 58 cm 3 4 150 cm 20 cm 77 cm 1 50 2 00 2 00 1 50 2 00 2 00 345 Kg 396 Kg BTRC MODELS 1...

Страница 3: ...1031 957 BTR 390 000 BTUH 100 Gal 80 1293 970 776 646 554 485 431 388 353 323 298 277 400 114 Kw Hr 379 L 4894 3671 2936 2447 2097 1835 1631 1468 1335 1224 1129 1049 TABLE 1D HEATER PERFORMANCE DATA B...

Страница 4: ...ooting Guide 33 Operational Checklist 34 Limited Warranty 35 Page Page FOREWORD These designs comply with ANSI Z21 10 3 CSA 4 3 as an automatic circulating or automatic storage tank type water heater...

Страница 5: ...explosive and heavier than air It collects first in the low areas making its odor difficult to detect at nose level If LP gas is present or even suspected do not attempt to find the cause yourself Go...

Страница 6: ...or operation at altitudes other than that specified on the heater rating plate is not permitted The input reduction is primarily achieved by reducing the size of the main burner orifices To do this th...

Страница 7: ...AUTOMATIC OPERATION and HOLD OPEN DAMPER For normal operation the switch should be in the AUTOMATIC OPERATION position If there is a problem with the damper the Service Switch can be placed in the HOL...

Страница 8: ...g must be a continuous run no joints and retain the 6 16cm clearance unless an approved reducing thimble is used The National Sanitation Foundation also recommends circulation of 180 F 82 C water Wher...

Страница 9: ...NAIR CONTAMINATIONTHATMAYBE HAZARDOUS TOLIFE SUCHACONDITIONOFTENWILLRESULTINAYELLOW LUMINOUSBURNERFLAME CAUSINGCARBONINGORSOOTING OF THE COMBUSTION CHAMBER BURNERS AND FLUE TUBES AND CREATESARISK OFAS...

Страница 10: ...S OF FIRE AND ASPHYXIATION Heater must be protected from freezing downdrafts Remove all soot or other obstructions from the chimney that will retard a free draft Type B venting is recommended with the...

Страница 11: ...BTR C 180 197 198 199 200 Input 180 000 190 000 199 000 Btuh Total Vent Height Feet Draft Hood 6 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter in inches 180 000 1 Ft 8 8 8 8 8 7 7 7...

Страница 12: ...10 10 10 8 8 8 Number of Combined Input Heaters in Thousands of Btuh Manifold Common Vent Diameter 2 610 14 14 12 12 12 10 10 10 3 915 16 16 16 14 14 12 12 12 4 1220 18 18 16 16 16 14 14 12 MODEL BTR...

Страница 13: ...used in conjunction with this appliance shall also be installed with a properly sized rated and approved combination temperature ANSI and pressure ASME relief valve s WARNING THE PURPOSE OF RELIEF VA...

Страница 14: ...AND CERTIFIED FOR GAS SERVICE BEFOREATTACHING THE GAS LINE BE SURE THATALL GAS PIPE IS CLEAN ON THE INSIDE TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE A DIRT LEG SOMETIMES CALLED SEDIM...

Страница 15: ...SUPPLY PRESSURE TESTING EXCEEDING 1 2 PSIG 3 5 kPa GAS SUPPLY LINE MUSTBE CAPPED WHEN DISCONNECTED FROM THE HEATER FOR TEST PRESSURES OF 1 2 PSIG 3 5 kPa OR LESS THE APPLIANCE NEED NOT BE DISCONNECTED...

Страница 16: ...ULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROLWARNING ON PAGE 27 IF HIGHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAINADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Страница 17: ...MUST BE CLOSED ON DURING THERINSEOPERATIONANDOPEN OFF WHENDISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACH...

Страница 18: ...wn in the installation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of the tem...

Страница 19: ...OTE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE...

Страница 20: ...ERS WITH MIXING VALVE TWO PRE HEATERS WITH BOOSTER HEATER DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 27 IF HIGHER PREHE...

Страница 21: ...STER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN WHEN USING AN A O SMITH T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 OPENING FOR TANK TEMPERAT...

Страница 22: ...OD A BTR MODELS BTRC MODELS 120 69 75 177cm 69 75 177cm 154 73 00 185cm 73 00 185cm 180 67 50 171cm 70 50 179cm 197 75 00 192cm 81 50 207cm 198 75 00 192cm N A 199 67 50 171cm 70 50 179cm 200 72 00 18...

Страница 23: ...ete instructions MULTIPLE UNIT INSTALLATIONS For multiple unit installations contact A O Smith Water Products Company Technical Support Center at 1 800 527 1953 In Canada contact A O Smith Enterprises...

Страница 24: ...AVOID RISK OF FIRE OR EXPLOSION PURGE DISCHARGE MUST NOT ENTER CONFINEDAREAS OR SPACES WHERE IGNITION CAN OCCUR THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION MUSTBE INACTIVATED OR REMOV...

Страница 25: ...25 FOR NATURAL GAS MODELS...

Страница 26: ...26 FOR PROPANE GAS MODELS...

Страница 27: ...e water temperature is controlled by a thermostat Fig 3 which has two sensing elements One sensor is located near the top of the tank and the other is near the center The thermostat is set in the lowe...

Страница 28: ...MAINTENANCE CHECK THE PILOT At least once a year check the pilot burner fig 15 and the main burner fig 16 for proper operation Refer to the following pilot and main burner sections PILOT BURNER For a...

Страница 29: ...pressure gauge or a manometer to the gauge port and refer to Table 5 for correct manifold pressure 2 Use this formula to clock the meter Be sure that other gas consuming appliances are not operating...

Страница 30: ...he heater and replacement of the factory installed magnesium anodes with aluminum anodes may correct the condition Occasionally water softener companies recommend removal of heater anodes for odor rea...

Страница 31: ...screws securing tank cleanout plate and remove plate 4 Remove lime scale or sediment using care not to damage the glass lining 5 Inspect cleanout plate gasket if new gasket is required replace with A...

Страница 32: ...e replaced TROUBLESHOOTING IGNITION MODULE SYSTEM Before calling your service agent the following checklist should be examined to eliminate obvious problems from those requiring replacement or servici...

Страница 33: ...Blown fuse or circuit breaker 5 Disconnect switch off 6 Harness not plugged into appliance receptacle A FLUE DAMPER OPEN OR OPENING Unit is calling for heat and damper disc should be in vertical posi...

Страница 34: ...slower Call serviceman Check gas input If incorrect adjust gas pressure or replace main burner orifice Draft hood not installed or Call serviceman Install draft hood or baffles as one or more flue ba...

Страница 35: ...e heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warrantor will provide only a...

Страница 36: ...36 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 527 1953 Fax 800 433 2515 www hotwater com...

Отзывы: