INSTALLATION DIAGRAMS-TOP INLET/OUTLET USAGE

GENERAL

The type, size and location of the relief valves must be in
accordance with local codes.  The locations of the relief valves
shown in the installation diagrams are typical.  The heater has a
factory installed high temperature limit switch and temperature
and pressure relief valve.

Cold water lines to heater should be installed as shown in order
to minimize gravity circulation of hot water to building cold water
lines.

A listed temperature and pressure relief valve of adequate capacity
is installed on the heater.  The locations shown in the installation
diagrams on the following pages are typical.

The discharge opening of the temperature and pressure relief
valve,  located in front of the heater must be piped to an open
drain and should not be subject to freezing temperatures.

Install in accordance with all local codes.

Use of the top inlet water connection requires installation of an
inlet dip tube (refer to figure 11).   The tube is supplied in the
heater. Follow caution labels if  applying heat to this fitting. Do
not allow pipe dope to contact the plastic tube during installation.

CODE RESTRICTIONS

Use of the top inlet water connection is not permitted on

installations in the state of North Carolina, due to the material of
the tube (Polypropylene).  Where such code restrictions exist,
use only lower inlet tank connection.  This may also require a
heat trap - check local codes. The “Top Outlet” connection may
still be used on these applications.  Plug or cap all unused
openings in the tank before filling with water.

 DANGER

TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE
TEMPERATURE AT FIXTURES.  SEE WATER TEMPERATURE
CONTROL WARNING ON PAGE 27.  IF HIGHER PREHEAT
TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE
BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT
WATER SUPPLIED TO FIXTURES.

TUBE INLET INSTALLATION

FIGURE 13

BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR
GAS LEAKAGE. 

 Use soap and water solution or other material

acceptable for the purpose in locating the leaks.  

DO NOT USE

MATCHES, CANDLES, FLAME OR OTHER SOURCES OF
IGNITION FOR THIS PURPOSE.

DISCONNECT THE HEATER AND ITS MANUAL GAS SHUT-OFF
VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY
SUPPLY PRESSURE TESTING EXCEEDING 1/2 PSIG (3.5 kPa).
GAS SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED
FROM THE HEATER FOR TEST PRESSURES OF 1/2 PSIG
(3.5 kPa) OR LESS. THE APPLIANCE NEED NOT BE
DISCONNECTED, BUT MUST BE ISOLATED FROM THE
SUPPLY PRESSURE TEST BY CLOSING THE MANUAL GAS
Shut-off VALVE.

GAS METER SIZE — NATURAL GASES ONLY

Be sure the gas meter has sufficient capacity to supply the full
rated gas input of the water heater as well as the requirements of
all other gas fired equipment supplied by the meter.  If gas meter
is too small, ask the gas company to install a larger meter having
adequate capacity.

GAS PRESSURE REGULATOR

The gas pressure regulator is built into the gas valve and is
equipped to operate on the gas specified on model and rating
plate.  The regulator is factory adjusted to deliver gas to burner at
correct water column pressure allowing for a nominal pressure
drop through the controls.

The minimum gas supply pressure for input adjustment must not
be less than 4.5" w.c. (1.12 kPa) for natural gas and 11.0" w.c.
(2.74 kPa) for propane gas.

Do not subject the combination gas valve to inlet gas
pressures of more than 14.0" W.C. (3.48 kPa) - natural gas,
14.0" W.C. (3.48 kPa)- propane gas.  A service regulator is
necessary if higher gas pressures are encountered.

Gas pressure specified in Table 5, refer to flow pressure taken at
pressure tap of automatic gas valve while heater is operating.

GROUNDING INSTRUCTIONS

This water heater must be connected to a grounded metal,
permanent wiring system; or an equipment grounding
conductor must be run with the circuit conductors and
connected to the equipment grounding terminal or lead on the
water heater.

HEATER WIRING

All electrical work must be installed in accordance with the current
edition of the National Electrical Code NFPA 70, for Canada use
Canadian Electric Code CSA C22.1 and must conform to all local
code authority having jurisdiction. 

 AN ELECTRICAL GROUND

IS REQUIRED TO REDUCE RISK OF ELECTRICAL SHOCK OR
POSSIBLE ELECTROCUTION.

For Canadian installations the electrical connections and
grounding shall be done in accordance with current Canadian
Electrical Code CSA C22.1, Part 1 and/or local codes.

If any of the original wire as supplied with the appliance must be
replaced, use only type 105°C thermoplastic or equivalent.  250°C
type F must be used for the flame sensor leads and the spark
ignition cable must be high voltage 250°C.

Содержание BTR 120

Страница 1: ...nnessee Waltz Parkway Ashland City TN 37015 Phone 800 527 1953 Fax 800 433 2515 www hotwater com CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROU...

Страница 2: ...3 4 59 00 8 30 25 1 50 2 00 2 00 1 50 2 00 2 00 760 Lbs 874 Lbs 114 kW Hr 379 L 192 cm 12 cm 171 cm 148 cm 68 cm 58 cm 3 4 150 cm 20 cm 77 cm 1 50 2 00 2 00 1 50 2 00 2 00 345 Kg 396 Kg BTRC MODELS 1...

Страница 3: ...1031 957 BTR 390 000 BTUH 100 Gal 80 1293 970 776 646 554 485 431 388 353 323 298 277 400 114 Kw Hr 379 L 4894 3671 2936 2447 2097 1835 1631 1468 1335 1224 1129 1049 TABLE 1D HEATER PERFORMANCE DATA B...

Страница 4: ...ooting Guide 33 Operational Checklist 34 Limited Warranty 35 Page Page FOREWORD These designs comply with ANSI Z21 10 3 CSA 4 3 as an automatic circulating or automatic storage tank type water heater...

Страница 5: ...explosive and heavier than air It collects first in the low areas making its odor difficult to detect at nose level If LP gas is present or even suspected do not attempt to find the cause yourself Go...

Страница 6: ...or operation at altitudes other than that specified on the heater rating plate is not permitted The input reduction is primarily achieved by reducing the size of the main burner orifices To do this th...

Страница 7: ...AUTOMATIC OPERATION and HOLD OPEN DAMPER For normal operation the switch should be in the AUTOMATIC OPERATION position If there is a problem with the damper the Service Switch can be placed in the HOL...

Страница 8: ...g must be a continuous run no joints and retain the 6 16cm clearance unless an approved reducing thimble is used The National Sanitation Foundation also recommends circulation of 180 F 82 C water Wher...

Страница 9: ...NAIR CONTAMINATIONTHATMAYBE HAZARDOUS TOLIFE SUCHACONDITIONOFTENWILLRESULTINAYELLOW LUMINOUSBURNERFLAME CAUSINGCARBONINGORSOOTING OF THE COMBUSTION CHAMBER BURNERS AND FLUE TUBES AND CREATESARISK OFAS...

Страница 10: ...S OF FIRE AND ASPHYXIATION Heater must be protected from freezing downdrafts Remove all soot or other obstructions from the chimney that will retard a free draft Type B venting is recommended with the...

Страница 11: ...BTR C 180 197 198 199 200 Input 180 000 190 000 199 000 Btuh Total Vent Height Feet Draft Hood 6 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter in inches 180 000 1 Ft 8 8 8 8 8 7 7 7...

Страница 12: ...10 10 10 8 8 8 Number of Combined Input Heaters in Thousands of Btuh Manifold Common Vent Diameter 2 610 14 14 12 12 12 10 10 10 3 915 16 16 16 14 14 12 12 12 4 1220 18 18 16 16 16 14 14 12 MODEL BTR...

Страница 13: ...used in conjunction with this appliance shall also be installed with a properly sized rated and approved combination temperature ANSI and pressure ASME relief valve s WARNING THE PURPOSE OF RELIEF VA...

Страница 14: ...AND CERTIFIED FOR GAS SERVICE BEFOREATTACHING THE GAS LINE BE SURE THATALL GAS PIPE IS CLEAN ON THE INSIDE TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE A DIRT LEG SOMETIMES CALLED SEDIM...

Страница 15: ...SUPPLY PRESSURE TESTING EXCEEDING 1 2 PSIG 3 5 kPa GAS SUPPLY LINE MUSTBE CAPPED WHEN DISCONNECTED FROM THE HEATER FOR TEST PRESSURES OF 1 2 PSIG 3 5 kPa OR LESS THE APPLIANCE NEED NOT BE DISCONNECTED...

Страница 16: ...ULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROLWARNING ON PAGE 27 IF HIGHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAINADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Страница 17: ...MUST BE CLOSED ON DURING THERINSEOPERATIONANDOPEN OFF WHENDISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACH...

Страница 18: ...wn in the installation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of the tem...

Страница 19: ...OTE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE...

Страница 20: ...ERS WITH MIXING VALVE TWO PRE HEATERS WITH BOOSTER HEATER DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 27 IF HIGHER PREHE...

Страница 21: ...STER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN WHEN USING AN A O SMITH T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 OPENING FOR TANK TEMPERAT...

Страница 22: ...OD A BTR MODELS BTRC MODELS 120 69 75 177cm 69 75 177cm 154 73 00 185cm 73 00 185cm 180 67 50 171cm 70 50 179cm 197 75 00 192cm 81 50 207cm 198 75 00 192cm N A 199 67 50 171cm 70 50 179cm 200 72 00 18...

Страница 23: ...ete instructions MULTIPLE UNIT INSTALLATIONS For multiple unit installations contact A O Smith Water Products Company Technical Support Center at 1 800 527 1953 In Canada contact A O Smith Enterprises...

Страница 24: ...AVOID RISK OF FIRE OR EXPLOSION PURGE DISCHARGE MUST NOT ENTER CONFINEDAREAS OR SPACES WHERE IGNITION CAN OCCUR THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION MUSTBE INACTIVATED OR REMOV...

Страница 25: ...25 FOR NATURAL GAS MODELS...

Страница 26: ...26 FOR PROPANE GAS MODELS...

Страница 27: ...e water temperature is controlled by a thermostat Fig 3 which has two sensing elements One sensor is located near the top of the tank and the other is near the center The thermostat is set in the lowe...

Страница 28: ...MAINTENANCE CHECK THE PILOT At least once a year check the pilot burner fig 15 and the main burner fig 16 for proper operation Refer to the following pilot and main burner sections PILOT BURNER For a...

Страница 29: ...pressure gauge or a manometer to the gauge port and refer to Table 5 for correct manifold pressure 2 Use this formula to clock the meter Be sure that other gas consuming appliances are not operating...

Страница 30: ...he heater and replacement of the factory installed magnesium anodes with aluminum anodes may correct the condition Occasionally water softener companies recommend removal of heater anodes for odor rea...

Страница 31: ...screws securing tank cleanout plate and remove plate 4 Remove lime scale or sediment using care not to damage the glass lining 5 Inspect cleanout plate gasket if new gasket is required replace with A...

Страница 32: ...e replaced TROUBLESHOOTING IGNITION MODULE SYSTEM Before calling your service agent the following checklist should be examined to eliminate obvious problems from those requiring replacement or servici...

Страница 33: ...Blown fuse or circuit breaker 5 Disconnect switch off 6 Harness not plugged into appliance receptacle A FLUE DAMPER OPEN OR OPENING Unit is calling for heat and damper disc should be in vertical posi...

Страница 34: ...slower Call serviceman Check gas input If incorrect adjust gas pressure or replace main burner orifice Draft hood not installed or Call serviceman Install draft hood or baffles as one or more flue ba...

Страница 35: ...e heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warrantor will provide only a...

Страница 36: ...36 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 527 1953 Fax 800 433 2515 www hotwater com...

Отзывы: