8

Servicing should only be performed by a Qualified Service Technician

To trap any dirt or foreign material in the gas supply line, a sediment trap must be incorporated in the piping 

(see Figure below). The sediment trap must be readily accessible and not subject to freezing conditions. 

Install  in  accordance  with  recommendations  of  serving  gas  suppliers.  Refer  to  the  latest  version  of  the 

National Fuel Gas Code.
To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to 

gas valve inlet. Apply joint compounds (pipe dope) sparingly and only to the male threads of pipe joints. Do 

not apply compounds to the first two threads. Use compounds resistant to the action of liquefied petroleum 

gases.
Be sure the gas meter has sufficient capacity to supply the full rated gas input of the water heater as well as 

the requirements of all other gas fired equipment supplied by the meter. If gas meter is too small, ask the gas 

company to install a larger meter having adequate capacity. 

GAS PIPING AND SEDIMENT TRAP INSTALLATION

Fire and Explosion Hazard

Leak test before placing the water

heater in operation.
Disconnect gas piping and main gas

shutoff valve before leak testing.
Install sediment trap in accordance

with NFPA 54.

Use joint compound or Teflon tape

compatible with propane gas.

Any time work is done on the gas supply system perform a leak test to avoid the possibility of fire or explosion. 

1. For test pressures exceeding 1/2 psi (3.45 kPa) disconnect the water heater and its Main Gas Shutoff 

Valve from the gas supply piping system during testing, see Figure above. The gas supply line must be 

capped when disconnected from the water heater.
2. For test pressures of 1/2 psi (3.45 kPa) or less, the water heater need not be disconnected, but must 

be isolated from the supply gas line by closing the Main Gas Shutoff Valve during testing.
3. Coat all supply gas line joints and connections upstream of the water heater with a non-corrosive soap 

and water solution to test for leaks. Bubbles indicate a gas leak. Do not use matches, candles, flame or 

other sources of ignition for this purpose.
4. Repair any leaks before placing the water heater in operation. 

PURGING

Gas line purging is required with new piping or systems in which air has entered.
Purging should be performed per the current edition of NFPA 54 the National Fuel Gas Code.

Содержание BTR 118 SERIES

Страница 1: ...6 100277701_2000536453_Rev A 500 Tennessee Waltz Parkway Ashland City TN 37015 FOR MODELS BTR 120 thru 400 A Series 118 119 INSTALLATION CONSIDERATIONS PRE SERVICE CHECKS CONSTRUCTION OPERATION SERVIC...

Страница 2: ...ATION FLOW CHART 13 FAULT AND WARNING CODES 14 Ignition Module 14 Flue Damper 14 Diagnostics Codes Ignition Module BTR 118 119 Series 15 TROUBLESHOOTING CHECKLIST 17 GENERAL SERVICE CHART 18 FAULT AND...

Страница 3: ...ied as defined by ANSI above and licensed or certified as required by the authority having jurisdiction to perform a given task do not attempt to perform any of the procedures described in this servic...

Страница 4: ...al expansion can cause premature tank failure leakage This type of failure is not covered under the limited warranty Thermal expansion can also cause intermittent Temperature Pressure Relief Valve ope...

Страница 5: ...he National Fuel Gas Code ANSI Z223 1 and with the Category I Venting Tables If any part of the vent system is exposed to ambient temperatures below 40 F it must be insulated to prevent condensation D...

Страница 6: ...ith power vent kits for sidewall venting A O Smith offers power vent kits for use on installations with a maximum of 100 equivalent feet of vent piping The power vent kits also use type B vent materia...

Страница 7: ...W C for natural gas and 11 0 W C for propane gas The minimum supply pressure is measured while gas is flowing dynamic pressure The supply pressure should never fall below 4 5 W C for natural gas and...

Страница 8: ...as lines or emergency malfunction of the supply system the gas valve must be checked for safe operation Make sure that the outside vents on the supply regulators and the safety vent valves are protect...

Страница 9: ...eak test before placing the water heater in operation Disconnect gas piping and main gas shutoff valve before leak testing Install sediment trap in accordance with NFPA 54 Use joint compound or Teflon...

Страница 10: ...its are equipped with an automatic flue damper that reduces heat loss during the OFF cycles The automatic flue damper drive assembly is a field replaceable part and may be obtained by contacting A O S...

Страница 11: ...witch must be in the ON position to perform ohm continuity tests ON OFF switch replaced the gas cock on this new valve design GAS PRESSURE SPECIFICATIONS MODELS NATURAL BTR 120 400 PROPANE BTR 120 400...

Страница 12: ...tic controls would allow the gas control valve to remain open causing water temperature to exceed the thermostat setting The water temperature would continue to rise until high limit switch operation...

Страница 13: ...g checklist should be examined to eliminate obvious problems from those requiring replacement or servicing Check that main manual gas shut off valve is fully open and that gas service has not been int...

Страница 14: ...13 Servicing should only be performed by a Qualified Service Technician SEQUENCE OF OPERATION FLOW CHART...

Страница 15: ...Condensation on outside of tank normal Rumbling Sediment accumulation on bottom of tank Drain a quantity of water through drain valve If rumbling persists call a qualified service agency Delime heate...

Страница 16: ...ANSION TANK FAULTY VALVE REPLACE RELIEF VALVE LARGE VOLUME WATER RELIEF FROM T P VALVE EXCESSIVE WATER TEMPERATURE CHECK WIRING REPLACE DUAL CONTROLLER FAULTY RELIEF VALVE REPLACE RELIEF VALVE PREMATU...

Страница 17: ...VAC is supplied to the heater Make sure the tank is full of water Make sure the gas is supplied to the unit EFFIKAL DAMPER The wiring colors from the damper PC Board are different colors than the wire...

Страница 18: ...r 3 Yellow White 24V Common 4 Black CONDITION Damper closed High Limit closed FLUE DAMPER Do not turn damper open manually or motor damage will result use the service switch All readings are taken fro...

Страница 19: ...customer to have automatic heat until a replacement damper can be installed C DAMPER ROTATES CONTINUOUSLY Change the entire damper assembly D DAMPER STICKS 1 Make sure no screws obstruct the damper b...

Страница 20: ...AC is not present Check Wiring Harness to Thermostat 24VAC present Damper Opens Continue to Step 3 CONDITION Damper rotates continuously STEP 3 TEST THE THREE AMP FUSE CONDITION Test via the terminals...

Страница 21: ...s lights are not visible on the thermostat 24VAC out of the thermostat via the Yellow wire to ground is not present No Pilot or Main burner flame present Error indication LED light on the Honeywell mo...

Страница 22: ...TEP 5 WIRE HARNESS TEST CONDITION Damper Open no 24VAC to module 24VAC terminal Test for 24 VAC between terminal 24V on the IID module and 24V GND IF THEN 24VAC is present This is correct Continue to...

Страница 23: ...OT VALVE CONDITION 24VAC to module no pilot Using a multimeter test for 24 VAC between terminal PV and 24 V GND on the IID during the 90 second trial for ignition IF THEN The meter does not read 24 VA...

Страница 24: ...k for spark at the pilot assembly Note The pilot burner mounts on the left side of the main burner IF THEN The igniter is not sparking during the 90 second trial for ignition Check for A 7 64 spark ga...

Страница 25: ...ignal becomes a DC current that the module can interpret The pilot hood must be properly grounded and the pilot flame must remain in contact with both surfaces for the flame proving signal to remain c...

Страница 26: ...EST CONDITION Pilot Flame Noted No Sparking No Main Burner Using a multimeter test for 24 VAC between terminal MV on the IID and 24V GND IF THEN 24 VAC is not present Replace the IID module Check the...

Страница 27: ...chnician STEP 10 MAIN BURNER TEST CONDITION Pilot flame Noted Main burner Check Visually check for main burner IF THEN The main burner ignites Sequence is complete The main burner does not ignite Chec...

Страница 28: ...27 Servicing should only be performed by a Qualified Service Technician WIRING DIAGRAM BTR 118 119 SERIES...

Страница 29: ...28 Servicing should only be performed by a Qualified Service Technician WIRING DIAGRAM BTR 118 119 SERIES CONTROLS...

Страница 30: ...29 Servicing should only be performed by a Qualified Service Technician NOTES...

Страница 31: ...additional information contact A O Smith Corporation 500 Tennessee Waltz Parkway Ashland City TN 37015 Tech Support 800 527 1953 Parts 800 433 2545 www hotwater com Copyright 2016 A O Smith Water Hea...

Отзывы: