Servicing should only be performed by a Qualified Service Technician
STEP 7: PILOT SPARK TEST
CONDITION:
•
24VAC at PV, no pilot.
Visually/audibly check for spark at the pilot assembly.
Note:
The pilot burner mounts on the left side of the main burner.
IF
THEN
The igniter is not sparking during the 90 second trial
for ignition.
Check for:
•
A 7/64" spark gap.
•
Spark cable continuity.
•
Ground cable continuity.
•
Replace module.
Sparking is present.
•
Check the gas valve.
Power To Module May Be Interrupted To Reset.