A. O. Smith Water Products Company
Service Handbook
Irving, Texas 2000©
Training Department
4
EXTERIOR CLEARANCES
Horizontal Vent (using room air for combustion)
EXTERIOR CLEARANCES
Direct Vent
CAUTION
DO NOT TERMINATE THE VENTING WHERE NOISE FROM THE EXHAUST OF INTAKE WILL BE OBJECTIONABLE.
THIS INCLUDES LOCATIONS CLOSE TO OR ACROSS FROM WINDOWS AND DOORS. AVOID ANCHORING THE
VENT AND INTAKE PIPES DIRECTLY TO FRAMED WALLS, FLOORS OR CEILINGS UNLESS RUBBER ISOLATION
PIPE HANGERS ARE USED. THIS PREVENTS ANY VIBRATIONS FROM BEING TRANSMITTED INTO THE LIVING
SPACES.
When multiple units are direct vented through a wall, all intake vent terminals must be no lower than the
highest exhaust vent terminal.
Regulator
Gas
Meter
3' Min.
3' Above Any Forced
Air Intake Within 10'
4' Minimum
4' Minimum
4' Minimum
Exhaust
3' Minimum
From
Inside Corner
Recommended
Vent Hood Must Be
Mounted 4' Minimum
Below Doors and Windows
Vent Hood Must Be
Mounted
4'
Minimum
Below Windows
1' Above
Grade*
Vent Hood Must Be
Mounted 1' Minimum
Below Windows
*Recommended Clearance of 1' Above "Anticipated Snow Level" Where Applicable
Exhaust
Exhaust
Exhaust
Warning-
Vent Hood(s) May Be
Extremely Hot During
Operation
Regulator
Gas
Meter
3' Min.
1' Above
Grade*
3' Above Any Forced
Air Intake Within 10'
Vent Hood Must Be
Mounted
1'
Away
Horizontally From Doors
and Windows
Vent Hood Must Be
Mounted 9" Minimum
Above Doors
and Windows
3' Minimum From
Inside Corner
Recommended
*Recommended Clearance of 1' Above "Anticipated Snow Level" Where Applicable
Exhaust
Exhaust
Exhaust
Exhaust
Intake
Intake
Intake
Intake
Air
intake
(optional)
Intake Air Must Be
Mounted 1' Minimum
Below Windows
Exhaust 4"
Minimum
Warning-
Vent Hood(s) May Be
Extremely Hot During
Operation