background image

30

MOTOR WILL NOT RUN

1. Confirm 120V AC to the controller. Also, to verify correct polarity, check

for 120 V AC between hot supply and ground.

If there is no voltage, check for a loose connection where it connects to

the controller.

2. If there is 120 volts to the controller, check for loose connections or a

locked rotor. If the rotor cannot be freed the motor and blower assembly

must be replaced.

MOTOR RUNS, PREPURGE TIME ELAPSES BUT MAIN

FLAME NOT ESTABLISHED.

1. Check to see if main manual gas valve is open.

2. Check for a loose connection at the transformer, or a defective

transformer.

3. Check for a loose connection at the gas valve.

4. Check for open pressure switches or open reset button. Check for

blockage in the intake and exhaust venting or at the vent hoods. If no

blockage is found, check vinyl tubing for cuts or crimps. If this tubing is

damaged it must be replaced. If these steps do not eliminate the problem,

replace the pressure switches.

5. Check to see if there is resistance across the igniter terminal with an

OHM meter. If there is no continuity, the igniter is broken and should be

replaced.

If the igniter appears to function properly, then verify that the inlet

pressure is 14.0" W.C. maximum. The gas valve supplied on this appliance

is not designed to open against a higher pressure. At this time also

check that the inlet pressure is not lower than the minimal gas supply

pressure, as shown in Table 4: that is, for Natural Gas, 5.0" W.C. for

BTH 120 & 250 or 4.5" W.C. for BTH 150 & 199 or; for L.P. Gas, 11.0"

W.C. if the inlet pressure is not within these limits then adjust the supply

pressure accordingly.

If the inlet pressure falls within the allowable limits, then verify that the

manifold pressure, when the gas is fully open, with the heater running,

is as called out in Table 4:  that is, for Natural Gas, 4.0" W.C. for BTH 120

& 250 or 3.5" W.C. for BTH 150 & 199 or; for L.P. Gas, 10.0" W.C. If the

manifold pressure is not correct then adjust accordingly.  See

ADJUSTMENT PROCEDURE in OPERATING INSTRUCTIONS selection,

page 18, for the manifold pressure adjustment procedure.

6. If the inlet and manifold pressures are within the limits specified in step

5, then reset the appliance. Verify 24V AC at the gas valve during the

three (3) second ignition trial, after the igniter reaches operating

temperature. If 24V AC at the gas valve is not seen during this period,

the controller must be replaced.

If there is 24V AC at the gas valve during the four second ignition trial

and the manifold pressure does not increase above 0" W.C. then verify

that the manual gas control valve is in the “ON” position (see page 20).

If the valve is in the “ON” position and the previous voltage and gas

pressure conditions are met, then the gas valve is defective and must

be replaced.

Note that a positive manifold pressure reading of approximately 1.5"

W.C. is normal during the prepurge portion of the ignition cycle due to

the location of the gas orifice.

MOTOR RUNS, BURNER LIGHTS MOMENTARILY,

THEN LOCKS OUT

1. Reset the appliance two more times to ensure that all of the air has been

purged from the gas line.

2. If the burner lights momentarily but does not sustain ignition, verify that

the inlet pressure is not greater than 14.0" W.C. or lower than the

minimal gas supply pressure, as shown in Table 4: that is, for Natural

Gas, 5.0" W.C. for BTH 120 & 250 or 4.5" W.C. for BTH 150 & 199 or; for

L.P. Gas, 11.0" W.C. pressure. Also, the manifold pressure should rise

during the three (3) second trial for ignition to the manifold pressure

value for the individual unit listed in Table 4: that is, for Natural Gas, 4.0"

W.C. for BTH 120 & 250 or 3.5" W.C. for BTH 150 & 199 or; for L.P. Gas,

10.0" W.C. If the manifold pressure is not correct then adjust accordingly.

See ADJUSTMENT PROCEDURE in OPERATING INSTRUCTIONS section,

page 18, for the manifold pressure adjustment procedure.

3. Check for the reversed polarity in the supply wiring. This controller is

polarity sensitive. If the hot and neutral supply wires are reversed, the

controller will not sense flame. Reverse the supply wires and try to fire

the unit.

NOTE:  

Always turn off and disconnect main supply wiring before servicing

the unit.

4. Check connecting wire to the flame sensor. Verify that the flame sensor

has not been damaged in any way.

5. Verify that the air supply is adequate. The air inlet screen or blower

wheel may be restricted. Also, check the installation for proper ventilation.

See AIR REQUIREMENTS.

6. Check the venting system for the correct sizing, excess or insufficient.

See VENTING.

7. Check for a maximum inlet pressure of 14.0" W.C. and the manifold

pressure as listed in Table 4: that is, for Natural Gas, 4.0" W.C. for BTH

120 & 250 or 3.5" W.C. for BTH 150 & 199 or; for L.P. Gas, 10.0" W.C.

Please note that the manifold pressure listed is the maximum value for

the manifold pressure. Do not set the manifold pressure higher than the

value shown for your heater in Table 4. Overfiring the heater will result

in rough ignition and/or noisy operation.

8. Confirm that the air inlet screen (see Figures 7 & 8) is free of obstructions.

 

 

CAUTION

Do not reach into the burner housing or combustion chamber if the heater

is still hot. Allow the heater to cool and always use gloves as the combustion

chamber and the burner sleeve and housing can become very hot after

operation. Overfiring is a dangerous condition that must be corrected

immediately.

NOISY BURNER OPERATION

The exhaust of this unit produces some noise. This noise may be

objectionable if the exhaust terminal is located too close to the opening of

an occupied space. The noise may also be objectionable if the exhaust is

located in the confined space between two buildings such as an alley or

walkway. Since everyone's perception and tolerance for background noise

varies, there is no standard recommendation. The best option when the

noise is a concern is to locate the exhaust as far away from any occupied

spaces as practical.

If noise becomes more than one can tolerate, a dampening muffler is available

through our Product Service Division. See “REPLACEMENT PARTS” segment

below.

GAS FAILS TO SHUT OFF

Check for defective gas valve or thermostat. If operation is incorrect,

replace.

REPLACEMENT PARTS

Replacement parts may be ordered through A.O. Smith dealers, authorized

servicers or distributors. Refer to the Yellow Pages for where to call or

contact the A.O. Smith Water Products Company, 5621 W. 115th Street,

Alsip, IL  60482, 1-800-433-2545. When ordering parts be sure to state the

quantity, part number and description of the items including the complete

model and serial number as it appears on the product. Refer to the parts list

for more information.

Содержание BTH 120 - 250

Страница 1: ...any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier cal...

Страница 2: ...20 125 000 Nat 60 475 356 285 237 203 178 158 142 129 119 110 102 BTH 120 120 000 L P 60 456 342 274 228 195 171 152 137 124 114 105 98 BTH 150 150 000 Nat 100 570 427 342 285 244 214 190 171 155 142...

Страница 3: ...hecking the proper functioning of the heater In addition to these instructions the equipment shall be installed in accordance with those installation regulations in force in the local area where the i...

Страница 4: ...r may be able to make minor operational adjustments and save himself unnecessary service calls However the user should not attempt repairs which are not listed in this section WATERTEMPERATURECONTROL...

Страница 5: ...personal injury or death Do not apply insulation to the top or the upper 15 of the water heater as this will interfere with safe operation Do not cover the temperature pressure relief valve Do not cov...

Страница 6: ...TEDTOTHEOUTDOORS AND HAS ADEQUATE AIR SUPPLY TO AVOID RISKS OF IMPROPER OPERATION FIRE EXPLOSIONORASPHYXIATION VENT PIPE TERMINATION NOTE Before installing venting determine place of vent pipe termina...

Страница 7: ...E ON AIR INTAKE TERMINAL DIRECT VENT HORIZONTAL VENT FIGURE 6 DO NOT TERMINATE EXHAUST OVER PUBLIC AREA WHERE CONDENSATE OR VAPOR CAN CAUSE NUISANCE OR HAZARD EXHAUST VENT HOOD MUST BE LOCATED 1 MINIM...

Страница 8: ...n the vent system layout so that proper clearances are maintained from plumbing and wiring Vent pipes serving power vented appliances are classified by building codes as vent connectors Required clear...

Страница 9: ...the holes by drilling a hole through the center of the template from the inside through to the outside The template can now be positioned on the outside wall using the drilled holes as a centering po...

Страница 10: ...ith a plumbing roof boot or equivalent flashing 3 The intake vent termination and the exhaust vent termination must penetrate the same side of roof 4 The center line of the intake vent termination and...

Страница 11: ...intake and six 6 on the exhaust A 90 elbow is equal to five 5 equivalent feet of pipe One 1 90 elbow is equal to two 2 45 elbows Any venting configuration using less than 50 equivalent feet should use...

Страница 12: ...improvements have been made to strengthen the igniter it is still fragile and care must be taken when handling the igniter to prevent breakage GAS PIPING Contact your local gas service company to ensu...

Страница 13: ...rements of all other gas fired equipment supplied by the meter If the gas meter is too small ask the gas company to install a larger meter having adequate capacity GAS PRESSURE REGULATION Main line ga...

Страница 14: ...Sensitive If the Hot and Neutral Supply Voltage is reversed the controller will not sense flame Verify polarity before connecting the unit WATER LINE CONNECTIONS This manual provides detailed install...

Страница 15: ...the state of other system devices If the temperature drops below the setpoint value less differential the control will automatically return to step 2 and repeat the entire operating cycle During this...

Страница 16: ...ate 3 Not Implimented h s 240 Executed State 4 Not Implimented h s 210 Executed State 10 Not Implimented h s 213 Executed State 13 Not Implimented h s 214 Executed State 14 Not Implimented h s 216 Exe...

Страница 17: ...ol problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe PossibleCause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiring shorted...

Страница 18: ...unit is equipped with the correct orifice PRIOR TO START UP REQUIREDABILITY INSTALLATIONORSERVICEOFTHISWATERHEATERREQUIRESABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED PLUM...

Страница 19: ...19 FOR YOUR SAFETY READ BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life...

Страница 20: ...below 160 F HIGH ALTITUDE INSTALLATIONS WARNING BTH HEATERS ARE CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 6500 FEET INSTALLATIONS ABOVE 6500 FEET MAY REQUIREREPLACEMENTOFTHEBURNERORIF...

Страница 21: ...drain valve when finished flushing 4 Turn on the heater electrical disconnect switch DRAINING The heater must be drained if it is to be shut down and exposed to freezing temperatures Maintenance and s...

Страница 22: ...operation and a tank explosion In areas with poor water conditions it may be necessary to inspect the T P valve more often than every three years CAUTION BEFOREMANUALLYOPERATINGTHEVALVE MAKESURETHATA...

Страница 23: ...WATER SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVEORWATERMETERWITH CHECK VALVE PROVISIONS...

Страница 24: ...GER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 4 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT AD...

Страница 25: ...NIFOLD KIT SPECIFICATIONS PAGE28 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONSFORTHERMALEXPANSIONOFWATERINTHEHOTWATER SYSTEM MU...

Страница 26: ...RCULATINGLINEOF180 FORBOOSTEDWATER IF USED TOINLETWATERLINETOBOOSTER INSTALLINACCORDANCEWITHLOCALCODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULAT...

Страница 27: ...INTHETANK NOTE4 IFTEMPEREDWATERISRECIRCULATED RETURNLINESHOULD BECONNECTEDATPOINTA DANGER TEMPERATURESETTINGSHOULDNOTEXCEEDSAFETEMPERATUREAT FIXTURES SEEWATERTEMPERATURECONTROLWARNINGONPAGE5 IF HIGHER...

Страница 28: ...er heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold k...

Страница 29: ...leaned Refer to MAINTENANCE for details 2 Some of the electrical components of the water heater make sounds which are normal Contacts click or snap as the heater starts and stops Transformers often hu...

Страница 30: ...0 W C or lower than the minimal gas supply pressure as shown in Table 4 that is for Natural Gas 5 0 W C for BTH 120 250 or 4 5 W C for BTH 150 199 or for L P Gas 11 0 W C pressure Also the manifold p...

Страница 31: ...r the limited warranty the warrantor will provide only a replacement water heater or part thereof The owner is responsible for all other costs Such costs may include but are not limited to a Labor cha...

Страница 32: ...32 A O SMITH WATER PRODUCTS CO INC 5621 W 115TH STREET ALSIP ILLINOIS 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 WWW HOTWATER COM E MAIL PARTS HOTWATER COM...

Отзывы: