background image

2

Table 1.  RECOVERY CAPACITIES - NATURAL GAS / L.P

.

ROUGH-IN -DIMENSIONS

CYCLONE XHE BTH 120 - 250

Recovery capacities are based on heater performance at 94% thermal efficiency.

TEMPERATURE RISE - DEGREES °F - GALLONS PER HOUR

Model

BTU

Approx.

Input

Gallon

Capacity

30

40

50

60

70

80

90

100

110

120

130

140

BTH - 120

125,000 Nat.

60

475

356

285

237

203

178

158

142

129

119

110

102

BTH - 120

120,000  L.P.

60

456

342

274

228

195

171

152

137

124

114

105

98

BTH - 150

150,000 Nat.

100

570

427

342

285

244

214

190

171

155

142

132

122

BTH - 150

150,000  L.P.

100

570

427

342

285

244

214

190

171

155

142

132

122

BTH - 199

199,900 Nat.

100

759

569

456

380

325

285

253

228

207

190

175

163

BTH - 199

199,900  L.P.

100

759

569

456

380

325

285

253

228

207

190

175

163

BTH - 250

240,000 Nat.

100

912

684

547

456

391

342

304

274

248

228

210

195

Содержание BTH 120 - 250

Страница 1: ...any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier cal...

Страница 2: ...20 125 000 Nat 60 475 356 285 237 203 178 158 142 129 119 110 102 BTH 120 120 000 L P 60 456 342 274 228 195 171 152 137 124 114 105 98 BTH 150 150 000 Nat 100 570 427 342 285 244 214 190 171 155 142...

Страница 3: ...hecking the proper functioning of the heater In addition to these instructions the equipment shall be installed in accordance with those installation regulations in force in the local area where the i...

Страница 4: ...r may be able to make minor operational adjustments and save himself unnecessary service calls However the user should not attempt repairs which are not listed in this section WATERTEMPERATURECONTROL...

Страница 5: ...personal injury or death Do not apply insulation to the top or the upper 15 of the water heater as this will interfere with safe operation Do not cover the temperature pressure relief valve Do not cov...

Страница 6: ...TEDTOTHEOUTDOORS AND HAS ADEQUATE AIR SUPPLY TO AVOID RISKS OF IMPROPER OPERATION FIRE EXPLOSIONORASPHYXIATION VENT PIPE TERMINATION NOTE Before installing venting determine place of vent pipe termina...

Страница 7: ...E ON AIR INTAKE TERMINAL DIRECT VENT HORIZONTAL VENT FIGURE 6 DO NOT TERMINATE EXHAUST OVER PUBLIC AREA WHERE CONDENSATE OR VAPOR CAN CAUSE NUISANCE OR HAZARD EXHAUST VENT HOOD MUST BE LOCATED 1 MINIM...

Страница 8: ...n the vent system layout so that proper clearances are maintained from plumbing and wiring Vent pipes serving power vented appliances are classified by building codes as vent connectors Required clear...

Страница 9: ...the holes by drilling a hole through the center of the template from the inside through to the outside The template can now be positioned on the outside wall using the drilled holes as a centering po...

Страница 10: ...ith a plumbing roof boot or equivalent flashing 3 The intake vent termination and the exhaust vent termination must penetrate the same side of roof 4 The center line of the intake vent termination and...

Страница 11: ...intake and six 6 on the exhaust A 90 elbow is equal to five 5 equivalent feet of pipe One 1 90 elbow is equal to two 2 45 elbows Any venting configuration using less than 50 equivalent feet should use...

Страница 12: ...improvements have been made to strengthen the igniter it is still fragile and care must be taken when handling the igniter to prevent breakage GAS PIPING Contact your local gas service company to ensu...

Страница 13: ...rements of all other gas fired equipment supplied by the meter If the gas meter is too small ask the gas company to install a larger meter having adequate capacity GAS PRESSURE REGULATION Main line ga...

Страница 14: ...Sensitive If the Hot and Neutral Supply Voltage is reversed the controller will not sense flame Verify polarity before connecting the unit WATER LINE CONNECTIONS This manual provides detailed install...

Страница 15: ...the state of other system devices If the temperature drops below the setpoint value less differential the control will automatically return to step 2 and repeat the entire operating cycle During this...

Страница 16: ...ate 3 Not Implimented h s 240 Executed State 4 Not Implimented h s 210 Executed State 10 Not Implimented h s 213 Executed State 13 Not Implimented h s 214 Executed State 14 Not Implimented h s 216 Exe...

Страница 17: ...ol problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe PossibleCause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiring shorted...

Страница 18: ...unit is equipped with the correct orifice PRIOR TO START UP REQUIREDABILITY INSTALLATIONORSERVICEOFTHISWATERHEATERREQUIRESABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED PLUM...

Страница 19: ...19 FOR YOUR SAFETY READ BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life...

Страница 20: ...below 160 F HIGH ALTITUDE INSTALLATIONS WARNING BTH HEATERS ARE CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 6500 FEET INSTALLATIONS ABOVE 6500 FEET MAY REQUIREREPLACEMENTOFTHEBURNERORIF...

Страница 21: ...drain valve when finished flushing 4 Turn on the heater electrical disconnect switch DRAINING The heater must be drained if it is to be shut down and exposed to freezing temperatures Maintenance and s...

Страница 22: ...operation and a tank explosion In areas with poor water conditions it may be necessary to inspect the T P valve more often than every three years CAUTION BEFOREMANUALLYOPERATINGTHEVALVE MAKESURETHATA...

Страница 23: ...WATER SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVEORWATERMETERWITH CHECK VALVE PROVISIONS...

Страница 24: ...GER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 4 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT AD...

Страница 25: ...NIFOLD KIT SPECIFICATIONS PAGE28 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONSFORTHERMALEXPANSIONOFWATERINTHEHOTWATER SYSTEM MU...

Страница 26: ...RCULATINGLINEOF180 FORBOOSTEDWATER IF USED TOINLETWATERLINETOBOOSTER INSTALLINACCORDANCEWITHLOCALCODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULAT...

Страница 27: ...INTHETANK NOTE4 IFTEMPEREDWATERISRECIRCULATED RETURNLINESHOULD BECONNECTEDATPOINTA DANGER TEMPERATURESETTINGSHOULDNOTEXCEEDSAFETEMPERATUREAT FIXTURES SEEWATERTEMPERATURECONTROLWARNINGONPAGE5 IF HIGHER...

Страница 28: ...er heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold k...

Страница 29: ...leaned Refer to MAINTENANCE for details 2 Some of the electrical components of the water heater make sounds which are normal Contacts click or snap as the heater starts and stops Transformers often hu...

Страница 30: ...0 W C or lower than the minimal gas supply pressure as shown in Table 4 that is for Natural Gas 5 0 W C for BTH 120 250 or 4 5 W C for BTH 150 199 or for L P Gas 11 0 W C pressure Also the manifold p...

Страница 31: ...r the limited warranty the warrantor will provide only a replacement water heater or part thereof The owner is responsible for all other costs Such costs may include but are not limited to a Labor cha...

Страница 32: ...32 A O SMITH WATER PRODUCTS CO INC 5621 W 115TH STREET ALSIP ILLINOIS 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 WWW HOTWATER COM E MAIL PARTS HOTWATER COM...

Отзывы: