background image

10

3/8" drain hose can be connected to the built-in drain port of 

the rubber boot on the blower assembly. For your convenience, 

the rubber boot is supplied with a removable cap on the built-in 

drain port. Prior to operating the water heater, make sure the 

removable cap is installed on the drain port (if a drain hose is 

not needed).

INSTALLATION OF VENT SYSTEM

Before beginning installation of piping system thoroughly read the 

section of this manual VENT PIPE PREPARATION.

If you are installing your system so that it vents through roof, please 

refer  to  following  section  titled  INSTALLATION  OF  VERTICAL 

VENT SYSTEM.

VENT TERMINAL INSTALLATION, SIDEWALL

1.  Install the vent terminal by using the cover plate as a template 

to mark the hole for the vent pipe to pass through the wall.  

BEWARE  OF  CONCEALED  WIRING AND  PIPING  INSIDE 

THE WALL.

2.  If the Vent Terminal is being installed on the outside of a finished 

wall, it may be easier to mark both the inside and outside wall.  

Align  the  holes  by  drilling  a  hole  through  the  center  of  the 

template from the inside through to the outside.  The template 

can now be positioned on the outside wall using the drilled hole 

as a centering point for the template.

3.  A)  MASONRY SIDE WALLS

  Chisel an opening approximately one half inch (13 mm) larger 

than the marked circle.

  B)  WOODEN SIDE WALLS

  Drill a pilot  hole approximately one quarter inch (6.4 mm) outside 

of the marked circle.  This pilot hole is used as a starting point 

for a saws-all or sabre saw blade.  Cut around the marked circle 

staying approximately one quarter inch (6.4 mm) outside of the 

line.  (This will allow the vent to easily slide through the opening.  

The resulting gap will be covered up by the Vent Terminal cover 

plate.)  Repeat this step on inside wall if necessary.

SEQUENCE OF INSTALLATIONS, FIGURE 5

Cut a length of 3" PVC pipe about 3.5 inches (8.9 cm) longer 

than the wall thickness at the opening.  Glue the vent terminal  

"45° Elbow" with screen to this section of pipe.  Slide the wall 

plate over the pipe to stop against "45° Elbow".  Place a bead 

of caulking (not supplied) around the gap between the pipe and 

cover plate.  Apply enough to fill some of the gap between the 

pipe and wall.  Place some of the caulking on the back of the 

plate to hold it against the wall after installation.  If the vent pipe 

is installed up to the wall, with a coupling on the end against the 

wall opening, the pipe with the vent terminal can be prepared for 

gluing before inserting through the wall.  Slide the pipe through 

the wall and insert into the coupling on the other side of the wall, 

making sure that the vent terminal ends up pointed in the correct 

position.  (See figure 5).

VENT TERMINATION - FIGURE 5

PREPARATION OF BLOWER ASSEMBLY

1.  Check to make sure that the wire harness is attached to the 

gas valve and blower control box.

2.  Make sure no material is still attached to the outside or inside 

of blower assembly.

FIGURE 6

3.  Make sure that plastic tubing is still attached to the pressure 

switch and fan housing.  Also make sure that wiring connector 

from motor to control box is securely attached.

4.  Do  not  plug  in  power  cord  until  vent  system  is  completely 

installed. The  Power  Vent  operates  on  120  Vac,  therefore 

a  grounded  outlet  must  be  within  reach  of  the  6  foot

 

(1.8 m) flexible power cord supplied with the vent (see figure 

1). The power cord supplied may be used on unit only where 

local codes permit. If local codes do not permit use of flexible 

power supply cord:

  A.   Remove screws that hold cover plate on control box and 

remove plate.

  B.  Cut flexible power cord on inside of control box, as close 

to inside wall as possible.

  C.  If flexible cord and strain relief are removed, then opening 

in box must be covered by a plastic cap on the front side 

of the control box.

  D.  Remove plastic cap on the right side of control box and 

install suitable conduit fitting in enclosure.

  E.  Splice field wiring into existing wiring using code authorized 

method (wire nuts, etc.).

  F.  Be certain that neutral and line connections are not reversed 

when making these connections.

  G.  Ground  heater  properly.  This  water  heater  must  be 

grounded in accordance with the National Electrical Code 

NFPA 70 or the Canadian Electrical Code CSA C22.1 and/

or local codes. These must be followed in all cases.

   

The water heater must be connected to a grounded metal, 

permanent  wiring  system;  or  an  equipment  grounding 

conductor  must  be  run  with  the  circuit  conductors  and 

connected to the equipment grounding terminal or lead on 

the water heater, see Figure 7.

  H.  Replace cover plate and secure with two screws.

MUST  INSTALL  MINIMUM  OF  2"  

(5.1 cm) LONG PIECE OF 3" PIPE INTO 

ELBOW  TO  MOUNT  ON  BLOWER 

DISCHARGE ADAPTER.    MAXIMUM 

LENGTH FOUR (4) FEET (1.2 m).

Содержание BTF-80

Страница 1: ...ONS CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE MODEL BTF 80 COMMERCIAL POWER VENT GAS WATER...

Страница 2: ...These shall be carefully followed in all cases Authorities having jurisdiction should be consulted before installations are made The installation must conform to these instructions and the local code...

Страница 3: ...at 500 Tennessee Waltz Parkway Ashland City TN 37015 When ordering parts provide complete model and serial numbers see rating plate quantity and name of part desired as listed in Figure 1 Standard har...

Страница 4: ...the air flow required for proper combustion potentially resulting in fire asphyxiation serious personal injury or death Do not cover the gas valve or temperature pressure relief valve Do not allow in...

Страница 5: ...learance of 4 10 cm must be allowed for access to replaceable parts such as the thermostats drain valve and relief valve A top clearance of 24 61 cm should be allowed for blower assembly service Adequ...

Страница 6: ...st be checked for safe operation Make sure that the outside vents on the supply regulators and the safety vent valves are protected against blockage These are parts of the gas supply system not the he...

Страница 7: ...7 FIGURE 3 WARNING VENT HOOD S MAY BE EXTREMELY HOT DURING OPERATION U S HORIZONTAL VENT CLEARANCES CANADIAN HORIZONTAL VENT CLEARANCES...

Страница 8: ...ION CHECK FOR GAS LEAKAGE USE SOAP AND WATER SOLUTION OR OTHER MATERIAL ACCEPTABLE FOR THIS PURPOSE DO NOT USE MATCHES CANDLES FLAME OR OTHER SOURCES OF IGNITION TO LOCATE GAS LEAKS RELIEF VALVE A NEW...

Страница 9: ...1785 or Cellular Core Schedule 40 DWV ASTM F 891 Schedule 40 CPVC ASTM F 441 orABS ASTM D 2661 pipe The fittings other than the TERMINATION 45 ELBOW should be equivalent to PVC DWV fittings meetingAS...

Страница 10: ...against the wall after installation If the vent pipe is installed up to the wall with a coupling on the end against the wall opening the pipe with the vent terminal can be prepared for gluing before...

Страница 11: ...OWER VENT WIRING SCHEMATIC FIGURE 7 CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVIC...

Страница 12: ...e where it exits the roof The total vent system should not exceed the thirty 30 equivalent feet 9 1 equivalent meters of 3 inch pipe or one hundred 100 equivalent feet 30 5 equivalent meters of 4 inch...

Страница 13: ...ing characteristics IMPORTANT NOTE A dauber type applicator should only be used on pipe sizes 2 5 1 cm and below For larger diameter pipe a brush or roller must be used 3 MAKING THE JOINT A Cutting Pi...

Страница 14: ...tting will have a tendency to slide back while the cement is still wet so hold the joint together for about 15 seconds STEP F G Cleanup and joint movement Remove all excess cement from around the pipe...

Страница 15: ...follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life BEFORE OPERATING ENTIRE SYSTEM MUST BE FILLED WITH WATER AND AIR PURGED FROM AL...

Страница 16: ...RESPONSE TIME OF CHILDREN AGED OR DISABLED PERSONS INCREASES THE HAZARDS TO THEM NEVER ALLOW SMALL CHILDREN TO USE A HOT WATER TAP OR TO DRAW THEIR OWN BATH WATER NEVER LEAVE A CHILD OR DISABLED PERS...

Страница 17: ...heater for several minutes and check to see if it is venting properly by passing a lit match or paper near the opening of the Air Mixing Box See figure 11 If the draft is proper the match flame will b...

Страница 18: ...oted above If you are having a problem with your water heater before calling for service please refer to the following TROUBLE SHOOTING sections If service becomes necessary contact your dealer instal...

Страница 19: ...r service to outlet Replace switch Replace control harness Replace blower and motor Replace switch Check for low voltage less than 102 vac have service checked and repaired Ifvoltageisabove102vac make...

Страница 20: ...circuit 1 Turn power to the water heater off for 10 seconds and then back on 2 Replace gas control valve Problem with the internal circuit 1 Turn power to the water heater off for 10 seconds and then...

Страница 21: ...21 NOTES...

Страница 22: ...22 NOTES...

Страница 23: ...23 NOTES...

Страница 24: ...eptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warrantor will provide only a replacement water heater or part thereof The owner is responsible for all other costs Such cos...

Отзывы: